| Plan Review Stops For Permit 13120923 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-02-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-02-24 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-02-24 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2014-02-24 14:57:58 | BUILDING PLAN REVIEW | | | PERMIT: 13120923 | | | ADD: 1703 PALM BEACH LAKES / SHELL BUILDING | | | CONT: EMJ | | | TEL: (561) 373-3902 | | | CONTACT: KARI | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: MONDAY FEB. 24/ 2014 | | | ACTION:BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | | | | 1) THE COVER SHEET BUILDING & CONSTRUCTION DATA UNDER | | | THE HEADING FIRE PROTECTION SYSTEM SPRINKLERS FBC903 | | | DESIGN STANDARD NFPA 13. NOTE NEITHER THE DRAWING INDEX | | | NOR THE 40 SHEETS SUBMITTED ELECTRONICALLY SHOW ANY | | | FIRE SPRINKLER PLANS. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 107.3.5.1.1(5) FIRE SPRINKLER SCHEMATIC. | | | | | | 2) MISSING COMPLIANCE FORMS FOR 2010 FL ENERGY CODE FOR | | | SHELL BUILDINGS: | | | 103.2 INFORMATION ON CONSTRUCTION DOCUMENTS. 103.2.1 | | | CODE DEMONSTRATION FORMS. SEE TABLE 103.2.1. | | | | | | 3) ROOF NOTES, NO ACTION REQUIRED!!! | | | | | | SHEET A141 ROOF PLAN INDICATES ZONE # 1 TO BE | | | MECHANICALLY FASTENED, NOTE ON PLAN ZONES 2 & 3 THE | | | ROOFING IS TO BE FULLY ADHERED SINGLE PLY TPO. | | | | | | NOA 12-0514.04 FIRESTONE 1-30 PAGES TPO OVER STEEL DECK | | | PAGE 12 HIGHLIGHTED SINGLE PLY TPO, STEEL INSULATED | | | DECK 22 GAUGE/ 6'-0" SPACING | | | ISO 95+GL MIN 2" THICK MAXIMUM DESIGN FOR MECH FASTENED | | | -75 PSI | | | ROOF ZONE PRESSURES VASD 10 SQ FT -65.1 | | | NOTE NO ROOF ZONE 3, THE PARAPETS ARE OVER 3'-0" HIGH. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2014-01-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-01-25 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-01-25 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2014-01-25 08:41:56 | BUILDING PLAN REVIEW | | | PERMIT: 13120923 | | | ADD: 1703 PALM BEACH LAKES / SHELL BUILDING | | | CONT: EMJ | | | TEL: (561) 373-3902 | | | CONTACT: KARI | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: SATURDAY JAN. 25/ 2014 | | | ACTION:BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | | | | 1) THE COVER SHEET BUILDING & CONSTRUCTION DATA UNDER | | | THE HEADING FIRE PROTECTION SYSTEM SPRINKLERS FBC903 | | | DESIGN STANDARD NFPA 13. NOTE NEITHER THE DRAWING INDEX | | | NOR THE 40 SHEETS SUBMITTED ELECTRONICALLY SHOW ANY | | | FIRE SPRINKLER PLANS. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 107.3.5.1.1(5) FIRE SPRINKLER SCHEMATIC. | | | | | | 2) MISSING COMPLIANCE FORMS FOR 2010 FL ENERGY CODE FOR | | | SHELL BUILDINGS: | | | 103.2 INFORMATION ON CONSTRUCTION DOCUMENTS. 103.2.1 | | | CODE DEMONSTRATION FORMS. SEE TABLE 103.2.1. | | | | | | 3) ROOF NOTES, NO ACTION REQUIRED!!! | | | | | | SHEET A141 ROOF PLAN INDICATES ZONE # 1 TO BE | | | MECHANICALLY FASTENED, NOTE ON PLAN ZONES 2 & 3 THE | | | ROOFING IS TO BE FULLY ADHERED SINGLE PLY TPO. | | | | | | NOA 12-0514.04 FIRESTONE 1-30 PAGES TPO OVER STEEL DECK | | | PAGE 12 HIGHLIGHTED SINGLE PLY TPO, STEEL INSULATED | | | DECK 22 GAUGE/ 6'-0" SPACING | | | ISO 95+GL MIN 2" THICK MAXIMUM DESIGN FOR MECH FASTENED | | | -75 PSI | | | ROOF ZONE PRESSURES VASD 10 SQ FT -65.1 | | | NOTE NO ROOF ZONE 3, THE PARAPETS ARE OVER 3'-0" HIGH. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-01-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-01-29 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-01-29 |
Time |
13:53 |
Sent To |
I |
|
| Notes |
| 2014-01-29 14:44:22 | THIS PERMIT IS CONDITIONALL APPROVED AS FOLLOWS: | | | THE FEEDER CONDUCTORS & RACEWAYS SHALL BE RE-EVALUATED | | | AND ADJUSTED ACCORDINGLY. | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | | (561) 805-6718 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2014-01-29 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2014-01-29 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2014-01-29 |
Time |
|
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-01-06 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-01-06 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-01-06 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2014-01-06 16:37:43 | PERMIT # 13120923 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND | | | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF | | | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE | | | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL | | | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE | | | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-03-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2014-03-10 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-02-24 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2014-02-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-12-20 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
N |
Date |
2014-02-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-02-26 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-02-26 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2014-02-26 14:08:02 | IMPACT FEE CREDITS STILL CONTINUES, RECEIPTS FROM PALM | | | BEACH COUNTY NO FEES DUE. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2014-02-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-02-24 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-02-24 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2014-02-24 14:52:23 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-01-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-01-25 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-01-25 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2014-01-25 08:19:59 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-01-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2014-01-04 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-01-04 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-01-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-01-25 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-01-25 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2014-01-25 10:01:13 | PLUMBING PLAN REVIEW | | | PERMIT: 13120923 | | | ADD: 1703 PALM BEACH LAKES / SHELL BUILDIN G-H | | | CONT: EMJ | | | TEL: (561) 373-3902 | | | CONTACT: KARI | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: SATURDAY JAN. 25/ 2014 | | | ACTION: PLUMBING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13. | | | SPECIAL PHASED PERMIT APPROVAL | | | AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION | | | DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE | | | A PERMIT FOR THE CONSTRUCTION OF SHELL OR ANY OTHER | | | PART OF A BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION | | | DOCUMENTS FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN | | | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE SHELL OR | | | OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED AT | | | THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION AND | | | WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE | | | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED | | | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS | | | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL | | | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST | | | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. | | | | | | SHEET P101 PLUMBING NOTES INDICATE THE EXTENT OF THIS | | | PERMIT FOR THE INTERIOR PLUMBING: | | | NOTE # 3 TO SUPPLY CW PIPING IN CEILING JOIST SPACE | | | VALVE AND CAP FOR FUURE TENANT CONNECTION. | | | NOTE # 4 TO PROVIDE 4 INCH SANITARY STUBBED UP IN AREA | | | OF SLAB LEAVE OUT AND CAPPED FOR FUTURE TENANT | | | CONNECTION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2014-03-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2014-03-14 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-03-14 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-03-10 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-03-10 |
Time |
23:28 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2014-03-10 |
Time |
23:02 |
Sent To |
|
|
| Notes |
| 2014-03-10 23:28:08 | PASSED. | | | | | | AWNINGS AND SIGNS REQUIRE SEPARATE PERMITS WITH PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2014-03-03 14:57:06 | 3/3/14 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-02-06 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-02-06 |
Time |
16:36 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2014-02-06 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2014-02-06 16:51:52 | 1) PROVIDE A SITE PLAN SHOWING THE DIMENSION FROM THE | | | NORTHEAST CORNER OF THE BUILDING TO THE PALM BEACH | | | LAKES BOULEVARD PROPERTY LINE. | | | | | | 2) SHOW THE BICYCLE RACK AND PAD ON THE PLANS. | | | | | | 3) THE BICYCLE RACK REQUIRES A SEPARATE PERMIT, WITH | | | PLANS. | | | | | | 4) THE PARKING LOT, TO INCLUDE STRIPING, REQUIRES A | | | SEPARATE PERMIT, WITH PLANS. | | | | | | 5) PLEASE PROVIDE VERIFICATION THAT THIS OUTPARCEL IS | | | INCLUDED IN THE CONSTRUCTION SITE SECURITY PLAN. PLEASE | | | CONTACT OFFICER KELLY CARSILLO. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2014-01-09 11:08:49 | 1/9/14 |
|
|