| Plan Review Stops For Permit 13120836 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-06-30 |
|
|
Cont ID |
|
| Sent By |
RM |
Date |
2014-06-30 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-06-20 |
Time |
14:02 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-06-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-06-30 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-06-30 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-01-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-14 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-14 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2014-01-14 16:44:22 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS / INSTALLATION INSTRUCTIONS FOR THE GAS | | | POOL HEATER. CITY AMENDMENTS 107.2.1.3 | | | | | | 2) SUBMIT AN ENGINEERED ANCHORING DETAIL THAT SPECIFIES | | | THE CONCRETE PAD THAT WILL SUPPORT THE POOL HEATER AND | | | INDICATES THE ATTACHMENT OF THE HEATER TO THE PAD TO | | | RESIST WIND-LOADS. SPECIFY THE WIND SPEED AND EXPOSURE | | | CATEGORY ON THE DETAIL. FBC R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
|