Plan Review Details - Permit 13120421
Plan Review Stops For Permit 13120421
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-21 Cont ID  
Sent By skennedy Date 2014-01-21 Time 10:57 Rev Time 0.00
Received By skennedy Date 2014-01-21 Time 10:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By albarran Date 2013-12-11 Time 16:30 Rev Time 0.00
Received By albarran Date 2013-12-11 Time 16:14 Sent To I
Notes
2013-12-11 16:39:07THIS PERMIT APPLICATION IS A BIT AMBIGUOUS. BE MORE
 SPECIFIC IF YOU ARE REPLACING TWO COMPLETE SETS, OR
 JUST ONE COMPONENT OF TWO SEPARATE SYSTEMS.
 THE SUBMITTED ONE LINE DIAGRAM DOES NOT COINCIDE WITH
 THE WORDING AND/OR THE ATTACHED LITERATURE. PLEASE
 PROVIDE A BETTER DESCRIPTION OF THE SCOPE OF WORK
 ACCOMPANIED BY THE LITERATURE OF THE INTENDED
 COMPONENTS.
 FURTHERMORE, FBC-R303.8 REQUIRES HEATING, THEREFOR
 UNLESS HEATING IS PROVIDED BY OTHER MEANS, THESE UNITS
 SHALL INCLUDE A HEATING ELEMENT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-21 Cont ID  
Sent By skennedy Date 2014-01-21 Time 10:57 Rev Time 0.00
Received By skennedy Date 2014-01-14 Time 15:47 Sent To  
Notes
2014-01-14 15:48:30RESUBMITTAL SENT TO ELECTRICAL UNDER $5000 SHELF FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-13 Cont ID  
Sent By shill Date 2013-12-13 Time 15:46 Rev Time 0.00
Received By shill Date 2013-12-10 Time 15:40 Sent To  
Notes
2013-12-11 16:39:44SENT TO SH DESK
2013-12-10 15:40:46ROUTED TO ELECTRICAL $5000 & UNDER