| 2014-01-29 17:54:47 | BUILDING PLAN REVIEW |
| | PERMIT: 13120817 |
| | ADD: 1801 PALM BEACH LAKES BLVD / GENERATOR |
| | CONT: EMJ CORP |
| | TEL: (561)423-414-1589 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED JAN. 29/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED ARE FOR A 60 KW GENERATOR, MISSING |
| | INFORMATION: |
| | 1) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 2) THERE WAS NO INFORMATION AS TO WHAT TYPE OF BASE, |
| | SLAB AND OR FOUNDATION THE GENERATOR WILL BE ANCHORED |
| | TO TO RESIST THE MOMENT OF OVERTURNING AND OR SLIDDING? |
| | 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) PLEASE PROVIDE TYPE OF ANCHOR AND QUANITY OF ANCHORS |
| | IN THIS INSTALATION. 107.2.1.3. ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 4) ADDITIONAL PERMITS WILL BE REQUIRED, EITHER LPOR |
| | NATURAL GAS FOR FUEL FOR THE GENERATOR. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected]. |