Plan Review Details - Permit 14010467
Plan Review Stops For Permit 14010467
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-01-15 Cont ID  
Sent By rmcdouga Date 2014-01-15 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2014-01-15 Time 17:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-02-07 Cont ID  
Sent By skennedy Date 2014-02-07 Time 09:12 Rev Time 0.00
Received By skennedy Date 2014-02-07 Time 08:22 Sent To  
Notes
2014-02-07 09:14:22PROVISO:
 1) PROVIDE LISTING AND MANUFACTURERS SPECIFICATION
 SHEET ON EQUIPMENT VAULT.
 2) PROVIDE BONDING GRID AND BOND ALL METAL PARTS PER
 NEC 680.
 3) PROVIDE FEEDER VOLTAGE DROP CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-01-23 Cont ID  
Sent By skennedy Date 2014-01-23 Time 11:14 Rev Time 0.00
Received By skennedy Date 2014-01-23 Time 11:14 Sent To Z
Notes
2014-01-23 15:20:59PROVIDE A MORE COMPREHENSIVE SITE PLAN SO THAT THE
 LOCATION OF THE WATER FEATURE CAN BE DETERMINED IN
 RELATION TO THE ELECTRICAL SERVICE FEEDING THE
 EQUIPMENT. PROVIDE ELECTRICAL DETAILS AS TO THE PANEL
 AND BRANCH CIRCUIT(S) FEEDING THE VAULT. PROVIDE
 INFORMATION ON WIRE SIZE & OVERCURRENT PROTECTION.
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-01-15 Cont ID  
Sent By rmcdouga Date 2014-01-15 Time 17:17 Rev Time 0.00
Received By rmcdouga Date 2014-01-15 Time 17:17 Sent To  
Notes
2014-01-15 17:17:49NO GAS SHOWN ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-07 Cont ID  
Sent By skennedy Date 2014-02-07 Time 09:14 Rev Time 0.00
Received By skennedy Date 2014-02-06 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-31 Cont ID  
Sent By skennedy Date 2014-01-31 Time 16:58 Rev Time 0.00
Received By skennedy Date 2014-01-09 Time 08:56 Sent To  
Notes
2014-01-11 08:58:26B10
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-15 Cont ID  
Sent By rmcdouga Date 2014-01-15 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2014-01-15 Time 17:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-31 Cont ID  
Sent By eschneid Date 2014-01-31 Time 09:03 Rev Time 0.50
Received By eschneid Date 2014-01-31 Time 09:03 Sent To E
Notes
2014-01-31 09:04:49PASSED W/PROVISO
  
 ALL FOUNTAIN EQUIPMENT, INCLUDING THE BACKFLOW
 PREVENTER, SHALL BE SCREENED.
2014-01-27 14:27:201/27/14