| 2014-01-06 13:12:12 | BUILDING PLAN REVIEW |
| | PERMIT: 13120278 |
| | ADD: 828 SOUTHERN BLVD |
| | CONT: MCINTYRE & ELWELL & STRAMMER GC INC |
| | TEL: (941)377-6800 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 06/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A LIFE SAFETY PLAN, SHEET A1 & A2 |
| | FLOOR PLAN & THE REFLECTED CEILING PLAN INDICATE TWO |
| | MEANS OF EGRESS THAT TAKE THE GENERAL PUBLIC THROUGH |
| | THE STOCKROOM AREAS. SHEET A7 SHOWS THESE TWO AREAS |
| | WITH THE FLOORS PAINTED WITH A DEMARCATED EGRESS PATH, |
| | BUT 2010 FBC-B 1014.2.4 DOES ALLOW EGRESS THROU STORAGE |
| | ROOMS WHEN ALL THE FOLLOWING ARE MET: 2. MEANS OF |
| | EGRESS ARE NOT PROHIBITED THROUGH STOCKROOMS IN GROUP M |
| | OCCUPANCIES WHEN ALL OF THE FOLLOWING ARE MET: |
| | |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |
| | 2) SHEET A-9A DETAIL DETAIL D3 INDICATES 3 5/8 INCH |
| | FULL LENGTH STUDS AT 16 INCHES ON CENTER BUT THE |
| | MAXIMUM LENGTH OF STUD IS NOT PROVIDED NOR GAUGE OF |
| | STUD OR DEFLECTION, |
| | 2010 FBC-B TABLE 1604.3 & TABLE 2506.2 STEEL STUDS, NON |
| | LOAD BEARING. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |