Plan Review Details - Permit 13120836
Plan Review Stops For Permit 13120836
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-30 Cont ID  
Sent By RM Date 2014-06-30 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2014-06-20 Time 14:02 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By rmcdouga Date 2014-06-30 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 10:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-01-14 Cont ID  
Sent By rmcdouga Date 2014-01-14 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2014-01-14 Time 16:34 Sent To  
Notes
2014-01-14 16:44:222010 FBC
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS / INSTALLATION INSTRUCTIONS FOR THE GAS
 POOL HEATER. CITY AMENDMENTS 107.2.1.3
  
 2) SUBMIT AN ENGINEERED ANCHORING DETAIL THAT SPECIFIES
 THE CONCRETE PAD THAT WILL SUPPORT THE POOL HEATER AND
 INDICATES THE ATTACHMENT OF THE HEATER TO THE PAD TO
 RESIST WIND-LOADS. SPECIFY THE WIND SPEED AND EXPOSURE
 CATEGORY ON THE DETAIL. FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]