Plan Review Details - Permit 13121099
| Plan Review Stops For Permit 13121099 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-04-28 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-28 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-28 |
Time |
13:24 |
Sent To |
I |
|
| Notes |
| 2014-04-28 13:48:38 | PER NFPA 72, SECTION 4.4, THE DEDICATED FIRE ALARM | | | CIRCUIT BREAKER SHALL BE MARKED IN RED AND IDENTIFIED | | | AS ?FIRE ALARM CIRCUIT? AND BE MECHANICALLY | | | PROTECTED.NOTICE TO FIRE ALARM CONTRACTOR: | | | ALL DOCUMENTATION AS REQUIRED PER NFPA 72 SECTION 4.5 | | | SHALL BE PROVIDED UPON COMPLETION AND BE AVAILABLE FOR | | | FINAL INSPECTION. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-01-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-01-14 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-01-14 |
Time |
15:23 |
Sent To |
I |
|
| Notes |
| 2014-01-14 16:58:31 | THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE | | | SUBMITTED DRAWINGS FOR THE NEXT REVIEW: | | | 1. THE MANUAL PULL STATIONS IN RETAIL SPACES 1 & 2 DO | | | NOT MEET THE REQUIREMENTS OF SECTION 5.13.7 OF THE 2007 | | | EDITION OF THE NFPA 72 | | | 2. THE NOTIFICATION APPLIANCES AS INDICATED ON THE | | | DRAWINGS FOR CONDO SPACE 111 AND RETAIL SPACES 1 & 2 DO | | | NOT MEET THE REQUIREMENTS OF CHAPTER 7 OF THE 2007 | | | EDITION OF THE NFPA 72 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-04-21 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-04-21 |
Time |
14:58 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-12-30 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-12-30 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-12-30 |
Time |
10:33 |
Sent To |
E |
|
| Notes |
| 2013-12-30 10:38:15 | PERMIT #13121099 | | | MASTER #13050713 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ***FAIL COMMENTS*** | | | F/A GROUND FLOOR PLAN: ADDITTIONAL DEVICES ARE NEEDED | | | IN CONDO SPACE (111) AND RETAIL #1 (115) SPACES, IN | | | ORDER TO MEET COVERAGE REQUIREMENTS. | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-04-09 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2014-04-10 16:58:57 | RESUBMITTAL SENT TO FIRE SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-01-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-01-16 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-12-27 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2014-01-14 16:59:01 | SH DESK | | | | | 2013-12-27 15:24:51 | ROUTED TO FIRE |
|
|
|