| Plan Review Stops For Permit 13120279 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-02-10 |
|
|
Cont ID |
|
| Sent By |
SHILL |
Date |
2014-02-10 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-02-10 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2014-02-04 14:18:38 | RETURNED TO BIN B 15 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-12-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-12-14 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-12-14 |
Time |
13:08 |
Sent To |
FIRE |
|
| Notes |
| 2013-12-14 13:14:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLAN IS TOO SMALL AND ILLEGIBLE. PROVIDE FULL SIZE | | | LEGIBLE SHEETS FBC 107. | | | | | | 2. IT APPEARS THAT WILLIAM H ROBERTS, PE IS PROPOSING | | | MECHANICAL, ELECTRICAL AND BUILDING CHANGES TO THE | | | DESIGN OF HLR ARCHITECTS. IS THIS NEW DESIGNER TAKING | | | OVER THIS PROJECT? THERE IS A PROCESS FOR THIS WHICH | | | INCLUDES NEW PLANS SUBMITTED, SEE FAC61G15. ENGINEER IS | | | MODIFING FIRE RATED WALLS ON A MECHANICAL SHEET - THIS | | | SHOULD ALSO BE DONE ON THE ARCHITECTURAL SHEETS. REVISE | | | ORIGINAL SUBMITTED PLAN PAGES. ALL CHANGES TO BE | | | INDICATED WITH CLOUDS AND REVISION NUMBERS. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-02-24 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-24 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-24 |
Time |
15:18 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-02-04 |
|
|
Cont ID |
|
| Sent By |
ALBARRAN |
Date |
2014-02-04 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-04 |
Time |
13:32 |
Sent To |
B |
|
| Notes |
| 2014-02-04 14:17:49 | NOW THAT LEGIBLE DRAWINGS HAVE BEEN PROVIDED A REVIEW | | | HAS BEEN COMPLETED. THE FOLLOWING CORRECTIONS ARE | | | REQUIRED: | | | 1.THE VERTICAL CLEARANCE FOR THE SERVICE SHALL COMPLY | | | WITH ALL THE REQUIREMENTS OF NEC 230.24 | | | 2. THOUGH INCLUDED IN THE LOAD CALCS OF THE PANEL, THE | | | REQUIRED SHOW WINDOW OUTLETS ARE NOT REFLECTED ON THE | | | DRAWINGS. FURTHERMORE, THE OUTLET REQUIRED BY NEC 600.5 | | | SHALL BE INCLUDED AS WELL. | | | 3. AS PER NEC 210.8, ALL OUTLETS IN THE KITCHEN AREA | | | SHALL BE GFI PROTECTED. | | | 4. SERVICE GROUNDING SHALL BE IN ACCORDANCE WITH | | | ARTICLE 250 OF THE NEC | | | 5. AS PER THE FBC AND NFPA, EMERGENCY LIGHTING IS | | | REQUIRED IN THE BATHROOMS. | | | 6. A PROPER LIGHTING SCHEDULE AND DIAGRAM MEETING THE | | | REQUIREMENTS OF FBC-ENERGY CONSERVATION SHALL BE | | | PROVIDED. | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | | PH: (561) 805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-12-27 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-12-27 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-12-27 |
Time |
10:21 |
Sent To |
I |
|
| Notes |
| 2013-12-27 12:44:54 | THIS IS THE SECOND TIME THESE PLANS ARE REJECTED FOR | | | ILLEGIBLE PLANS. AS PER FBC SECTION 107, LEGIBLE PLANS | | | SHALL BE SUBMITTED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2014-02-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-02-21 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-02-21 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2014-02-21 12:06:20 | 710 NORTH SAPODILLA AVENUE | | | TRACKING #13120279 | | | PERMIT #13060319 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF | | | HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY | | | (MERCANTILE) OF THE BUILDING, SHALL BE SEPARATED FROM | | | NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR | | | BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS | | | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND | | | FIRE-RATED FOR AT LEAST 45-MINUTES. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2014-01-31 |
|
|
Cont ID |
|
| Sent By |
WJOLIN |
Date |
2014-01-31 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-01-28 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2014-01-31 13:44:12 | 710 NORTH SAPODILLA AVENUE | | | TRACKING #13120279 | | | PERMIT #13060319 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF | | | HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY | | | (MERCANTILE) OF THE BUILDING, SHALL BE SEPARATED FROM | | | NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR | | | BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS | | | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND | | | FIRE-RATED FOR AT LEAST 45-MINUTES. | | | | | | NOTE: THIS SAME REQUIREMENT WAS WRITTEN ON THE PLANS BY | | | THE FIRE DEPARTMENT ON 09/10/13. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-12-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-12-21 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-12-21 |
Time |
09:30 |
Sent To |
E |
|
| Notes |
| 2013-12-21 09:32:11 | PLANS WILL BE SIGNED, STAMPED AND DATED BY THE FIRE | | | DEPARTMENT ONCE THE BUILDING REVIEW COMMENTS HAVE BEEN | | | ADDRESSED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-02-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-02-24 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-01-16 |
Time |
19:05 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-01-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-01-02 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-12-06 |
Time |
18:14 |
Sent To |
|
|
| Notes |
| 2013-12-14 13:22:32 | 12/14 TO FIRE | | | | | 2013-12-13 16:01:38 | 12/13 TO SH DESK | | | | | 2013-12-10 11:39:47 | SENT TO HMOSER DESK | | 2013-12-06 18:14:54 | SENT TO ELECTRICAL BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-02-14 |
|
|
Cont ID |
|
| Sent By |
HMOSER |
Date |
2014-02-04 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-02-04 |
Time |
09:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-12-10 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-12-10 |
Time |
16:48 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-02-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-02-24 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-02-24 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|