Plan Review Details - Permit 13120574
Plan Review Stops For Permit 13120574
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-02 Cont ID  
Sent By jwitmer Date 2014-01-02 Time 18:04 Rev Time 0.00
Received By jwitmer Date 2014-01-02 Time 17:41 Sent To  
Notes
2014-01-02 18:04:31BUILDING PLAN REVIEW
 PERMIT: 13120574
 ADD: 4117 BROADWAY
 CONT: DREAMWORKS CONSTRUCTION
 TEL: (813)249-5541
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 02/ 2014
 ACTION: DENIED
  
 1) SHEET A-1 SHOWS THE DEMOLITION OF THE EXISTING
 STOREFRONT AND ALSO THE NEW DESIGN. IN THE NEW
 STOREFRONT DESIGN THERE IS A MEASUREMENT OF 7 INCHES,
 NOT SHOWN ON THE DEMO PLAN, IS THIS A STRUCTURAL COLMN,
 OR STRUCTURAL MULLION, 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) THE PRODUCT APPROVAL FOR THE FRONT DOORS, TRANSOM
 AND SIDELIGHTS HAS LARGE MISSILE TESTING, NO PRODUCT
 APPROVAL WAS SUBMITTED FOR THE STOREFRONT WINDOWS ONLY
 NOA 09-0127.13 DESCRIPTION SOLUTIA INTERLAYER FOR
 LAMINATED GLASS, NO LARGE MISSILE TESTING.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-01-29 Cont ID  
Sent By albarran Date 2014-01-29 Time 13:29 Rev Time 0.00
Received By albarran Date 2014-01-29 Time 11:46 Sent To I
Notes
2014-01-29 13:38:37THE FOLLOWING ITEMS SHALL BE ADDRESSED AND RESUBMIT FOR
 REVIEWS>
 1. NEC 600.05 REQUIRES A SIGN OUTLET BY EVERY ENTRY
 DOOR
 2. NEC 210.62 REQUIRES A SHOW WINDOW LIGHTING OUTLET
 FOR EVERY 12 LINEAR FOOT OF WINDOW.
 3. NEC 110.16 REQUIRES ARC-FLASH WARNING LABELS AT THE
 ELECTRICAL PANELS
 4. NEC 210.08 REQUIRES THAT ALL OUTLETS WITHIN 6' OF
 THE SINK BE GFCI PROTECTED.
 5. MISSING PANEL SCHEDULE AND LOAD CALCS FOR PANEL "B"
 LIGHTING CONDITIONS AS STATED ON THE DRAWINGS DO NOT
 SEEM TO COMPLY WITH THE MINIMUM REQUIREMENTS OF THE
 FBC-ENERGY CONSERVATION CODE SECTION 505
 THE EMERGENCY LIGHTING AS SHOWN ON THE PLANS DO NOT
 COMPLY WITH THE MINIMUM REQUIREMENTS OF NFPA 101
 SECTION 7.9
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH BLDG. DEPARTMENT
 (561) 805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-21 Cont ID  
Sent By wjolin Date 2013-12-21 Time 12:53 Rev Time 0.00
Received By jwitmer Date 2014-01-02 Time 17:41 Sent To  
Notes
2014-01-02 17:42:22SEE APPROVED PLANS STAMPED BY WESLEY JOLIN.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-31 Cont ID  
Sent By skennedy Date 2014-01-29 Time 08:54 Rev Time 0.00
Received By skennedy Date 2013-12-13 Time 09:38 Sent To  
Notes
2014-01-29 13:39:11SENT TO SH DESK
2013-12-14 09:38:48B33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-01-02 Cont ID  
Sent By jwitmer Date 2014-01-02 Time 18:05 Rev Time 0.00
Received By jwitmer Date 2014-01-02 Time 18:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-01-09 Cont ID  
Sent By hmoser Date 2014-01-09 Time 08:17 Rev Time 0.00
Received By hmoser Date 2014-01-09 Time 06:52 Sent To  
Notes
2014-01-09 08:17:09NO A/C ON PLAN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-02 Cont ID  
Sent By lwagner Date 2014-01-02 Time 10:38 Rev Time 0.00
Received By lwagner Date 2014-01-02 Time 09:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-12-30 Cont ID  
Sent By jroach Date 2013-12-30 Time 11:23 Rev Time 0.00
Received By jroach Date 2013-12-30 Time 11:23 Sent To  
Notes
2013-12-30 11:23:30ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.30.2013
 PERMIT NO.: 13120574
 ADDRESS: 4117 BROADWAY
 CONTRACTOR/CONTACT: MAJID HAWARI
 TELEPHONE NO.: 813.249.5541
 SCOPE OF REVIEW: INTERIOR AND EXTERIOR MODIFICATIONS TO
 EXISTING FOOD STORE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-441 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), BECAUSE THE
 PROPOSED SCOPE OF WORK EXCEEDS 50 PERCENT OF THE VALUE
 OF THE EXISTING STRUCTURE, THE SITE SHALL BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS. PLANS SHALL BE SUBMITTED INDICATING SUCH. IF
 EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A LANDSCAPE PERMIT. PLEASE NOTE THAT
 PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
  A. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
  B. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
  C. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
  D. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
  E. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
  F. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE PROVIDED
 WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM, INCLUDING
 THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT ANY NEW
 IRRIGATION SHALL BE DONE UNDER A SEPARATE PERMIT).
  
 2. PURSUANT TO SECTION 94-221(D)(5), STOREFRONTS SHALL
 HAVE CLEAR GLAZED AREAS ALONG A MINIMUM OF 70 PERCENT
 OF THEIR FA?ADE LENGTH, BETWEEN A HEIGHT OF TWO (2) AND
 EIGHT (8) FEET.
  
 IT IS ENCOURAGED THAT YOU MEET WITH THE CITY?S
 COMMUNITY REDEVELOPMENT AGENCY (CRA) TO DISCUSS THE
 PROPOSED RENOVATIONS, POSSIBLE INCENTIVES, ETC. YOU MAY
 CONTACT GRACE JOYCE AT (561) 822-1552 OR VIA EMAIL AT
 [email protected]
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION