Plan Review Details - Permit 13120839
Plan Review Stops For Permit 13120839
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-07 Cont ID  
Sent By albarran Date 2014-01-07 Time 20:15 Rev Time 0.00
Received By albarran Date 2014-01-07 Time 18:33 Sent To I
Notes
2014-01-07 20:16:06THIS APPLICATION WAS CONDITIONALLY APPROVED AS FOLLOWS:
 PROVISO:
 AS PER FBC-B SECTION 907
 A SMOKE DETECTOR IS REQUIRED
 IN THE ELECTRICAL ROOM.
 AS THIS ADDITION ALTERS THE RISER
 DIAGRAM, A REVISED RISER
 DIAGRAM SHOWING THE ADDED
 DEVICE ALONG WITH THE REVISED
 LOAD AND BATTERY CALCS SHALL
 BE SUBMITTED FOR APPROVAL
 PRIOR TO FINAL INSPECTION.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-21 Cont ID  
Sent By wjolin Date 2013-12-21 Time 11:24 Rev Time 0.00
Received By wjolin Date 2013-12-21 Time 09:34 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-08 Cont ID  
Sent By shill Date 2014-01-08 Time 11:31 Rev Time 0.00
Received By shill Date 2013-12-19 Time 12:39 Sent To  
Notes
2014-01-07 20:16:43SAK
2013-12-19 12:40:19ROUTED TO FIRE