Plan Review Details - Permit 13120635
Plan Review Stops For Permit 13120635
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-01-31 Cont ID  
Sent By scaldero Date 2014-01-31 Time 08:26 Rev Time 0.00
Received By scaldero Date 2014-01-31 Time 08:26 Sent To  
Notes
2014-01-31 08:26:42NEW PERMIT 3 ISSUED FOR REVISIONS - 14010839

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-12-16 Cont ID  
Sent By scaldero Date 2013-12-16 Time 14:02 Rev Time 0.00
Received By scaldero Date 2013-12-16 Time 14:02 Sent To M
Notes
2013-12-16 14:04:57PERMIT #13120635
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF
 THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS.
  
 PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM
 NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS
 PERMITTED IN THE LISTING DATA.
  
 SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS
 PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE
 BRAIDED OR UNBRAIDED.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-16 Cont ID  
Sent By skennedy Date 2013-12-16 Time 15:07 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-01-31 Cont ID  
Sent By skennedy Date 2014-01-31 Time 15:14 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-16 Cont ID  
Sent By skennedy Date 2013-12-16 Time 15:07 Rev Time 0.00
Received By skennedy Date 2013-12-16 Time 15:07 Sent To  
Notes
2013-12-16 15:07:43AMMEND DRAWING PER FIRE COMMENTS.