Plan Review Details - Permit 13120664
Plan Review Stops For Permit 13120664
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-12-30 Cont ID  
Sent By jwitmer Date 2013-12-30 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2013-12-30 Time 07:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-06 Cont ID  
Sent By skennedy Date 2014-01-06 Time 11:58 Rev Time 0.00
Received By skennedy Date 2014-01-06 Time 11:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-21 Cont ID  
Sent By wjolin Date 2013-12-21 Time 12:11 Rev Time 0.00
Received By wjolin Date 2013-12-21 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-06 Cont ID  
Sent By skennedy Date 2014-01-06 Time 16:55 Rev Time 0.00
Received By skennedy Date 2013-12-16 Time 18:50 Sent To  
Notes
2013-12-18 18:51:16EXPEDITED B21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-12-30 Cont ID  
Sent By jwitmer Date 2013-12-30 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2013-12-30 Time 08:44 Sent To  
Notes
2013-12-30 09:02:39BUILDING PLAN REVIEW
 PERMIT: 13120664
 ADD: 221 CLEMATIS ST. 3RD FL. TENANT BUILD-OUT
 CONT: GALFA CEE CO.
 TEL: (561)718-9509
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: DEC. 30/2013
 ACTION: PROVISO
  
 MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET M-1 THE CONFERENCE ROOM # 106 SHOWS A 14 INCH
 DIAMETER DUCT SUPPLYING 720 CFM FULL HEIGHT PARTITION
 (P4) AND NO TRANSFER GRILLE. PLEASE PROVIDE COMPLIANCE
 WITH
 2010 FBC-MECHANICAL 601.4 BALANCED RETURN AIR.
  
 2) SHEET M-2 INDICATES A NEW ROOF TOP A/C STAND, PLEASE
 PROVIDE THE PRODUCT APPROVAL IN COMPLIANCE WITH RULE
 9N-3 (31)(G).
  
 3) SEE ATTACHMENT FROM MASTER PERMIT # 07110013 &
 MECHANICAL REVISION # 09050030 FOR EXISTING DUCT WORK,
 SHAFT LOCATION, FIRE DAMPER LOCATION AND ACCESS DOORS,
 FOR REFERENCE ONLY, VERIFY AT SITE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-12-30 Cont ID  
Sent By jwitmer Date 2013-12-30 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2013-12-30 Time 09:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2014-01-06 Cont ID  
Sent By aaponte Date 2014-01-06 Time 16:55 Rev Time 0.00
Received By skennedy Date 2014-01-06 Time 12:01 Sent To  
Notes
2014-01-06 12:04:42LEFT MESSAGE WITH AAPONTE TO SEE IF REVIEW IS REQUIRED.
2014-01-02 11:58:311/2/14