Plan Review Details - Permit 13120975
Plan Review Stops For Permit 13120975
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-08-27 Cont ID  
Sent By skennedy Date 2014-08-27 Time 15:41 Rev Time 0.00
Received By skennedy Date 2014-08-27 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-29 Cont ID  
Sent By jwitmer Date 2014-05-29 Time 17:54 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-22 Cont ID  
Sent By jwitmer Date 2014-04-22 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2014-04-17 Time 08:30 Sent To  
Notes
2014-04-17 09:06:374/17/2014 08:30 AM CALL IN FOR THE STRUCTURAL ENGINEER
 OF RECORD CHRISTIAN AQUINO 305-392-0024
  
 4/22/2014
 BUILDING PLAN REVIEW
 PERMIT: 13120975
 ADD: 1721 BELVEDERE RD
 CONT: TO BE DETERMINED
 TEL: (561)
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY JAN. 10/2014
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4A) 2ND REQUEST.THE PRODUCT THAT ARE NEW TO THE
 BUILDING WILL BE COVERED UNDER COMPONENTS AND CLADDING.
 THE IDEA IS TO MAKE SURE THAT THE NEW COMPONENTS WILL
 NOT FLY AWAT IN A HIGH WIND EVENT. THE RESPONSE
 INDICATES THAT THE EXISTING STRUCTURE IS ALREAD A
 WEATHER TIGHT BUILDING. THE EXISTING BUILDING IS
 ALREADY A WEATHER TIGHT BUILDING BUT WILL YOU NOT STRIP
 THE ROOFING MATERIAL OFF THE AREA WHERE THE NEW PARAPET
 WALLS BOTTOM PLATE BE SECURED THROUGH THE ROOF DECK
 INTO THE 2X4 FRAMING MEMBERS AS DETAILED IN DETAIL #1
 OF SHEET S-3.0
  
 4B) THE OTHER 2 DETAILS DO NOT SHOW ANY ANCHORAGE OF
 THE BACK PARAPET WALL TO THE ROOF DECK OR FRAMING
 MEMBER BELOW. IS THIS A DISCREPANCY? 107.2.1.3
 ADDITIONAL INFORMATION REGUIRED.
  
 4C) THESE SAME THREE DETAILS INDICATE 18 GAUGE ANGLES
 BEING ATTACHED TO THE WALL WITH (3) 0,177 INCH DIAMETER
 P.A.F. FASTENERS. THE STRUCTURAL CALCULATIONS P 15
 INDICATE 432 LB RESISTANCE IS REQUIRED. WHAT WILL THE
 MINIMUM LENGTH BE REQUIRED FOR THE FASTENERS.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) , EFIS SYSTEMS, PANEL WALL SYSTEMS HARDIPLANK
 LAP SIDING
 (B) ROOFING PRODUCTS AND ASSEMBLIES
  
 5) 2ND REQUEST. * 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2010 EDITION 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY
 THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) THE BACK SIDE OF THE PARAPET DOES NOT PROVIDE A
 FLASHING DETAIL ON THE BACK SIDE OF THE NEW PARAPET
 WALL. 2010 FBC-B:
 1503.2 FLASHING.
 FLASHING SHALL BE INSTALLED IN SUCH A MANNER SO AS TO
 PREVENT MOISTURE ENTERING THE WALL AND ROOF THROUGH
 JOINTS IN COPINGS, THROUGH MOISTURE-PERMEABLE MATERIALS
 AND AT INTERSECTIONS WITH PARAPET WALLS AND OTHER
 PENETRATIONS THROUGH THE ROOF PLANE.
 1503.2.1 LOCATIONS.
 FLASHING SHALL BE INSTALLED AT WALL AND ROOF
 INTERSECTIONS, AT GUTTERS, WHEREVER THERE IS A CHANGE
 IN ROOF SLOPE OR DIRECTION AND AROUND ROOF OPENINGS.
 WHERE FLASHING IS OF METAL, THE METAL SHALL BE
 CORROSION RESISTANT WITH A THICKNESS NOT LESS THAN
 PROVIDED IN TABLE 1503.2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-10 Cont ID  
Sent By jwitmer Date 2014-01-10 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2014-01-10 Time 12:52 Sent To  
Notes
2014-01-10 15:36:40BUILDING PLAN REVIEW
 PERMIT: 13120975
 ADD: 1721 BELVEDERE RD
 CONT: TO BE DETERMINED
 TEL: (561)
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY JAN. 10/2014
 ACTION: DENIED
  
 1) SHEET A-3.0 THE ELEVATION SHEET DOES NOT PROVIDE
 WHAT THE FINISHES WILL BE ON THE BACK SIDE OF THE
 TOWERS, NOR DOES SHEET A-10.0. 2010 FBC-B 1403.2
 WEATHER PROTECTION.
 EXTERIOR WALLS SHALL PROVIDE THE BUILDING WITH A
 WEATHER-RESISTANT EXTERIOR WALL ENVELOPE. THE EXTERIOR
 WALL ENVELOPE SHALL INCLUDE FLASHING, AS DESCRIBED IN
 SECTION 1405.4. THE EXTERIOR WALL ENVELOPE SHALL BE
 DESIGNED AND CONSTRUCTED IN SUCH A MANNER AS TO PREVENT
 THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY
 PROVIDING A WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR
 VENEER, AS DESCRIBED IN SECTION 1404.2, AND A MEANS FOR
 DRAINING WATER THAT ENTERS THE ASSEMBLY TO THE
 EXTERIOR. PROTECTION AGAINST CONDENSATION IN THE
 EXTERIOR WALL ASSEMBLY SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 1405.3.
  
 2) SHEET A-3.0 THE ELEVATION SHEET DOES NOT PROVIDE
 WHAT THE FINISHES WILL BE ON THETOP SURFACE OF THE
 TOWERS, NOR DOES SHEET A-10.0. 2010 FBC-B 1503.1
 GENERAL.
 ROOF DECKS SHALL BE COVERED WITH APPROVED ROOF
 COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CHAPTER. ROOF
 COVERINGS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH THIS CODE AND THE APPROVED MANUFACTURER?S
 INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO
 PROTECT THE BUILDING OR STRUCTURE.
  
 3) SHEET A-10.0 FINISHES, UNDER THE EF-1- EF-5 THE
 PRODUCT TYPE, STO OR OTHER APPROVED EQUAL. * 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) , EFIS SYSTEMS, PANEL WALL SYSTEMS HARDIPLANK
 LAP SIDING
 (B) ROOFING PRODUCTS AND ASSEMBLIES
  
 5) * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-05-01 Cont ID  
Sent By rlecky Date 2014-05-01 Time 11:57 Rev Time 0.00
Received By rlecky Date 2014-05-01 Time 11:54 Sent To  
Notes
2014-05-01 12:00:15CORRESPONDENCE RECEIVED MARCH 25, 2014 INDICATES THERE
 IS NO ELECTRICAL WORK PROPOSED FOR THIS RENOVATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-06 Cont ID  
Sent By dharvey Date 2014-02-06 Time 13:01 Rev Time 0.00
Received By dharvey Date 2014-02-06 Time 13:01 Sent To  
Notes
2014-02-06 12:34:03BY RL
  
 13120975
 1721 BELVEDERE ROAD
 BURGER KING RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL PLAN DETAILING THE SCOPE OF
 ELECTRICAL CHANGES PROPOSED. SHOW BOTH THE NEW AND
 EXISTING CIRCUITS AND PANEL BOARDS. INCLUDE A FIXTURE
 SCHEDULE. INCLUDE A LIGHTING DENSITY SUMMARY ON THE
 PLAN SHOWING COMPLIANCE WITH THE FLORIDA BUILDING CODE,
 ENERGY CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-08 Cont ID  
Sent By lphilmor Date 2014-01-08 Time 10:52 Rev Time 0.00
Received By lphilmor Date 2014-01-08 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-08-27 Cont ID  
Sent By skennedy Date 2014-08-27 Time 15:43 Rev Time 0.00
Received By skennedy Date 2014-08-27 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-29 Cont ID  
Sent By jwitmer Date 2014-05-29 Time 17:54 Rev Time 0.00
Received By jwitmer Date 2014-05-22 Time 15:52 Sent To Z
Notes
2014-05-22 15:52:49ROUTE TO ZONIING. J. ROACH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-01 Cont ID  
Sent By rlecky Date 2014-05-01 Time 12:01 Rev Time 0.00
Received By rlecky Date 2014-04-03 Time 09:49 Sent To  
Notes
2014-04-04 09:50:12RESUB SENT TO C9 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-07 Cont ID  
Sent By jwitmer Date 2014-02-07 Time 15:08 Rev Time 0.00
Received By jwitmer Date 2013-12-23 Time 08:53 Sent To  
Notes
2013-12-26 08:54:11C14
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-01-08 Cont ID  
Sent By hmoser Date 2014-01-08 Time 13:59 Rev Time 0.00
Received By hmoser Date 2014-01-08 Time 13:27 Sent To  
Notes
2014-01-08 13:59:13NO AIR CONDITIONING PLAN SUBMITTED AT THIS TIME.
 HAVE A/C CONTRACTOR SUBMIT AN APPLICATION AND PLANS
 AT TIME OF PERMITTING
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-02-07 Cont ID  
Sent By jwitmer Date 2014-02-07 Time 15:08 Rev Time 0.00
Received By jwitmer Date 2014-02-07 Time 15:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2014-08-12 Cont ID  
Sent By jroach Date 2014-08-12 Time 10:39 Rev Time 0.00
Received By jroach Date 2014-08-12 Time 10:38 Sent To  
Notes
2014-08-12 10:39:16PROVISO
  
 1. PRIOR TO THE REMOVAL/RELOCATION OF ANY TREES/PALMS
 (IF NECESSARY), A TREE ALTERATION PERMIT SHALL BE
 OBTAINED FROM THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2014-05-28 Cont ID  
Sent By jwitmer Date 2014-05-29 Time 17:45 Rev Time 0.00
Received By jroach Date 2014-05-28 Time 16:47 Sent To B
Notes
2014-05-28 16:48:49ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.28.2014
 PERMIT NO.: 13120975
 ADDRESS: 1721 BELVEDERE ROAD
 CONTRACTOR/CONTACT: DEB SNYDER
 TELEPHONE NO.: 305.527.6282
 SCOPE OF REVIEW: INTERIOR/EXTERIOR RENOVATION TO
 EXISTING DRIVE-THRU RESTAURANT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. IT APPEARS THAT SINCE ORIGINAL SUBMITTAL OF THE
 PERMIT THAT THE SCOPE OF WORK HAS BEEN EXPANDED TO
 INCLUDE IMPROVEMENTS TO THE PARKING LOT, PEDESTRIAN
 CONNECTION TO THE PUBLIC SIDEWALK, ETC. AS THE PROPERTY
 IS CURRENTLY ZONED AS A COMMERCIAL PLANNED DEVELOPMENT
 (CPD), A MINOR AMENDMENT SHALL BE SUBMITTED TO AND
 APPROVED BY THE PLANNING DIVISION PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT. PLEASE EMAIL ME FOR FOR A COPY OF
 THE APPLICATION.
  
 2. IN REVIEWING PHOTOS OF THE SITE, IT APPEARS THAT
 EXISTING LANDSCAPE AREA IS PROPOSED TO BE REMOVED TO
 ACCOMMODATE THE NEW PEDESTRIAN CONNECTION. REMOVAL OF
 ANY TREES SHALL REQUIRE THE ISSUANCE OF A TREE
 ALTERATION PERMIT, AND A REVISED LANDSCAPE PLAN WILL
 NEED TO BE APPROVED THROUGH THE MINOR AMENDMENT PROCESS
 DESCRIBED PREVIOUSLY.
  
 3. THE PARKING STALL STRIPING SHALL CONFORM TO THE
 CITY'S MINIMUM STANDARDS. THE COLORING OF THE STRIPING
 IS REVERSED FROM WHAT SHOULD BE PROVIDED; THE BLUE
 STRIPING SHOULD BE PROVIDED FOR THE ACCESSIBLE PARKING
 SPACE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
2014-05-28 11:38:455/28/14
2014-05-23 09:12:165/23/14 ZONING SENT TO JR. SG

Review Stop Z ZONING
Rev No 2 Status F Date 2014-05-01 Cont ID  
Sent By jroach Date 2014-05-01 Time 09:27 Rev Time 0.00
Received By jroach Date 2014-04-24 Time 15:39 Sent To  
Notes
2014-05-01 09:28:11ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.01.2014
 PERMIT NO.: 13120975
 ADDRESS: 1721 BELVEDERE ROAD
 CONTRACTOR/CONTACT: DEB SNYDER
 TELEPHONE NO.: 305.527.6282
 SCOPE OF REVIEW: INTERIOR/EXTERIOR RENOVATION TO
 EXISTING DRIVE-THRU RESTAURANT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. IT APPEARS THAT SINCE ORIGINAL SUBMITTAL OF THE
 PERMIT THAT THE SCOPE OF WORK HAS BEEN EXPANDED TO
 INCLUDE IMPROVEMENTS TO THE PARKING LOT, PEDESTRIAN
 CONNECTION TO THE PUBLIC SIDEWALK, ETC. AS THE PROPERTY
 IS CURRENTLY ZONED AS A COMMERCIAL PLANNED DEVELOPMENT
 (CPD), A MINOR AMENDMENT SHALL BE SUBMITTED TO AND
 APPROVED BY THE PLANNING DIVISION PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT. PLEASE EMAIL ME FOR A COPY OF THE
 APPLICATION.
  
 2. IN REVIEWING PHOTOS OF THE SITE, IT APPEARS THAT
 EXISTING LANDSCAPE AREA IS PROPOSED TO BE REMOVED TO
 ACCOMMODATE THE NEW PEDESTRIAN CONNECTION. REMOVAL OF
 ANY TREES SHALL REQUIRE THE ISSUANCE OF A TREE
 ALTERATION PERMIT, AND A REVISED LANDSCAPE PLAN WILL
 NEED TO BE APPROVED THROUGH THE MINOR AMENDMENT PROCESS
 DESCRIBED PREVIOUSLY.
  
 3. THE PARKING STALL STRIPING SHALL CONFORM TO THE
 CITY'S MINIMUM STANDARDS. PLEASE EMAIL ME FOR A COPY OF
 THE STANDARD PARKING STALL DETAIL. THE DIMENSION
 BETWEEN THE 4 INCH STRIPES SHOULD ONLY BE 1 FOOT...NOT
 1 FOOT 4 INCHES. ADDITIONALLY, THE COLORING OF THE
 STRIPING IS REVERSED FROM WHAT SHOULD BE PROVIDED; THE
 BLUE STRIPING SHOULD BE PROVIDED FOR THE ACCESSIBLE
 PARKING SPACE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2014-04-14 11:39:104/14/14

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-05 Cont ID  
Sent By jroach Date 2014-02-05 Time 23:05 Rev Time 0.00
Received By jroach Date 2014-02-05 Time 23:05 Sent To  
Notes
2014-02-05 23:06:45PLEASE NOTE THE OVERALL HEIGHT OF THE BUILDING.....BOTH
 TO THE ROOF DECK, AS WELL AS TO THE TOP OF THE PROPOSED
 ARCHITECTURAL ELEMENTS.
  
 SIGNAGE WILL BE REQUIRED TO BE SUBMITTED AND REVIEWED
 UNDER A SEPARATE PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT (561) 822-1448 OR VIA EMAIL AT
 [email protected]
2014-01-02 12:08:381/2/14