Plan Review Details - Permit 13120390
Plan Review Stops For Permit 13120390
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-12-11 Cont ID  
Sent By skennedy Date 2013-12-11 Time 17:47 Rev Time 0.00
Received By skennedy Date 2013-12-11 Time 17:47 Sent To  
Notes
2013-12-12 16:45:5212/12/13 - ADDED CORK SUBMITTAL TO PLANS.
2013-12-11 17:56:43PROVISIONALLY APPROVED. PROVIDE A SUBMITTAL TO
 DEMONSTRATE COMPLIANCE WITH THE SECTION BELOW FOR
 PROPOSED FLOORING:
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-11 Cont ID  
Sent By skennedy Date 2013-12-11 Time 17:47 Rev Time 0.00
Received By skennedy Date 2013-12-11 Time 17:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-11 Cont ID  
Sent By skennedy Date 2013-12-11 Time 18:05 Rev Time 0.00
Received By skennedy Date 2013-12-10 Time 17:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-12-11 Cont ID  
Sent By skennedy Date 2013-12-11 Time 17:48 Rev Time 0.00
Received By skennedy Date 2013-12-11 Time 17:48 Sent To  
Notes
***NONE***