Plan Review Details - Permit 13121113
Plan Review Stops For Permit 13121113
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-12-31 Cont ID  
Sent By rmcdouga Date 2013-12-31 Time 06:13 Rev Time 0.00
Received By rmcdouga Date 2013-12-31 Time 06:13 Sent To  
Notes
2014-01-02 14:41:08SENT TO FIRE
2013-12-30 20:01:35MCDUGAL

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-07 Cont ID  
Sent By albarran Date 2014-01-07 Time 08:32 Rev Time 0.00
Received By albarran Date 2014-01-07 Time 08:17 Sent To FIRE
Notes
2014-01-07 08:34:04I MET WITH THE DESIGN PROFESSIONAL TO DISCUSS THE
 REQUIRED CHANGES. HE RED LINED AND SIGNED THE CHANGES
 ON THE PLANS.
 ALL WORK WILL BE SUBJECT TO FIELD INSPECTOR'S APPROVAL
  
2014-01-02 14:33:35INSERTED UPDATED ELECTRICAL RESUBMITTED ON 01/02/14.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-30 Cont ID  
Sent By albarran Date 2013-12-30 Time 19:52 Rev Time 0.00
Received By albarran Date 2013-12-30 Time 19:35 Sent To B
Notes
2013-12-30 20:00:27THE FOLLOWING ELECTRICAL CORRECTIONS HAVE TO BE MADE TO
 THE SUBMITTED DRAWINGS:
 1. INDICATE FROM WHICH OF THE THREE TRANSFORMER SHOWN
 ON THE PLANS IS THE SERVICE IN QUESTION BEING SERVED.
 2. INDICATE IF THE FEEDERS ARE OVERHEAD OR UNDERGROUND,
 THE DRAWING LEADS ME TO BELIEVE THESE ARE TRANSFORMER
 PADS ON THE GROUND, AND THE RISER DIAGRAM REFLECTS
 SERVICE FROM OVERHEAD.
 3. THERE IS A CONFLICT BETWEEN ELECTRICAL NOTE 5 AND
 THE RISER DIAGRAM.
 4. THE RISER DIAGRAM APPEARS TO VIOLATE THE
 REQUIREMENTS OF NEC 300.5(B)
 5. INDICATE ON THE PLANS THE INTENDED WIRING METHOD
 APPLIED TO SERVE THE NEW RECEPTACLES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-07 Cont ID  
Sent By wjolin Date 2014-01-07 Time 11:26 Rev Time 0.00
Received By wjolin Date 2014-01-07 Time 11:15 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-07 Cont ID  
Sent By rmcdouga Date 2014-01-07 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2013-12-30 Time 18:54 Sent To  
Notes
2013-12-30 18:55:10C19

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-03 Cont ID  
Sent By avann Date 2014-01-03 Time 15:59 Rev Time 0.00
Received By ajones Date 2014-01-03 Time 15:59 Sent To  
Notes
2014-01-02 12:12:181/2/14