Plan Review Details - Permit 13120550
Plan Review Stops For Permit 13120550
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-02-10 Cont ID  
Sent By scaldero Date 2014-02-10 Time 10:44 Rev Time 0.00
Received By scaldero Date 2014-02-10 Time 10:44 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-12-30 Cont ID  
Sent By scaldero Date 2013-12-30 Time 09:33 Rev Time 0.00
Received By scaldero Date 2013-12-30 Time 09:33 Sent To  
Notes
2013-12-30 09:35:43PERMIT #13120550
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMMENTS UNDER MECHANICAL REVIEW NEED TO BE ADDRESSED.
  
 PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
  
 PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8 INCH TALL STEEL BAFFLE OR PROVIDE 16
 INCHES OF SPACE BETWEEN THE DEEP FAT FRYER AND SURFACE
 FLAMES OF THE ADJACENT EQUIPMENT.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-14 Cont ID  
Sent By hmoser Date 2014-02-14 Time 10:37 Rev Time 0.00
Received By hmoser Date 2014-02-07 Time 17:37 Sent To  
Notes
2014-02-07 17:37:49TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-07 Cont ID  
Sent By shill Date 2013-12-30 Time 17:30 Rev Time 0.00
Received By shill Date 2013-12-13 Time 08:56 Sent To  
Notes
2013-12-14 08:57:27SENT TO MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-02-14 Cont ID  
Sent By hmoser Date 2014-02-14 Time 10:34 Rev Time 0.00
Received By hmoser Date 2014-02-14 Time 09:42 Sent To  
Notes
2014-02-14 10:37:35REVISION REQUIRED FOR GREASE DUCT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-27 Cont ID  
Sent By hmoser Date 2013-12-27 Time 12:40 Rev Time 0.00
Received By hmoser Date 2013-12-27 Time 12:40 Sent To FIRE
Notes
2013-12-27 12:49:23PLAN DENIED
 1) PROVIDE A PLAN SHOWING GREASE DUCT,
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER ON
 HOW THE EXHAUST FAN CURB IS TIED TO ROOF.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 3) AIR CONDITIONING PLANS, COOLER AND HOOD SUPPRESSION
 REQUIRE SEPARATE APPLICATION, PLAN AND PERMITS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  