Plan Review Details - Permit 13120321
Plan Review Stops For Permit 13120321
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-10 Cont ID  
Sent By hmoser Date 2013-12-10 Time 15:53 Rev Time 0.00
Received By hmoser Date 2013-12-09 Time 11:13 Sent To  
Notes
2013-12-09 11:13:43ROUTED TO MECHANICAL LESS THAN 5000

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-19 Cont ID  
Sent By hmoser Date 2013-12-19 Time 08:25 Rev Time 0.00
Received By hmoser Date 2013-12-19 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-10 Cont ID  
Sent By hmoser Date 2013-12-10 Time 15:53 Rev Time 0.00
Received By hmoser Date 2013-12-10 Time 15:40 Sent To  
Notes
2013-12-10 15:53:05PLAN DENIED
 1) PROVIDE WIND CALCULATIONS FOR WALK IN COOLER &
 FREEZER
 PER SECTION 301.12 WIND RESISTANCE.
 2) VALUE IS TO LOW COOLER FREEZER MUST BE ADDED TO
 VALUE
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  