Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-12-27 Cont ID  
Sent By jwitmer Date 2013-12-27 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2013-12-27 Time 14:13 Sent To  
Notes
2013-12-27 15:48:59BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET LS-2 RED LINED, TO KEEP EXIT LIGHT AT
 STAIRWELL 4.2, I SPOKE WITH THE DESIGNER OF RECORD TED
 DAVIS ABOUT THIS HE WAS OK WITH THE RED LINING TO KEEP
 THE EXIT LIGHT.
  
 2) A REVISION IS REQUIRED, NO PRODUCT APPROVALS WERE
 SUBMITTED, PRESSURES ARE OK. WE WILL NEED PRODUCT
 APPROVALS FOR STOREFRONT GLAZING, EXTERIOR GLAZED DOORS
 WITH PANIC HARDWARE. 2010 FBC-B 1008.1.10 REQUIRES
 PANIC HARDWARE WITH AN ASSEMBLY OCUPANCY OVER 50
 OCCUPANTS.
  
 3) ALL EXIT DOORS WILL REQUIRE PANIC HARDWARE 2010
 FBC-B 1008.1.10.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-03-26 Cont ID  
Sent By albarran Date 2014-03-26 Time 11:34 Rev Time 0.00
Received By albarran Date 2014-03-26 Time 10:56 Sent To I
Notes
2014-03-26 11:37:03THIS APPLICATION WAS APPROVED CONTINGENT ON THE
 ELECTRICAL CONDITIONS NOTED ON THE APPROVED PLANS. SOME
 OF THOSE CONDITIONS ARE EXPRESSED ON THE PLANS BUT NOT
 CLEARLY.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-03-03 Cont ID  
Sent By albarran Date 2014-03-03 Time 16:46 Rev Time 0.00
Received By albarran Date 2014-03-03 Time 16:20 Sent To I
Notes
2014-03-03 16:36:42OBVIOUSLY, ALL OF THE PRIOR ELECTRICAL PLAN REVIEW
 COMMENTS HAVE BEEN IGNORED, IN CASE YOU DON'T HAVE
 ACCESS TO A COPY OF THE FLORIDA BLDG. CODE, FOLLOWING
 IS A RECAP OF ALL PREVIOUS COMMENTS ALONG WITH THE FBC
 SECTION STATING THE MINIMUM REQUIREMENTS FOR PLAN
 REVIEW. FBC-B 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS ARE PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL
 AS INDICATED ON THE PREVIOUS REVIEW, NO ELECTRICAL
 SHEET PROVIDED FOR ELECTRICAL REVIEW
 AN ELECTRICAL SHEET REFLECTING THE OUTLET PLACEMENT
 WITH THEIR DESIGNATED CIRCUIT FOR EACH ELECTRICAL
 DEVICE INSTALLED, INC. EXIT & EMERGENCY LIGHTS. ALL
 EMERGENCY LIGHTING SHALL BE CONNECTED TO A LIGHTING
 CIRCUIT WITHIN THE AREA THEY OCCUPY.
 THIS SHEET SHALL ALSO INCLUDE THE REQUIRED SIGN AND
 SHOW WINDOW OUTLETS REQUIRED BY NEC. YOU SHALL ALSO
 PROVIDE THE REQUIRED NUMBER OF SETS.
 THOUGH MINIMAL, THERE ARE DIFFERENT ELECTRICAL
 REQUIREMENTS FOR THE DIFFERENT OCCUPANCIES. AN
 ELECTRICAL DRAWING SHOWING THE REQUIRED LIGHTING, EXIT
 AND EMERGENCY LIGHTS AS WELL AS THE REQUIRED SIGN AND
 SHOW WINDOW CIRCUITS. A PANEL SCHEDULE AND ELECTRICAL
 LOAD CALCS SHALL BE PROVIDED. ALL LIGHTING AND SIGNAGE
 SHALL ADHERE TO THE REQUIREMENTS OF THE FBC-ENERGY
 CONSERVATION SECTION 505.
 NO ELECTRICAL DRAWING PROVIDED.FOR REVIEW.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT: MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER,
 PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  
2014-02-28 09:49:43MALBARRAN TO REVIEW ELECTRICAL INFORMATION PROVIDED ON
 SHEET LS-2

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-02-19 Cont ID  
Sent By albarran Date 2014-02-19 Time 12:07 Rev Time 0.00
Received By albarran Date 2014-02-19 Time 11:48 Sent To FIRE
Notes
2014-02-19 12:12:34AS INDICATED ON THE PREVIOUS REVIEW, NO ELECTRICAL
 SHEET PROVIDED FOR ELECTRICAL REVIEW
 AN ELECTRICAL SHEET REFLECTING THE OUTLET PLACEMENT
 WITH THEIR DESIGNATED CIRCUIT FOR EACH ELECTRICAL
 DEVICE INSTALLED, INC. EXIT & EMERGENCY LIGHTS.
 THIS SHEET SHALL ALSO INCLUDE THE REQUIRED SIGN AND
 SHOW WINDOW OUTLETS REQUIRED BY NEC. YOU SHALL ALSO
 PROVIDE THE REQUIRED NUMBER OF SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-01-08 Cont ID  
Sent By albarran Date 2014-01-08 Time 18:18 Rev Time 0.00
Received By albarran Date 2014-01-08 Time 18:12 Sent To FIRE
Notes
2014-01-08 18:23:39THOUGH MINIMAL, THERE ARE DIFFERENT ELECTRICAL
 REQUIREMENTS FOR THE DIFFERENT OCCUPANCIES. AN
 ELECTRICAL DRAWING SHOWING THE REQUIRED LIGHTING, EXIT
 AND EMERGENCY LIGHTS AS WELL AS THE REQUIRED SIGN AND
 SHOW WINDOW CIRCUITS. A PANEL SCHEDULE AND ELECTRICAL
 LOAD CALCS SHALL BE PROVIDED. ALL LIGHTING AND SIGNAGE
 SHALL ADHERE TO THE REQUIREMENTS OF THE FBC-ENERGY
 CONSERVATION SECTION 505.
 NO ELECTRICAL DRAWING PROVIDED.FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-02-24 Cont ID  
Sent By scaldero Date 2014-02-24 Time 11:36 Rev Time 0.00
Received By scaldero Date 2014-02-24 Time 11:36 Sent To I
Notes
2014-02-19 12:14:17ROUTED TO FIRE BIN

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-01-13 Cont ID  
Sent By scaldero Date 2014-01-13 Time 16:52 Rev Time 0.00
Received By scaldero Date 2014-01-13 Time 16:52 Sent To I
Notes
2014-01-13 17:18:10PERMIT #13120518
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***FAILED COMMENTS****
  
 WHERE SOCCER FIELD #4 IS TO BE LOCATED, THERE SHOWS A
 FAX/COPY ROOM. THIS ROOM SHOULD BE RELOCATED TO AN AREA
 NOT OCCUPIED BY A FIELD.
  
 ALL EXIT DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 PRODUCT DETAILS FOR EQUIPMENT AND/OR FURNISHINGS TO BE
 USED INSIDE SOCCER FIELD #4 AND ON THE FIRST FLOOR
 EXERCISE ROOM NEED TO BE PROVIDED. THE INTERIOR FINISH
 MATERIALS FOR WALLS, CEILINGS, AND FLOORS SHALL MEET
 THE REQUIRED SMOKE DEVELOPMENT AND FLAME SPREAD
 REQUIREMENTS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
2014-01-08 18:27:20PLACED IN FIRE BIN

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-03-26 Cont ID  
Sent By skennedy Date 2014-03-26 Time 14:14 Rev Time 0.00
Received By skennedy Date 2014-03-26 Time 09:45 Sent To  
Notes
2014-03-26 11:41:04TO SAK FOR DETERMINATION OF ROUTING TO IMPACT
  
2014-03-26 09:45:39TO MA DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-03-14 Cont ID  
Sent By skennedy Date 2014-03-14 Time 13:17 Rev Time 0.00
Received By skennedy Date 2014-03-14 Time 13:17 Sent To E
Notes
2014-03-14 13:17:57SENT TO MALBARRAN DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2014-03-03 Cont ID  
Sent By skennedy Date 2014-03-03 Time 16:45 Rev Time 0.00
Received By albarran Date 2014-02-28 Time 09:48 Sent To  
Notes
2014-03-03 16:46:12SMALL DENIED BIN "D"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-24 Cont ID  
Sent By scaldero Date 2014-02-24 Time 11:36 Rev Time 0.00
Received By scaldero Date 2014-02-14 Time 12:08 Sent To  
Notes
2014-02-15 12:08:56C09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-22 Cont ID  
Sent By shill Date 2014-01-13 Time 14:42 Rev Time 0.00
Received By shill Date 2013-12-12 Time 14:30 Sent To  
Notes
2013-12-12 14:32:57EXPEDITED C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-03-28 Cont ID  
Sent By jwitmer Date 2014-03-28 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2014-03-28 Time 14:15 Sent To  
Notes
2014-03-28 14:16:313/38/2014
 P B COUNTY IMPACT FEE ASSESSMENT
 MU201210236
 NO FEES DUE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-03-26 Cont ID  
Sent By JWITMER Date 2014-03-26 Time 14:13 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2014-03-26 14:13:46SEE PREVIOUS REVIEW COMMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-12-27 Cont ID  
Sent By jwitmer Date 2013-12-27 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2013-12-27 Time 15:55 Sent To  
Notes
2013-12-27 15:58:00ONLY THE NEW 1ST FLOOR GYM WILL NEED TO BE ASSESSED,
 THE NEW 2ND FLOOR SOCCER FIELD WAS ASSESSED UNDER
 PERMIT 12030117/ COUNTY IMPACT # MU 2012 010236 0000.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-01-02 Cont ID  
Sent By hmoser Date 2014-01-02 Time 14:37 Rev Time 0.00
Received By hmoser Date 2014-01-02 Time 14:27 Sent To  
Notes
2014-01-02 14:37:50NO MECHANICAL PLAN SUBMITTED.
 HAVE AIRCONDITIONING CONTRACTOR SUBMIT
 HIS OWN APPLICATION AND PLANS FOR PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6676
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-12-30 Cont ID  
Sent By lwagner Date 2013-12-30 Time 08:34 Rev Time 0.00
Received By lwagner Date 2013-12-30 Time 07:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-12-20 Cont ID  
Sent By dkittred Date 2013-12-20 Time 10:38 Rev Time 0.00
Received By dkittred Date 2013-12-18 Time 12:36 Sent To  
Notes
2013-12-18 10:35:4012/18/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved