Plan Review Details - Permit 13120147
Plan Review Stops For Permit 13120147
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-02-18 Cont ID  
Sent By rmcdouga Date 2014-02-18 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2014-02-18 Time 09:43 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-14 Cont ID  
Sent By rmcdouga Date 2014-01-14 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2014-01-14 Time 15:39 Sent To  
Notes
2014-01-14 16:03:352010 FBC
  
 DENIED BY BUILDING
  
 1) NONE OF THE MODEL NUMBERS LISTED IN THE CONCRETE PAD
 SCHEDULE CORRESPOND TO THE GENERAC MODEL 04390-3
 GENERATOR THAT IS TO BE INSTALLED. THE GENERATOR PAD
 ENGINEERING IS VALID FOR ONE JOB AND IS REQUIRED TO
 HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL, AS
 STATED ON THE DOCUMENT.
  
 2) PROVIDE ENGINEERING THAT SPECIFIES WINDSPEED,
 EXPOSURE CATEGORY AND REQUIRED WIND LOAD PRESSURES AT
 THE JOB LOCATION AND THE ATTACHMENT METHOD AND
 FASTENERS THAT WILL BE USED TO ATTACH THE GENERATOR TO
 THE PAD AND BE CAPABLE OF RESISTING THE WINLOADS. FBC
 R301.2.1
  
 3) SUBMIT TWO COMPLETE SETS OF THE MANUFACTURER'S
 INSTALLATION AND OWNER'S MANUAL. CITY AMENDMENTS
 107.2.1.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-07-23 Cont ID  
Sent By dhayes Date 2014-07-23 Time 13:36 Rev Time 0.00
Received By dhayes Date 2014-07-23 Time 13:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-07-11 Cont ID  
Sent By dhayes Date 2014-07-11 Time 12:12 Rev Time 0.00
Received By dhayes Date 2014-07-11 Time 12:09 Sent To  
Notes
2014-07-11 12:12:53DATE: 7/11/2014
 PROJECT: SUMMA ST. GENERATOR
 PERMIT#: 13120147
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PROPOSED GENERATOR IS NOT CAPABLE OF SUSTAINING
 THE ENTIRE LOAD OF THE HOME, THEREFORE AN EMERGENCY
 SUB-PANEL SHALL BE PROVIDED IF THERE IS TO BE AN
 AUTOMATIC TRANSFER SWITCH. NEC 702.4(2)(B)
  
 2) THE ONE LINE DIAGRAM APPEARS TO BE INCOMPLETE. HOW
 DOES THE BALANCE OF THE HOME RECEIVE ELECTRICAL
 UTILITY? IS THERE ANOTHER PANEL INSIDE THE HOUSE? OR
 ARE THE BALANCE OF BRANCH CIRCUITS FED FROM THE "MAIN"
 PANEL? MORE INFORMATION REQUIRED. FBC 107.3.1.2
  
 3) LOAD CALCULATIONS, PANEL SCHEDULE AND SPECIFICATIONS
 SHALL BE PROVIDED FOR THE ATS/SUB-PANEL AND A PANEL
 SCHEDULE AND LOAD CALCULATION FOR THE "MAIN" PANEL. THE
 SUBMITTAL PACKAGE INCLUDES INFORMATION ON A LINE OF
 ATS'S BUT NOT A SPECIFIC ONE. THE LIST DOES NOT LIST
 ANY THAT ARE ALSO USED AS LOAD CENTERS. I NEED THE
 SPECIFIC MODEL NUMBER OF THE ATS/SUB-PANEL PROPOSED
 INDICATING THE CAPACITY TO INCLUDE A SUB-PANEL AS AN
 INTEGRAL PART OF THE EQUIPMENT AS INDICATED ON THE ONE
 LINE DIAGRAM. MORE INFORMATION REQUIRED. FBC 107.3.1.2
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-02-18 Cont ID  
Sent By albarran Date 2014-02-18 Time 14:09 Rev Time 0.00
Received By albarran Date 2014-02-18 Time 14:00 Sent To I
Notes
2014-02-18 14:19:40THE PROPOSED GENERAUTOR IS NOT CAPABLE OF SUSTAINING
 THE ENTIRE LOAD OF THE HOME, THEREFORE AS PROVIDED IN
 NEC 702.4(2)(B) AND EMERGENCY SUB-PANEL SHALL BE
 PROVIDED IF THERE IS TO BE AN AUTOMATIC TRANSFER
 SWITCH.
 THE FOLLOWING CORRECTIONS TO THE DRAWINGS SHALL BE
 MADE:
 1. THE RISER DIAGRAM SHALL BE REVISED ACCORDINGLY.
 2. LOAD CALCS SHALL BE PROVIDED FOR THE EMERGENCY
 SUB-PANEL
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-01-07 Cont ID  
Sent By albarran Date 2014-01-07 Time 17:12 Rev Time 0.00
Received By albarran Date 2014-01-07 Time 16:29 Sent To I
Notes
2014-01-07 17:18:37THIS PERMIT CAN NOT BE ISSUED WITHOUT PERMITS FOR THE
 REMOVAL AND SAFE-OFF OF THE GENERATOR AT 5407 S.
 FLAGLER. (THIS MAY REQUIRE ADDITIONAL PERMITS BEYOND
 JUST ELECTRICAL)
 THE NEW INSTALLATION REQUIRES ADDITIONAL PERMITS BEYOND
 AN ELECTRICAL IF NOT ALREADY SECURED UNDER SEPARATE
 COVER FOR THE CONCRETE SLAB AND THE INSTALLATION OF THE
 FUEL SOURCE.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-07-23 Cont ID  
Sent By dhayes Date 2014-07-23 Time 13:36 Rev Time 0.00
Received By dhayes Date 2014-07-19 Time 09:17 Sent To  
Notes
2014-07-19 09:18:36SENT TO ELECTRIC UNDER $5000 BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-11 Cont ID  
Sent By dhayes Date 2014-07-11 Time 12:13 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-18 Cont ID  
Sent By albarran Date 2014-02-18 Time 14:22 Rev Time 0.00
Received By albarran Date 2014-02-18 Time 14:22 Sent To  
Notes
2014-02-18 14:23:19SCOTT WAS CONTACTED TODAY AND TOLD OF BOTH, FAILED
 BLDG. & FAILED ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-14 Cont ID  
Sent By rmcdouga Date 2014-01-14 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2013-12-19 Time 12:24 Sent To  
Notes
2014-01-07 17:19:18SAK DESK
2013-12-19 12:24:44ROUTRD TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-01-14 Cont ID  
Sent By rmcdouga Date 2014-01-14 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2014-01-14 Time 16:04 Sent To  
Notes
2014-01-14 16:07:03THE GENERATOR SHALL BE INSTALLED ACCORDING TO THE
 MANUFACTURER'S SPECIFICATIONS AND THE EXHAUST OUTLET
 SHALL BE A MINIMUM OF 10 FEET FROM ANY OPENINGS INTO
 THE STRUCTURE.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-12-26 Cont ID  
Sent By llouie Date 2013-12-26 Time 16:37 Rev Time 0.00
Received By llouie Date 2013-12-26 Time 16:37 Sent To E
Notes
2013-12-26 16:39:50ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) THE LOCATION OF THE GENERATOR AND POOL EQUIPMENT
 SHALL BE SETBACK AT LEAST 4 FT. FROM THE WEST SIDE
 PROPERTY LINE. (ZLDR S.94-305(B)(4))
  
 2.) THE NOISE LEVEL FROM ALL MECHANICAL EQUIPMENT
 INSTALLED SHALL BE MAINTAINED IN ACCORDANCE WITH CH.34,
 ART. II, S.34-37, OF THE CITY'S CODE OF ORDINANCES.
  