Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-02-04 Cont ID  
Sent By rmcdouga Date 2014-02-04 Time 07:57 Rev Time 0.00
Received By rmcdouga Date 2014-02-04 Time 06:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-01-22 Cont ID  
Sent By rmcdouga Date 2014-01-22 Time 18:04 Rev Time 0.00
Received By rmcdouga Date 2014-01-21 Time 18:04 Sent To Z
Notes
2014-01-22 18:04:492010 FBC
  
 DENIED BY BUILDING
  
 1) ON SHEET 3 THE SECTION MARKER FOR A-A IS NOT IN THE
 CORRECT LOCATION ON THE SLAB, BEAM AND COLUMN PLAN
 BASED ON WHAT IS SHOWN IN THE SECTION A-A DETAIL.
 PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE 8" X 12"
 BEAM TIES INTO THE EXTERIOR WALL. IT APPEARS FROM THE
 WAY THIS BEAM IS SHOWN ON THE SLAB, BEAM AND COLUMN
 PLAN THAT THERE IS A WALL AND A COLUMN UNDER THE 8" X
 12" TIE BEAM. PLEASE CLARIFY.
  
 2) THE MULE-HIDE SELF ADHERED ROOFING PRODUCT APPROVAL
 THAT WAS SUBMITTED FOR THE FLAT ROOF IS FOR A STEEL
 DECK. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 FLAT ROOF THAT IS FOR A WOOD DECK AS REQUIRED BY DCA
 RULE 9N-3. IF THE DESIGN PRESSURE FOR THE SYSTEM IS
 LESS THAN THE - 96 PSF REQUIRED AT THE CORNERS OF THE
 FLAT ROOFS, SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING OF THE BASE
 SHEET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-17 Cont ID  
Sent By rmcdouga Date 2013-12-17 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2013-12-16 Time 18:30 Sent To Z
Notes
2013-12-17 16:04:092010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENGINEER NEEDS TO EVALUATE THE STRUCTURAL DESIGN
 SPECIFIED AT THE EXTERIOR WALL FOR THE 8 X 12 CONCRETE
 BEAM WITH (4) # 4 BARS SHOWN IN SECTION A - A ON SHEET
 3 AND PROVIDE CALCULATIONS. THE PLANS SHOW 2 FILLED
 CONCRETE BLOCK AT THE EXTERIOR WALL RATHER THAN A
 FORMED AND POURED CONCRETE COLUMN LIKE THE ONE ON THE
 OTHER END. CITY AMENDMENTS 107.2.1.3 NOTE: RATHER THAN
 HAVE A BEAM BELOW THE CEILING, THIS BEAM COULD BE
 ELIMINATED BY USING ROOF GIRDER TRUSSES TO HANG THE
 EXISTING AND NEW TRUSSES ON.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 LARGE MISSILE IMPACT RATED EXTERIOR DOORS AND WINDOWS
 DO NOT HAVE THE DBPR APPROVED INSTALLATION AND
 EVALUATION INFORMATION ATTACHED TO THE FLORIDA FL#
 COVER-SHEETS. THEY ALL HAVE MIAMI-DADE NOAS AS THEIR
 APPROVED INFORMATION. THIS IS THE LINK TO THE FLORIDA
 PRODUCT APPROVAL WEB SITE WHERE YOU CAN PRINT OUT THE
 APPROVED INFORMATION THAT IS REQUIRED TO BE SUBMITTED
 BY DCA RULE 9N-3.
 HTTP://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOTING MATERIAL THAT WILL BE INSTALLED ON THE FLAT
 ROOF. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING AT THE PERIMETER
 AND CORNER ROOF AREAS IF THE MAXIMUM DESIGN PRESSURES
 FOR THE SELECTED SYSTEM FROM THE PRODUCT APPROVAL ARE
 NOT ADEQUATE FOR THESE AREAS. FBC R301.2.1.
  
 4) SPECIFY THE METHOD OF ATTACHMENT FROM THE ROOF TILE
 PRODUCT APPROVAL THAT WILL BE USED TO INSTALL IT AND
 RESIST THE REQUIRED OVERTURN MOMENT. IF A ROOF TILE
 ADHESIVE WILL BE USED SUBMIT TWO COPIES OF IT'S PRODUCT
 APPROVALS THAT HAVE BEEN APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. DCA RULE 9N-3 AND CITY AMENDMENTS
 107.3.4.1
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AND THE SIMPSON CONNECTORS
 THAT WILL BE USED AND THAT HAVE BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND
 CITY AMENDMENTS 107.3.4.1
  
 6) SUBMIT TWO COPIES OF THE ICC-ES EVALUATION REPORT
 FOR THE ICYNENE SPRAY FOAM INSULATION. CITY AMENDMENTS
 107.2.1.3
  
 7) THE PLANS SPECIFY A 4' 0" X 6' 8" EXTERIOR SLIDING
 GLASS DOOR AT THE LAUNDRY. THIS IS NOT A STANDARD SIZE
 SLIDING GLASS DOOR AND WOULD PROVIDE AN OPENING LESS
 THAN 2 FEET WIDE. PLEASE CLARIFY IF THIS IS YOUR
 INTENT. CITY AMENDMENTS 107.2.1 THE SMALLEST SGD WIDTH
 ON THE PRODUCT APPROVAL THAT WAS SUBMITTED IS 5 FEET.
  
 8) TWO SETS OF PLANS ARE REQUIRED PER CITY AMENDMENTS
 107.1. ONLY ONE ROOF FRAMING PLAN WAS SUBMITTED. SUBMIT
 AN ADDITIONAL PLAN SHEET T-1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-21 Cont ID  
Sent By rmcdouga Date 2014-01-21 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2014-01-21 Time 18:39 Sent To  
Notes
2014-01-21 18:40:16REDLINED PLANS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-17 Cont ID  
Sent By rmcdouga Date 2013-12-17 Time 06:58 Rev Time 0.00
Received By rmcdouga Date 2013-12-17 Time 06:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-04 Cont ID  
Sent By rmcdouga Date 2014-02-04 Time 07:57 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2014-01-31 10:00:24INCOMING SENT TO R. MCDOUGAL'S DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2014-01-23 Cont ID  
Sent By dkittred Date 2014-01-23 Time 13:02 Rev Time 0.00
Received By dkittred Date 2014-01-21 Time 18:03 Sent To  
Notes
2014-01-23 13:01:321/23/2014
  
 NOTIFIED CONTRACTOR VIA PHONE THE PLANS WERE DENIED.
 PLANS FILED IN LARGE DENIED BIN 'S'. DK
  
2014-01-21 11:39:27GIVEN TO RMCDOUGA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2013-12-18 Cont ID  
Sent By dkittred Date 2013-12-18 Time 16:05 Rev Time 0.00
Received By dkittred Date 2013-12-10 Time 18:13 Sent To  
Notes
2013-12-18 16:06:2512/18/13
 NOTIFIED CONTRACTOR VIA PHONE AND EMAIL THE PLANS WERE
 DENIED. PLANS FILED IN DENIED PLANS UNDER 'S'. DK
2013-12-11 18:18:37R01 EXPEDITED

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-02-04 Cont ID  
Sent By rmcdouga Date 2014-02-04 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2014-02-04 Time 08:31 Sent To  
Notes
2014-02-04 08:32:13MU 2014-1771 IMPACT FEE OF $408.24 WAS PAID. VERIFIED
 BY PHONE CALL TO WILLIE SWOOPES ON 2/4/2014.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-12-16 Cont ID  
Sent By rmcdouga Date 2013-12-16 Time 18:31 Rev Time 0.00
Received By rmcdouga Date 2013-12-16 Time 18:31 Sent To  
Notes
2013-12-16 18:33:37AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.
 ADDING 1300 SQFT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-02-04 Cont ID  
Sent By rmcdouga Date 2014-02-04 Time 06:57 Rev Time 0.00
Received By rmcdouga Date 2014-02-04 Time 06:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-01-22 Cont ID  
Sent By rmcdouga Date 2014-01-22 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2014-01-22 Time 06:55 Sent To  
Notes
2014-01-22 13:08:122010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE ROOF
 A/C STAND HAS BEEN CLOSED BY MIAMI-DADE AND IS NO
 LONGER ACCEPTABLE. SUBMIT A CURRENT PRODUCT APPROVAL.
 DCA RULE 9N-3
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS, INSTALLATION INSTRUCTIONS AND LISTING
 INFORMATION FOR THE EXHAUST HOOD THAT IS SHOWN ON THE
 EXTERIOR AT THE COVERED PORCH.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-17 Cont ID  
Sent By rmcdouga Date 2013-12-17 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2013-12-17 Time 06:40 Sent To  
Notes
2013-12-17 09:44:532010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS ARE FOR WORST CASE. THE 2010 FBC ENERGY
 CONSERVATION SECTION 403.6.1 REQUIRES EQUIPMENT LOAD
 CALCULATIONS TO BE BASED ON THE BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. PLEASE SUBMIT
 LOAD CALCULATIONS THAT ARE BASED ON THE ACTUAL
 DIRECTIONAL ORIENTATION OF THE BUILDING.
  
 2) THE HEATING AND COOLING EQUIPMENT SPECIFIED ON THE
 PLANS IS REQUIRED TO MATCH THE EQUIPMENT SIZING
 CALCULATIONS AND THE ENERGY CALCULATIONS. FBC ENERGY
 CONSERVATION SECTION 403.6.1 AND CITY AMENDMENTS
 107.2.1
  
 3) THE ENERGY CALCULATION FORM WAS NOT SIGNED BY THE
 OWNER/AGENT. FBC ENERGY CONSERVATION SECTION 405.4
  
 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOF
 TOP A/C STANDS AS REQUIRED BY DCA RULE 9N-3 AND FBCR
 M1307.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-21 Cont ID  
Sent By rmcdouga Date 2014-01-21 Time 18:17 Rev Time 0.00
Received By rmcdouga Date 2014-01-21 Time 18:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-12-17 Cont ID  
Sent By rmcdouga Date 2013-12-16 Time 18:50 Rev Time 0.00
Received By rmcdouga Date 2013-12-16 Time 18:30 Sent To  
Notes
2013-12-17 16:59:52DENIED BY PLUMBING
  
 TWO SETS OF PLANS ARE REQUIRED PER CITY AMENDMENTS
 107.1. ONLY ONE PLUMBING PLAN WAS SUBMITTED. SUBMIT AN
 ADDITIONAL PLUMBING PLAN SHEET P-1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-02-04 Cont ID  
Sent By rmcdouga Date 2014-02-04 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2014-02-04 Time 08:00 Sent To  
Notes
2014-02-04 08:10:04ROOFING PRODUCT APPROVALS THAT WERE SUBMITTED:
  
 1) ENTEGRA PLANTATION ROOF TILE, NOA NO. 10-1202.01
  
 2) 3M AH-160 ROOF TILE ADHESIVE, NOA NO. 12-0228.18
  
 3) FLAT ROOF = MULE-HIDE SELF-ADHERED ROOF SYSTEM, NOA
 NO. 13-0514.12

Review Stop Z ZONING
Rev No 2 Status P Date 2014-01-23 Cont ID  
Sent By dkittred Date 2014-01-23 Time 12:59 Rev Time 0.00
Received By dkittred Date 2014-01-23 Time 08:13 Sent To  
Notes
2014-01-23 08:13:491/23/14 - ZONING RECEIVED. SENT TO DK FOR REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status F Date 2013-12-18 Cont ID  
Sent By dkittred Date 2013-12-18 Time 15:49 Rev Time 0.00
Received By dkittred Date 2013-12-18 Time 12:37 Sent To  
Notes
2013-12-18 15:49:40PLANNING AND ZONING COMMENTS: ***FAILED***
  
 12/18/13
 1. THE FRONT AND SIDE SETBACKS ON THE PLOT PLAN DO NOT
 FULLY COMPLY WITH THE ZONING CODE [FRONT SETBACK - 25
 FEET; SIDE SETBACK - MINIMUM OF 5 FEET AND TOTAL OF 15
 FEET]. PLEASE INDICATE ON THE SURVEY THE SETBACKS OF
 THE EXISTING STRUCTURE (IF THERE IS ANY
 NON-CONFORMANCE, THEY CAN REMAIN, JUST NOT BE
 INCREASED) AND PROPOSED SETBACKS OF THE NEW ADDITION.
  
 2. THE CONSTRUCTION PLANS INDICATE A COVERED PORCH WILL
 BE CONSTRUCTED ON THE REAR AND FRONT OF THE HOUSE.
 THESE COVERED PORCH STRUCTURES, WITH THEIR SETBACKS,
 NEED TO BE SHOWN ON THE PLOT PLAN.
  
 3. THE VALUE OF THE CONSTRUCTION ($150,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($57,208) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. (NOTE: ZLDR SEC.
 94-442(B)(2)A. ? FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.)
  
 4. TWO ON SITE PARKING SPACES ARE REQUIRED FOR SINGLE
 FAMILY HOME. IT APPEARS THE NEW ADDITION WILL EXTEND
 INTO AN EXISTING DRIVEWAY. PLEASE DEMONSTRATE HOW TWO
 PARKING SPACES WILL BE ACCOMMODATED ON THE SITE WITH
 THE PROPOSED RENOVATION.
  
 5. IF ANY TREES WILL BE REMOVED OR RELOCATED WITH THE
 PROPOSED ADDITION, A TREE ALTERATION PERMIT THROUGH THE
 PLANNING DIVISION IS REQUIRED.
  
2013-12-18 11:01:4512/18/13