Plan Review Details - Permit 14010472
Plan Review Stops For Permit 14010472
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-06-19 Cont ID  
Sent By skennedy Date 2014-06-19 Time 12:07 Rev Time 0.00
Received By skennedy Date 2014-06-19 Time 12:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-28 Cont ID  
Sent By skennedy Date 2014-05-28 Time 08:51 Rev Time 0.00
Received By skennedy Date 2014-05-28 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 07:25 Rev Time 0.00
Received By skennedy Date 2014-05-17 Time 07:25 Sent To  
Notes
2014-05-17 07:25:531ST REVIEW:
  
 THE APPLICANT HAS UPLOADED TWO SEPARATE DESIGNS FOR THE
 SPACE. PLEASE RESUBMIT WITH THE DESIGN YOU PLAN TO
 CONSTRUCT ONLY. NO REVIEW CAN PROCEED UNTIL THIS MATTER
 IS CLARIFIED. DO THIS FOR THE ENTIRE FILE REGARDLESS OF
 APPROVAL IN MECHANICAL AND FIRE.
  
 THANK YOU,
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 (561) 805-6710
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2014-04-21 Cont ID  
Sent By skennedy Date 2014-04-21 Time 13:43 Rev Time 0.00
Received By skennedy Date 2014-04-21 Time 13:43 Sent To  
Notes
2014-04-21 13:46:41NO REVIEW, REDESIGN TO BE RESUBMITTED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-05-27 Cont ID  
Sent By albarran Date 2014-05-27 Time 16:38 Rev Time 0.00
Received By albarran Date 2014-05-27 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-05-06 Cont ID  
Sent By albarran Date 2014-05-06 Time 18:44 Rev Time 0.00
Received By albarran Date 2014-05-06 Time 15:11 Sent To  
Notes
2014-05-06 18:47:08THESE DRAWINGS ARE NOT A MATCH ALL THE WAY THROUGH.
 SEVERAL CHANGES HAVE BEEN MADE ON INDIVIDUAL PAGES W/O
 CORRECTING THE SUBSEQUENT PAGES. SEE ELECTRICAL COMMENT
 LAYER FOR DETAILS.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-04-21 Cont ID  
Sent By skennedy Date 2014-04-21 Time 13:46 Rev Time 0.00
Received By skennedy Date 2014-04-21 Time 13:46 Sent To  
Notes
2014-04-21 13:48:27NO REVIEW, REDESIGN TO BE RESUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2014-06-25 Cont ID  
Sent By wjolin Date 2014-06-25 Time 17:46 Rev Time 0.00
Received By wjolin Date 2014-06-25 Time 17:05 Sent To  
Notes
2014-06-25 17:46:141835 OKEECHOBEE ROAD
 PERMIT #14010472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NEW COMMENT - SHEET A3.1: IN LIEU OF PANIC HARDWARE
 (EXISTING STORE FRONT DOORS), KEY OPERATED LOCKS ARE
 PERMISSIBLE ON THE MAIN ENTRANCE DOOR(S) IF THE
 FOLLOWING IS PROVIDED:
 (1) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1-INCH HIGH ON A CONTRASTING BACKGROUND THAT READS
 AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED.
 (2) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED (EQUIVALENT TO ADAMSRITE
 #4089)
 (3) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-05-23 Cont ID  
Sent By wjolin Date 2014-05-23 Time 10:07 Rev Time 0.00
Received By wjolin Date 2014-05-23 Time 10:02 Sent To  
Notes
2014-05-23 10:07:291835 OKEECHOBEE ROAD
 PERMIT #14010472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - SHEET A1.2: INDICATE THE COMMODITIES
 THAT WILL BE STORED (FLOOR AND RACKING SYSTEM) AND THE
 INTENDED HEIGHT OF STORAGE. NOTE: STORAGE EXCEEDING 12
 FEET IN ELEVATION IS CONSIDERED HIGH-PILED STORAGE AND
 MAY REQUIRE SPECIAL SPRINKLER PROTECTION.
  
 REPEAT COMMENT - SHEET A3.1: PANIC HARDWARE WILL BE
 REQUIRED ON ALL NEW AND EXISTING EXIT AND EXIT ACCESS
 DOORS DUE TO THE ASSEMBLY OCCUPANT LOAD EXCEEDING 100
 PERSONS (50 PERSONS PER FBC) AND USING THE MIXED
 NON-SEPARATED OCCUPANCY DESIGN (PER THE COVER SHEET
 DESCRIPTION). IF SEPARATED OCCUPANCIES ARE DESIRED, THE
 ASSEMBLY AND BUSINESS OCCUPANCIES WOULD BE PROHIBITED
 FROM HAVING TO EXIT THROUGH THE STORAGE OCCUPANCY AS IS
 CURRENTLY SHOWN.
  
 REPEAT COMMENT - GENERAL: PER SECTION 8.3.2.4, EACH
 FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS
 OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 REPEAT COMMENT - GENERAL: NO FIRE PROTECTION
 ENGINEERING DOCENTS SUBMITTED. FOR ISSUANCE OF A
 GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE
 FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING,
 "FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-04-25 Cont ID  
Sent By wjolin Date 2014-04-25 Time 17:37 Rev Time 0.00
Received By wjolin Date 2014-04-25 Time 17:22 Sent To  
Notes
2014-04-25 17:37:121835 OKEECHOBEE ROAD
 PERMIT #14010472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - SHEET A1.2: INDICATE THE COMMODITIES
 THAT WILL BE STORED (FLOOR AND RACKING SYSTEM) AND THE
 INTENDED HEIGHT OF STORAGE. NOTE: STORAGE EXCEEDING 12
 FEET IN ELEVATION IS CONSIDERED HIGH-PILED STORAGE AND
 MAY REQUIRE SPECIAL SPRINKLER PROTECTION.
  
 REPEAT COMMENT - SHEET A3.1: PANIC HARDWARE WILL BE
 REQUIRED ON ALL NEW AND EXISTING EXIT AND EXIT ACCESS
 DOORS DUE TO THE ASSEMBLY OCCUPANT LOAD EXCEEDING 100
 PERSONS (50 PERSONS PER FBC) AND USING THE MIXED
 NON-SEPARATED OCCUPANCY DESIGN (PER THE COVER SHEET
 DESCRIPTION). IF SEPARATED OCCUPANCIES ARE DESIRED, THE
 ASSEMBLY AND BUSINESS OCCUPANCIES WOULD BE PROHIBITED
 FROM HAVING TO EXIT THROUGH THE STORAGE OCCUPANCY AS IS
 CURRENTLY SHOWN.
  
 REPEAT COMMENT - GENERAL: PER SECTION 8.3.2.4, EACH
 FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS
 OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 REPEAT COMMENT - GENERAL: NO FIRE PROTECTION
 ENGINEERING DOCENTS SUBMITTED. FOR ISSUANCE OF A
 GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE
 FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 REPEAT COMMENT - DEMO: PROVIDE DRAWING NOTE INDICATING,
 "FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-01-17 Cont ID  
Sent By wjolin Date 2014-01-17 Time 11:19 Rev Time 0.00
Received By wjolin Date 2014-01-17 Time 09:21 Sent To  
Notes
2014-01-17 11:19:191835 OKEECHOBEE ROAD
 PERMIT #14010472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.2: INDICATE THE COMMODITIES THAT WILL BE
 STORED (FLOOR AND RACKING SYSTEM) AND THE INTENDED
 HEIGHT OF STORAGE. NOTE: STORAGE EXCEEDING 12 FEET IN
 ELEVATION IS CONSIDERED HIGH-PILED STORAGE AND MAY
 REQUIRE SPECIAL SPRINKLER PROTECTION.
  
 SHEET A3.1: PANIC HARDWARE WILL BE REQUIRED ON ALL NEW
 AND EXISTING EXIT AND EXIT ACCESS DOORS DUE TO THE
 ASSEMBLY OCCUPANT LOAD EXCEEDING 100 PERSONS (50
 PERSONS PER FBC) AND USING THE MIXED NON-SEPARATED
 OCCUPANCY DESIGN (PER THE COVER SHEET DESCRIPTION). IF
 SEPARATED OCCUPANCIES ARE DESIRED, THE ASSEMBLY AND
 BUSINESS OCCUPANCIES WOULD BE PROHIBITED FROM HAVING TO
 EXIT THROUGH THE STORAGE OCCUPANCY AS IS CURRENTLY
 SHOWN.
  
 SHEET FA2.1: NO FIRE ALARM NOTIFICATION APPLIANCE
 LOCATED AT THE SOUTHEAST AREA OF THE SPACE.
  
 GENERAL: PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 GENERAL: NO FIRE PROTECTION ENGINEERING DOCENTS
 SUBMITTED. FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 DEMO: PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION
 AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 DEMO: PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-06-27 Cont ID  
Sent By skennedy Date 2014-07-03 Time 13:04 Rev Time 0.00
Received By skennedy Date 2014-06-06 Time 21:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-28 Cont ID  
Sent By hmoser Date 2014-05-28 Time 11:42 Rev Time 0.00
Received By hmoser Date 2014-05-28 Time 11:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 07:26 Rev Time 0.00
Received By skennedy Date 2014-04-21 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-21 Cont ID  
Sent By rregueir Date 2014-01-21 Time 10:02 Rev Time 0.00
Received By rregueir Date 2014-01-09 Time 15:45 Sent To  
Notes
2014-01-21 10:03:02REVIEW CYCLE CLOSED DUE TO CUSTOMER REQUEST. SEE EMAIL
 ATTACHED TO PERMIT RECORD.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 07:09 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-04-21 Cont ID  
Sent By skennedy Date 2014-04-21 Time 13:47 Rev Time 0.00
Received By skennedy Date 2014-04-21 Time 13:47 Sent To  
Notes
2014-04-21 13:48:11NO REVIEW, REDESIGN TO BE RESUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2014-06-26 Cont ID  
Sent By hmoser Date 2014-06-26 Time 09:28 Rev Time 0.00
Received By hmoser Date 2014-06-26 Time 09:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-05-28 Cont ID  
Sent By hmoser Date 2014-05-28 Time 11:41 Rev Time 0.00
Received By hmoser Date 2014-05-28 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-05-14 Cont ID  
Sent By hmoser Date 2014-05-14 Time 13:18 Rev Time 0.00
Received By hmoser Date 2014-05-14 Time 13:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-01-09 Cont ID  
Sent By rregueir Date 2014-01-09 Time 16:56 Rev Time 0.00
Received By rregueir Date 2014-01-09 Time 16:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-05-28 Cont ID  
Sent By skennedy Date 2014-05-28 Time 08:42 Rev Time 0.00
Received By skennedy Date 2014-05-28 Time 08:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-05-17 Cont ID  
Sent By skennedy Date 2014-05-17 Time 07:21 Rev Time 0.00
Received By skennedy Date 2014-05-17 Time 07:09 Sent To  
Notes
2014-05-17 07:25:111ST REVIEW:
  
 THE APPLICANT HAS UPLOADED TWO SEPARATE DESIGNS FOR THE
 SPACE. PLEASE RESUBMIT WITH THE DESIGN YOU PLAN TO
 CONSTRUCT ONLY. NO REVIEW CAN PROCEED UNTIL THIS MATTER
 IS CLARIFIED. DO THIS FOR THE ENTIRE FILE REGARDLESS OF
 APPROVAL IN MECHANICAL AND FIRE.
  
 THANK YOU,
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 (561) 805-6710
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-04-21 Cont ID  
Sent By skennedy Date 2014-04-21 Time 13:47 Rev Time 0.00
Received By skennedy Date 2014-04-21 Time 13:47 Sent To  
Notes
2014-04-21 13:48:41NO REVIEW, REDESIGN TO BE RESUBMITTED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2014-07-02 Cont ID  
Sent By skennedy Date 2014-07-02 Time 07:57 Rev Time 0.00
Received By skennedy Date 2014-07-02 Time 07:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By skennedy Date 2014-07-01 Time 07:27 Rev Time 0.00
Received By skennedy Date 2014-06-30 Time 07:06 Sent To  
Notes
2014-07-01 07:27:48PEDDS MISSING FOR SHEETS GN, D1.1, A1.2, A3.2, A4.1, &
 A4.2.