Plan Review Details - Permit 13120257
Plan Review Stops For Permit 13120257
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-13 Cont ID  
Sent By rmcdouga Date 2013-12-13 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2013-12-13 Time 08:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-07 Cont ID  
Sent By rmcdouga Date 2013-12-07 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2013-12-07 Time 09:32 Sent To  
Notes
2013-12-07 10:07:402010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED WITHIN 600 FT OF THE
 INTER-COASTAL WATERWAY AND IS EXPOSURE CATEGORY D. FBC
 R301.2.1.4.3 SUBMIT REVISED RAS 117 CALCULATIONS.
  
 2) THE PROPERTY APPRAISER'S INFROMATION INDICATES THAT
 THE ROOF COVERING IS COMPOSITE SHINGLES AND NOT TILE.
 SUBMITT A SIGNED AND SEALED ENGINEER'S EVALUATION
 REPORT STATING THE THE EXISTING ROOF STRUCTURE IS
 CAPABLE OF SAFELY SUPPORTING ALL OF THE LOADS FOR THE
 PROPOSED TILE ROOF. FBC R301.1
  
 3) THE 3M RTA-1 FOAM ROOF TILE ADHESIVE IS NOT LISTED
 AS AN APPROVED TILE ADHESIVE IN THE POLYGLASS
 UNDERLAYMENT PRODUCT APPROVAL LIMITATIONS ON PAGE 4 OF
 THE EVALUATION REPORT FOR FL 5259. SEE LIMITATION #
 5.4.1 ON PAGE 4 OF 10.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-13 Cont ID  
Sent By rmcdouga Date 2013-12-13 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2013-12-13 Time 06:10 Sent To  
Notes
2013-12-13 06:10:56SENT TO R MCDOUGAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved