| 2013-12-26 13:56:01 | BUILDING PLAN REVIEW |
| | PERMIT: 13120617 |
| | ADD: 2905 45TH ST |
| | CONT: RAPP CONSTRUCTION |
| | TEL: (561)842-3299 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY/ DEC. 26/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET KEY PROVIDES OCCPANT LOADS 1ST FLOOR |
| | AND SECOND FLOOR. THE PLANS DOES NOT LIST THE SQUARE |
| | FOOTAGE OF THE ROOM THE MEZZANINE IS LOCATED. THE 2010 |
| | FBC-B 505.2 LIMITS THE AGGREGATE AREA OF A MEZZANINE OR |
| | MEZZANINES WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF |
| | THE FLOOR AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE |
| | LOCATED. THE ENCLOSED PORTION OF A ROOM SHALL NOT BE |
| | INCLUDED IN A DETERMINATION OF THE FLOOR AREA OF THE |
| | ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING |
| | THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE |
| | SHALL NOT BE INCLUDED IN THE FLOOR AREA OF THE ROOM. |
| | PLEASE PROVIDE A FLOOR PLAN (AND SQ FT) SHOWING THE |
| | ACTAUL OPEN ROOM THE MEZZANINE IS LOCATED AND THE AREA |
| | (SQ FT) OF THE EXISTING MEZZANINE AND THE ADDITIONAL |
| | SQUARE FOOTAGE BEING PROPOSED. |
| | |
| | PLEASE SEE EXCEPTION # 2 THE AGGREGATE AREA OF |
| | MEZZANINES IN BUILDINGS AND STRUCTURES OF TYPE I OR II |
| | CONSTRUCTION SHALL NOT EXCEED ONE-HALF OF THE FLOOR |
| | AREA OF THE ROOM IN BUILDINGS AND STRUCTURES EQUIPPED |
| | THROUGHOUT WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM |
| | IN ACCORDANCE WITH SECTION 903.3.1.1 AND AN APPROVED |
| | EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN |
| | ACCORDANCE WITH SECTION 907.5.2.2. |
| | |
| | 2) PLEASE PROVIDE WHAT THE MINIMUM BUILDING TYPE FOR |
| | THIS BUILDING WITH FRONTAGE INCREASE (506.2) AND IF |
| | FIRE SPRINKLERED (506.3). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |