Plan Review Details - Permit 13120880
Plan Review Stops For Permit 13120880
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-01-09 Cont ID  
Sent By jwitmer Date 2014-01-09 Time 17:57 Rev Time 0.00
Received By jwitmer Date 2014-01-09 Time 17:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-02-04 Cont ID  
Sent By dharvey Date 2014-02-04 Time 12:17 Rev Time 0.00
Received By dharvey Date 2014-02-04 Time 12:17 Sent To  
Notes
2014-02-04 12:17:21BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-16 Cont ID  
Sent By wjolin Date 2014-01-16 Time 09:55 Rev Time 0.00
Received By wjolin Date 2014-01-16 Time 09:54 Sent To  
Notes
2014-01-16 09:55:043501 ELECTRONICS WAY - PHASE 4B
 PERMIT #13120880
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E5.0: EMERGENCY LIGHTING PHOTOMETRICS INDICATES
 LESS THAN 1 FOOT-CANDLE (NORMAL) AND LESS THAN 10
 FOOT-CANDLES (EMERGENCY) ON THE EGRESS STAIRS. PER NFPA
 101 SECTION 7.8.1.3. DURING CONDITIONS OF USE, THE
 MINIMUM ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST
 10 FOOT-CANDLES MEASURED AT THE WALKING SURFACE. DURING
 CONDITIONS OF NON-USE THE STAIRS SHALL BE PROVIDED WITH
 AT LEAST 1 FOOT-CANDLE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-16 Cont ID  
Sent By wjolin Date 2014-01-16 Time 09:55 Rev Time 0.00
Received By wjolin Date 2013-12-19 Time 17:51 Sent To  
Notes
2013-12-19 17:51:24INCOMING SENT TO C33 BOX. JW