Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-20 Cont ID  
Sent By jgomez Date 2013-12-20 Time 16:48 Rev Time 0.00
Received By jgomez Date 2013-12-20 Time 16:48 Sent To  
Notes
2013-12-20 17:04:28RESIDENTIAL (R3) ROOFING REVISION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTES:
 A)THIS PROPERTY IS LOCATED IN THE HISTORIC DISTRICT.
 REVISION NEEDS TO BE APPROVED BY HISTORIC. SEE HISTORIC
 COMMENTS.
 B) OWES $10 FOR HISTORIC REVIEW FEE.
  
 1- SELECTED ASSEMBLY W-16 FROM FLORIDA PRODUCT APPROVAL
 FL10497-R2 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
 THE DESIGN PRESSURES ON THE CORNERS OF THE ROOF ARE
 HIGHER THAN THE DESIGN PRESSURES LISTED ON THE SELECTED
 ASSEMBLY.
 NEED TO USE ANOTHER ASSEMBLY THAT MEETS THE DESIGN
 PRESSURES.
 ***NOTE: BONDED ROOF ASEMBLY DOENS'T ALLOW NAIL
 ENHANCING. SEE LIMITATION 5.7 ON PAGE 3 OF 4 OF PRODUCT
 APRPOVAL SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2013-12-20 Cont ID  
Sent By fmittner Date 2013-12-20 Time 16:38 Rev Time 0.00
Received By fmittner Date 2013-12-20 Time 16:38 Sent To  
Notes
2013-12-20 16:40:27ROOFING MODIFICATION DOES NOT MATCH WHAT WAS APPROVED
 FOR HISTORIC PRESERVATION. QUESTIONS CONTACT FRIEDERIKE
 MITTNER 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-20 Cont ID  
Sent By jgomez Date 2013-12-20 Time 16:48 Rev Time 0.00
Received By jgomez Date 2013-12-20 Time 16:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-12-20 Cont ID  
Sent By fmittner Date 2013-12-20 Time 16:37 Rev Time 0.00
Received By fmittner Date 2013-12-20 Time 16:37 Sent To  
Notes
***NONE***