Plan Review Details - Permit 13120916
Plan Review Stops For Permit 13120916
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 11:12 Rev Time 0.00
Received By jwitmer Date 2014-01-07 Time 10:05 Sent To  
Notes
2014-01-23 11:12:51 
 BUILDING PLAN REVIEW
 PERMIT: 13120916
 ADD: 1815 PALM BEACH LAKES SHELL BLDG "E"
 CONT: EMJ
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURSDAY JAN. 23/ 2014
 ACTION: BUILDING PROVISO
  
 1) SHEET A141 ROOF PLAN INDICATES ZONE # 1 TO BE
 MECHANICALLY FASTENED, NOTE ON PLAN ZONES 2 & 3 THE
 ROOFING IS TO BE FULLY ADHERED SINGLE PLY TPO.
  
 NOA 12-0514.04 FIRESTONE 1-30 PAGES TPO OVER STEEL DECK
 PAGE 12 HIGHLIGHTED SINGLE PLY TPO, STEEL INSULATED
 DECK 22 GAUGE/ 6'-0" SPACING
 ISO 95+GL MIN 2" THICK MAXIMUM DESIGN FOR MECH FASTENED
 -75 PSI
  
 NO SHEETS HIGHLIGHTED IN THE NOA FOR FULLY ADHERED FOR
 ZONES 2 & 3, ADDITIONAL INFORMATION IS REQUIRED. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.2.1.3.
  
 =======================================================
 ======================
  
 NOA- 13-0603.19 GAF ENERGY GAURD

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-30 Cont ID  
Sent By dharvey Date 2014-01-30 Time 12:03 Rev Time 0.00
Received By dharvey Date 2014-01-30 Time 10:23 Sent To  
Notes
2014-01-30 10:24:16BY RL

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-01-29 Cont ID  
Sent By mgonzale Date 2014-01-29 Time   Rev Time 1.00
Received By mgonzale Date 2014-01-29 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-30 Cont ID  
Sent By scaldero Date 2013-12-30 Time 10:19 Rev Time 0.00
Received By scaldero Date 2013-12-30 Time 10:19 Sent To  
Notes
2013-12-30 10:22:37PERMIT #13120916
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 12:06 Sent To  
Notes
2014-02-26 12:26:20FUEL GAS PLAN REVIEW
 PERMIT: 13120916
 ADDRESS: 1815 PALM BEACH LAKES BLDG "SHELL"
 CONT: EMJ
 TEL: (423) 855-6857
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: WED.26/ 2014
 ACTION: GAS PROVISO
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
  
 1) A SEPARATE GAS PERMIT IS REQUIRED, IT IS NOT COVERED
 UNDER THE PLUMBING PERMIT OR PLAN REVIEW, THIS IS FOR
 THE SHELL ONLY!
  
 2) 2010 FUEL GAS SECTION:
 404.4 UNDERGROUND PENETRATIONS PROHIBITED.
 GAS PIPING SHALL NOT PENETRATE BUILDING FOUNDATION
 WALLS AT ANY POINT BELOW GRADE. GAS PIPING SHALL ENTER
 AND EXIT A BUILDING AT A POINT ABOVE GRADE AND THE
 ANNULAR SPACE BETWEEN THE PIPE AND THE WALL SHALL BE
 SEALED.
 404.6 PIPING IN SOLID FLOORS.
 PIPING IN SOLID FLOORS SHALL BE LAID IN CHANNELS IN THE
 FLOOR AND COVERED IN A MANNER THAT WILL ALLOW ACCESS TO
 THE PIPING WITH A MINIMUM AMOUNT OF DAMAGE TO THE
 BUILDING. WHERE SUCH PIPING IS SUBJECT TO EXPOSURE TO
 EXCESSIVE MOISTURE OR CORROSIVE SUBSTANCES, THE PIPING
 SHALL BE PROTECTED IN AN APPROVED MANNER. AS AN
 ALTERNATIVE TO INSTALLATION IN CHANNELS, THE PIPING
 SHALL BE INSTALLED IN A CONDUIT OF SCHEDULE 40 STEEL,
 WROUGHT IRON, PVC OR ABS PIPE IN ACCORDANCE WITH
 SECTION 404.6.1 OR 404.6.2.
  
 3) NOTE # 10 INDICATES THE GAS PIPE IS TO BE SIZED FOR
 FUTURE TENANT CONNECTION. VERIFY TENANT GAS LOAD DEMAND
 & PRESSURE REQUIREMENTS WITH TENANT IMPROVEMENT PLAN
 PROR TO THE INSTALATION OF GAS LINE. GAS IS TO BE SIZED
 TO THE MAXIMUM DEMAND 402.2.PROVIDE SIZING METHOD AND
 TABLES FOR SIZING OF PIPE AND DEVELOPED LENGTH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2014-01-23 Time 11:29 Sent To  
Notes
2014-01-23 11:29:28FUEL GAS PLAN REVIEW
 PERMIT: 13120916
 ADDRESS: 1815 PALM BEACH LAKES BLDG "SHELL"
 CONT: EMJ
 TEL: (423) 855-6857
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. JAN. 23/ 2014
 ACTION: DENIED
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
  
 1) A SEPARATE GAS PERMIT IS REQUIRED, IT IS NOT COVERED
 UNDER THE PLUMBING PERMIT OR PLAN REVIEW, THIS IS FOR
 THE FOUNDATION ONLY.
  
 2) SHEET P101 NOTE # 9 INDICTES UNDERGROUND GAS LINE,
 METER AND REGULATOR SHALL BE PROVIDED AND INSTALLED BY
 THE GAS UTILITY COMPANY. NOTE # 10 GAS CAPPED FOR
 FUTURE TENANT CONNECTION. VERIFY TENANT GAS LOAD DEMAND
 & PRESSURE REQUIREMENTS WITH TENANT IMPROVEMENT PLAN
 PROR TO THE INSTALATION OF GAS LINE.
  
 2A) IT IS NOT CLEAR AS TO WHERE FLORIDA GAS UTIULITIES
 METER IS TO BE SET. IT APPEARS THAT THE GAS LINES ARE
 TO BE BENEATH THE SLAB. PLEASE REVIEW 2010 FBC-GAS
 SECTIONS :
 404.4 UNGROUND PENETRATIONS PROHIBITED, AND 404.6
 PIPING IN SOLID FLOORS.
  
 2B) NOTE # 10 INDICATES THE GAS PIPE IS TO BE SIZED FOR
 FUTURE TENANT CONNECTION. VERIFY TENANT GAS LOAD DEMAND
 & PRESSURE REQUIREMENTS WITH TENANT IMPROVEMENT PLAN
 PROR TO THE INSTALATION OF GAS LINE. GAS IS TO BE SIZED
 TO THE MAXIMUM DEMAND 402.2.PROVIDE SIZING METHOD AND
 TABLES FOR SIZING OF PIPE AND DEVELOPED LENGTH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-13 Cont ID  
Sent By rregueir Date 2014-03-10 Time 08:27 Rev Time 0.00
Received By rregueir Date 2014-02-24 Time 09:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2014-02-06 Time   Rev Time 0.00
Received By rregueir Date 2013-12-26 Time 14:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 14:04 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 14:04 Sent To  
Notes
2014-02-26 14:05:58IMPACT FEE CREDITS STILL CONTINUES, RECEIPTS FROM PALM
 BEACH COUNTY NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 11:14 Rev Time 0.00
Received By jwitmer Date 2014-01-23 Time 11:14 Sent To  
Notes
2014-01-23 11:14:50BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-01-04 Cont ID  
Sent By rregueir Date 2014-01-04 Time 11:55 Rev Time 0.00
Received By rregueir Date 2014-01-04 Time 11:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-25 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2014-01-23 Time 11:29 Sent To  
Notes
2014-01-23 11:56:33PLUMBING PLAN REVIEW
 PERMIT: 13120916
 ADD: 1703 PALM BEACH LAKES / SHELL BUILDING-E
 CONT: EMJ
 TEL: (561) 373-3902
 CONTACT: KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURSDAY JAN. 23/ 2014
 ACTION: PLUMBING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13.
 SPECIAL PHASED PERMIT APPROVAL
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF SHELL OR ANY OTHER
 PART OF A BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION
 DOCUMENTS FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE SHELL OR
 OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED AT
 THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 SHEET P101 PLUMBING NOTES INDICATE THE EXTENT OF THIS
 PERMIT FOR THE INTERIOR PLUMBING:
 NOTE # 3 TO SUPPLY CW PIPING IN CEILING JOIST SPACE
 VALVE AND CAP FOR FUURE TENANT CONNECTION.
 NOTE # 4 TO PROVIDE 4 INCH SANITARY STUBBED UP IN AREA
 OF SLAB LEAVE OUT AND CAPPED FOR FUTURE TENANT
 CONNECTION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-03-14 Cont ID  
Sent By rregueir Date 2014-03-14 Time 10:07 Rev Time 0.00
Received By rregueir Date 2014-03-14 Time 10:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-03-11 Cont ID  
Sent By eschneid Date 2014-03-10 Time 23:29 Rev Time 0.75
Received By eschneid Date 2014-03-10 Time 23:29 Sent To  
Notes
2014-03-11 00:08:50PASSED
  
 1) PRIOR TO C.O., A REVISED SHEET A100 SHALL BE
 SUBMITTED SHOWING THE DRIVE THROUGH CONFIGURATION AND
 FEATURES AS APPROVED BY THE MARCH 10, 2014 MINOR
 AMENDMENT APPROVAL LETTER.
  
 2) SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
2014-03-03 14:58:003/3/14

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-06 Cont ID  
Sent By eschneid Date 2014-02-06 Time 13:50 Rev Time 2.00
Received By eschneid Date 2014-02-06 Time 13:50 Sent To  
Notes
2014-02-06 15:33:06FAILED
  
 1) PROVIDE A SITE PLAN SHOWING THE DIMENSION FROM THE
 NORTHEAST CORNER OF THE BUILDING TO THE PALM BEACH
 LAKES BOULEVARD PROPERTY LINE.
  
 2) SHOW CORRECT BICYCLE RACK AND PAD.
  
 3) THE DRIVE THRU CONFIGURATION IS NOT CORRECTLY SHOWN
 BASED ON THE RECENT DISCUSSIONS WITH URBAN DESIGN
 KILDAY STUDIOS.
  
 4) THE DUMPSTER ENCLOSURE, MENU BOARDS, SPEAKER POST,
 GUARDRAIL, BICYCLE RACK, ETC. REQUIRE SEPARATE PERMITS,
 WITH PLANS.
  
 5) THE PARKING LOT, TO INCLUDE STRIPING, REQUIRES A
 SEPARATE PERMIT, WITH PLANS.
  
 6) PLEASE PROVIDE VERIFICATION THAT THIS OUTPARCEL IS
 INCLUDED IN THE CONSTRUCTION SITE SECURITY PLAN. PLEASE
 CONTACT OFFICER KELLY CARSILLO.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  