Plan Review Details - Permit 13120707
Plan Review Stops For Permit 13120707
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2014-01-08 Time 14:50 Sent To  
Notes
2014-01-08 15:06:41BUR NOA NO. 13-0424.09 AND RAS 117 CALCULATIONS WERE
 SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-12-30 Cont ID  
Sent By rmcdouga Date 2013-12-30 Time 17:02 Rev Time 0.00
Received By rmcdouga Date 2013-12-30 Time 17:02 Sent To  
Notes
2013-12-30 17:16:43DENIED BY BUILDING
  
 1) THE ENGINEERING (RAS 117 CALCULATIONS) THAT WAS
 SUBMITTED DOES NOT MATCH THE PRODUCT APPROVAL THAT WAS
 SUBMITTED OR THE DECK MATERIAL. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C WITH
 A VULT WINDSPEED OF 170 MPH. THE UPLIFT PRESSURES
 LISTED ARE CORRECT FOR 170 MPH, EXPOSURE 'C'. HOWEVER
 THE CALCULATIONS SPECIFY VULT 180MPH AND NO EXPOSURE
 CATEGORY WAS SPECIFIED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-21 Cont ID  
Sent By shill Date 2013-12-21 Time 14:36 Rev Time 0.00
Received By shill Date 2013-12-21 Time 14:36 Sent To  
Notes
2013-12-21 14:38:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NO ASSEMBLY PROPOSED IN THE SHEETS SUBMITTED. ONLY
 THE FIRST SHEETS SHOWING PRODUCTS AND THE LAST SHEET
 SHOWING LIMITATIONS WERE PROVIDED; NO SHEETS IN THE
 MIDDLE (WHICH CONTAIN ALL OF THE APPROVED ASSEMBLIES)
 WERE SUBMITTED.
  
 NO REVIEW CAN BE DONE AT THIS TIME.
 FBC 2010 RESIDENTIAL 301.
  