Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 06:35 Rev Time 0.00
Received By rmcdouga Date 2014-01-08 Time 06:35 Sent To  
Notes
2014-01-08 17:13:272010 FBC
  
 REVISION DENIED BY BUILDING
  
 1) NOTE #7 ON THE DRAWING FROM TURQUOISE ENGINEERING
 SPECIFIES A SIMPSON LTT19 STRAP ANCHORED THROUGH THE
 TOP PLATE INTO THE TIE BEAM WITH A 1/2" X 4" TITEN
 ANCHOR. THIS IS DESIGNED AND TESTED AS TENSION STRAP
 AND THE TENSION VALUE IS THE ONLY ONE THAT IS PROVIDED.
 THE LTT19 STRAP IS NOT DESIGNED TO BE USED TO ANCHOR
 ROOF TRUSSES, WHICH ARE REQUIRED TO RESIST LATERAL
 LOADS IN ADDITION TO UPLIFT. SPECIFY A CONNECTOR THAT
 HAS BEEN DESIGNED, TESTED AND APPROVED TO USED TO
 ANCHOR ROOF TRUSSES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-03 Cont ID  
Sent By rmcdouga Date 2014-01-03 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2014-01-03 Time 16:22 Sent To  
Notes
2014-01-03 16:59:012010 FBC
  
 REVISION DENIED BY BUILDING
  
 1) PROVIDE THE VALUE FOR THE INCREASED SCOPE OF WORK,
 INCLUDE DESIGN COSTS. CITY AMENDMENTS 109.3
  
 2) THE ROOF FRAMING REPAIR DETAIL DRAWINGS FROM RIZA N.
 ALTAN, PE # 38521. BECAUSE HE IS NOT THE DESIGNER OF
 RECORD FOR THIS PROJECT, HIS DRAWINGS WILL NEED TO HAVE
 A SHOP DRAWING REVIEW STAMP FROM THE DESIGNER OF
 RECORD, ROBERT F. SONBERG, AR #6280 OR A LETTER FROM
 HIM DELEGATING THE SCOPE OF WORK SHOWN IN THE
 ENGINEER'S DRAWINGS TO HIM. FS 471, 481 AND CITY
 AMENDMENTS 107.1
  
 3) NOTE #7 ON THE DRAWING FROM TURQUOISE ENGINEERING
 REQUIRES BENDING A SIMPSON ST18 STRAP 90 DEGREES AND
 ANCHORING IT THROUGH THE TOP PLATE INTO THE TIE BEAM
 WITH A TAPCON. THIS IS NOT AN ACCEPTABLE APPLICATION
 FOR THIS STRAP. PLEASE SPECIFY A CONNECTOR THAT HAS
 BEEN DESIGNED, TESTED AND APPROVED FOR THE SPECIFIC
 APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 06:36 Rev Time 0.00
Received By rmcdouga Date 2014-01-07 Time 17:42 Sent To  
Notes
2014-01-07 17:43:31INCOMING SENT TO R MCDOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-03 Cont ID  
Sent By rmcdouga Date 2014-01-03 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2014-01-03 Time 16:21 Sent To  
Notes
2014-01-03 16:21:34TO R MCDOUGAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved