Plan Review Details - Permit 13120817
Plan Review Stops For Permit 13120817
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2014-02-10 Time   Rev Time 0.00
Received By jwitmer Date 2014-02-08 Time 08:30 Sent To  
Notes
2014-02-08 09:48:57BUILDING PLAN REVIEW
 PERMIT: 13120817
 ADD: 1801 PALM BEACH LAKES BLVD / GENERATOR
 CONT: EMJ CORP
 TEL: (561)423-414-1589
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: SAT. FEB. 08/2014
 ACTION: BUILDING PROVISO
  
 1) SEPERATE PERMIT REQUIRED FOR GEN-ELECTRIC & GAS.
  
 NOTES KOHLER
 MODEL: 60REZGB
 NATURAL GAS
 FUEL SUPPLY INLET 1 1/4 NPFT
 NATURAL GAS/ LPG FUEL SUPPLY PRESSURE, KPA(IN. H2O)
 1.74-2.74 (7-11)
 FUEL CONSUMPTION
 FUEL CONSUMPTION @ 100% LOAD 22.4M3/HR.
  
  
 GAS PLAN UNDER REV# 13120864
 SHEET P-403
 NATURAL GAS
 INLET PRESSURE 2PSI SYSTEM
 PRESSUE DROP 0.5 WC
 S.G. 0.60
 SCHEDULE 40 METALLIC
 LONGEST RUN 10'
 MAX. LOAD 790,000 BTU
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-29 Cont ID  
Sent By jwitmer Date 2014-01-29 Time 17:58 Rev Time 0.00
Received By jwitmer Date 2014-01-29 Time 17:30 Sent To  
Notes
2014-01-29 17:54:47BUILDING PLAN REVIEW
 PERMIT: 13120817
 ADD: 1801 PALM BEACH LAKES BLVD / GENERATOR
 CONT: EMJ CORP
 TEL: (561)423-414-1589
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED JAN. 29/ 2014
 ACTION: DENIED
  
 1) PLANS SUBMITTED ARE FOR A 60 KW GENERATOR, MISSING
 INFORMATION:
 1) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 2) THERE WAS NO INFORMATION AS TO WHAT TYPE OF BASE,
 SLAB AND OR FOUNDATION THE GENERATOR WILL BE ANCHORED
 TO TO RESIST THE MOMENT OF OVERTURNING AND OR SLIDDING?
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 3) PLEASE PROVIDE TYPE OF ANCHOR AND QUANITY OF ANCHORS
 IN THIS INSTALATION. 107.2.1.3. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) ADDITIONAL PERMITS WILL BE REQUIRED, EITHER LPOR
 NATURAL GAS FOR FUEL FOR THE GENERATOR.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected].

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-28 Cont ID  
Sent By albarran Date 2014-01-28 Time 18:11 Rev Time 0.00
Received By albarran Date 2014-01-28 Time 17:32 Sent To I
Notes
2014-01-28 18:19:11THIS IS BEING CONDITIONALLY APPROVED AS FOLLOWS:
 AS PER NEC 445.13 THE AMPACITY OF THE CONDUCTOR FROM
 THE GENERATOR TO THE PANEL OCPD MUST NOT BE LESS THAN
 115% OF THE NAMEPLATE RATING OF THE GENERATOR.
 I=KW/(E*1.732), I= 60*1000/(480*1.732), I=60000/831,
 I=72 AMP
 AS PER NEC 310.15(B), MORE THAN THREE CURRENT CARRYING
 CONDUCTORS, DERATE TO 80%
 F-4 FEEDER NOT ADEQUATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-24 Cont ID  
Sent By scaldero Date 2014-01-24 Time 15:40 Rev Time 0.00
Received By scaldero Date 2014-01-24 Time 15:40 Sent To E
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-02-08 Cont ID  
Sent By jwitmer Date 2014-02-08 Time 09:49 Rev Time 0.00
Received By jwitmer Date 2014-02-08 Time 09:49 Sent To  
Notes
2014-02-08 09:50:21FUEL -GAS PLAN REVIEW
 PERMIT: 13120817
 ADD: 1801 PALM BEACH LAKES BLVD / GENERATOR
 CONT: EMJ CORP
 TEL: (561)423-414-1589
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: SAT. FEB. 08/2014
 ACTION: PASSED
  
 1) PROVISO: SEPERATE PERMIT REQUIRED FOR GEN-ELECTRIC &
 GAS.
  
 NOTES KOHLER
 MODEL: 60REZGB
 NATURAL GAS
 FUEL SUPPLY INLET 1 1/4 NPFT
 NATURAL GAS/ LPG FUEL SUPPLY PRESSURE, KPA(IN. H2O)
 1.74-2.74 (7-11)
 FUEL CONSUMPTION
 FUEL CONSUMPTION @ 100% LOAD 22.4M3/HR.
  
  
 GAS PLAN UNDER REV# 13120864
 SHEET P-403
 NATURAL GAS
 INLET PRESSURE 2PSI SYSTEM
 PRESSUE DROP 0.5 WC
 S.G. 0.60
 SCHEDULE 40 METALLIC
 LONGEST RUN 10'
 MAX. LOAD 790,000 BTU
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-10 Cont ID  
Sent By swurafti Date 2014-02-10 Time 12:30 Rev Time 0.00
Received By swurafti Date 2014-02-07 Time 16:53 Sent To  
Notes
2014-02-07 16:53:52TO JW
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-29 Cont ID  
Sent By albarran Date 2014-01-29 Time 17:54 Rev Time 0.00
Received By jwitmer Date 2014-01-29 Time 12:21 Sent To  
Notes
2014-01-29 12:21:381/29 TO JW DESK
  
2013-12-19 17:44:10INCOMING SENT TO ZONING BOX. JW

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-29 Cont ID  
Sent By eschneid Date 2014-01-29 Time 11:50 Rev Time 0.50
Received By eschneid Date 2013-12-23 Time 09:29 Sent To PC
Notes
2014-01-29 11:51:12PASSED W/PROVISO
  
 1) PRIOR TO THE FINAL INSPECTION (104) FOR THE
 GENERATOR, A PERMIT, WITH PLANS, IS REQ. FOR CHAIN LINK
 FENCE. THE CHAIN LINK FENCE SHALL BE INSTALLED AND PASS
 INSPECTION.
2013-12-23 09:30:2712/23/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL