| 2013-12-12 19:09:55 | 2010 FBC / 2008 NEC |
| | |
| | THE SCOPE OF WORK FOR THIS PROJECT IS TO WIRE AN |
| | EXISTING 1434 SQFT RESIDENTIAL STRUCTURE THAT WAS |
| | COMPLETELY GUTTED (ALL INTERIOR WALLS WERE REMOVED) |
| | THAT WILL HAVE AN ADDITIONAL 112 SQFT ADDED TO IT FOR A |
| | TOTAL OF 2546 SQFT. |
| | |
| | DENIED BY ELECTRICAL |
| | |
| | 1) PROVIDE TWO SETS OF PLANS WITH A SERVICE RISER |
| | DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING |
| | DETAIL. NEC 230, 250 |
| | |
| | 2) PROVIDE COMPLETE LOAD CALCULATIONS. NEC 220.40 |
| | |
| | 3) PROVIDE COMPLETE PANEL SCHEDULES. NEC 240 |
| | |
| | 4) SPECIFY THE METER AND PANEL LOCATIONS ON THE FLOOR |
| | PLANS. NEC 230, 408 |
| | |
| | 5) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT. |
| | NEC 110.9 |
| | |
| | 6) LABEL THE ROOMS ON THE ELECTRICAL FLOOR PLANS, |
| | SPECIFY THE LOCATIONS OF THE AIR HANDLERS, CONDENSING |
| | UNITS, WATER HEATER, WASHER, DRYER, KITCHEN COUNTER |
| | TOPS, BATHROOM BASINS, TUBS AND SHOWERS ON THE FLOOR |
| | PLAN TO SHOW COMPLIANCE WITH NEC 210.52, 210.63, |
| | 406.8(B) |
| | |
| | 7) SHOW COMPLIANCE WITH NEC 210.8 GFCI, 210.12 AFCI, |
| | 406.11 TAMPER-RESISTANT RECEPTACLES WHERE REQUIRED. |
| | |
| | 8) THESE PLANS SHOW A FIREPLACE THAT IS NOT SHOWN ON |
| | THE MASTER PLANS. IF THERE IS A FIREPLACE CARBON |
| | MONOXIDE DETECTORS ARE REQUIRED. FBCR 315 |
| | |
| | 9) IN ADDITION TO THE SIGNATURE, PLEASE PROVIDE THE |
| | PRINTED NAME AND LICENSE NUMBER OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN ON THE DRAWINGS. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | THIS REVIEW IS NOT INTENDED AS A PUNCH LIST TO LIST ALL |
| | OF THE DEFICIENCIES WITH THE ELECTRICAL PLANS. DUE TO |
| | THE AMOUNT OF MISSING INFORMATION IT IS SUGGESTED THAT |
| | THESE PLANS BE REVIEWED BY A LICENSED DESIGN |
| | PROFESSIONAL BEFORE THEY ARE RESUBMITTED FOR REVIEW. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |