Plan Review Details - Permit 13120411
Plan Review Stops For Permit 13120411
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 09:02 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-30 Cont ID  
Sent By jwitmer Date 2013-12-30 Time 16:31 Rev Time 0.00
Received By jwitmer Date 2013-12-30 Time 15:42 Sent To  
Notes
2013-12-30 16:31:00BUILDING PLAN REVIEW
 PERMIT: 13120411
 ADD: 6651 N JOG RD
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MONDAY DEC. 30/2013
 ACTION: DENIED
  
 1) LETTER FROM HEAVY STURTURES DESCRIBING WHICH PRODUCT
 APPROVALS THEY WERE GOING TO INSTALLDOES NOT MATCH THE
 PRODUCT APPROVAL COVER SHEETS SUBMITTED. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SUBMITTED PRODUCT APPROVAL MIAMI-DADE NOA 10-0901.20
 THE TECHNICAL DRAWINGS WERE NOT LOADED IN LANDSCAPE AND
 1/2 OF THE INFORMATION IS LEFT OFF THE PAGE (6-11)
 THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE OR COULD,
 PLEASE IDENTIFY WHICH SUB-SYSTEM IS BEING INSTALLED AND
 PRESSURES CAN BE VERIFIED.
  
 3) MIAMI-DADE NOA 10-0901.18 WAS NEVER SUBMITTED. NOTE
 THIS PRODUCT APPROVAL WAS NOT PART OF HEAVY STRUCTURES
 APPROVAL LETTER. FLORIDA APPROVAL # FL 12493-R1 BUTLER
 PANELWALL, THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE
 OR CLOUD. THE EVALUATION REPORT FOR LIMITATION & LOAD
 TABLES NOR THE INSTALATION INSTRUCTIONS WERE NOT
 UPLOADED. NO REVIEW CAN TAKE PLACE WITHOUT THIS
 INFORMATION.
  
 4) FLORIDA APPROVAL # FL 12760-R1 BUTLER PANEL WALL/
 LITE PANEL. THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE
 OR CLOUD. THE EVALUATION REPORT FOR LIMITATION & LOAD
 TABLES NOR THE INSTALATION INSTRUCTIONS WERE NOT
 UPLOADED. NO REVIEW CAN TAKE PLACE WITHOUT THIS
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-29 Cont ID  
Sent By dharvey Date 2014-01-29 Time 15:18 Rev Time 0.00
Received By dharvey Date 2014-01-29 Time 14:17 Sent To  
Notes
2014-01-29 15:18:42BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-26 Cont ID  
Sent By wjolin Date 2013-12-26 Time 08:39 Rev Time 0.00
Received By wjolin Date 2013-12-26 Time 07:47 Sent To  
Notes
2013-12-26 08:26:596651 NORTH JOG ROAD - TURBINE GENERATOR
 TRACKING #13120411
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO - SUBMIT REVISION
  
 HOSE REEL WITH 1-1/2" HOSE VALVES APPEAR TO HAVE
 PRESSURES THAT WILL EXCEED 100 PSI. PER NFPA 14 SECTION
 7.2.3.1, WHERE THE RESIDUAL PRESSURE AT A 1-1/2" OUTLET
 ON A HOSE CONNECTION AVAILABLE FOR TRAINED PERSONNEL
 USE EXCEEDS 100 PSI, AN APPROVED PRESSURE-REGULATING
 DEVICE SHALL BE PROVIDED TO LIMIT THE RESIDUAL PRESSURE
 TO 100 PSI. ALSO PER NFPA 14 SECTION 7.2.3.2, AN
 APPROVED PRESSURE-REGULATING DEVICE SHALL BE PROVIDED
 TO LIMIT STATIC AND RESIDUAL PRESSURES AT THE OUTLET OF
 THE HOSE CONNECTION TO 100 PSI FOR 1-1/2" HOSE
 CONNECTIONS AVAILABLE FOR TRAINED PERSONNEL USE AND 175
 PSI FOR OTHER HOSE CONNECTIONS.
  
 TO AVOID PRESSURE REGULATING DEVICES I WOULD RECOMMEND
 A TRUE CLASS I STANDPIPE SYSTEM (2-1/2 FDVS ONLY) AND
 ELIMINATE THE 1-1/2" FDVS WITH HOSE AND REEL BECAUSE
 FIRE DEPARTMENT PERSONNEL WILL NOT USE THIS EQUIPMENT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2014-02-18 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-29 Cont ID  
Sent By skennedy Date 2014-01-29 Time 15:33 Rev Time 0.00
Received By skennedy Date 2013-12-10 Time 09:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-12-11 Cont ID  
Sent By rregueir Date 2013-12-11 Time 09:39 Rev Time 0.00
Received By rregueir Date 2013-12-11 Time 09:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-27 Cont ID  
Sent By jwitmer Date 2014-01-27 Time 18:59 Rev Time 0.00
Received By jwitmer Date 2014-01-27 Time 18:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-04-03 Cont ID  
Sent By skennedy Date 2014-04-03 Time 14:53 Rev Time 0.00
Received By skennedy Date 2014-03-28 Time 14:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-02 Cont ID  
Sent By eschneid Date 2014-01-02 Time 18:38 Rev Time 0.75
Received By eschneid Date 2014-01-02 Time 18:38 Sent To  
Notes
2014-01-02 18:39:29A FINAL AS-BUILT SITE PLAN SHALL BE SUBMITTED TO THE