Plan Review Details - Permit 13121015
Plan Review Stops For Permit 13121015
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 17:43 Rev Time 0.00
Received By skennedy Date 2013-12-30 Time 17:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-27 Cont ID  
Sent By scaldero Date 2013-12-27 Time 10:56 Rev Time 0.00
Received By scaldero Date 2013-12-27 Time 10:56 Sent To E
Notes
2013-12-27 10:59:40PERMIT #13121015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****PROVISO****
 ADDITONAL DEVICE NEEDED IN THE STOCKROOM TO MEET
 COVERAGE REQUIREMENTS OR CURRENT DEVICES SHOULD BE
 RAISED TO 110CD (CURRENTLY SET AT 75CD).
 THIS IS TO BE VERIFIED DURING FIELD INSPECTION. SEE
 NOTE ON PLAN FOR EXACT LOCATION.
 *******************
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 17:43 Rev Time  
Received By skennedy Date 2013-12-26 Time   Sent To  
Notes
2013-12-26 09:10:25TO FIRE PER S KENNEDY