| Plan Review Stops For Permit 13120147 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-02-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-02-18 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-02-18 |
Time |
09:43 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-01-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-14 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-14 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2014-01-14 16:03:35 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) NONE OF THE MODEL NUMBERS LISTED IN THE CONCRETE PAD | | | SCHEDULE CORRESPOND TO THE GENERAC MODEL 04390-3 | | | GENERATOR THAT IS TO BE INSTALLED. THE GENERATOR PAD | | | ENGINEERING IS VALID FOR ONE JOB AND IS REQUIRED TO | | | HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL, AS | | | STATED ON THE DOCUMENT. | | | | | | 2) PROVIDE ENGINEERING THAT SPECIFIES WINDSPEED, | | | EXPOSURE CATEGORY AND REQUIRED WIND LOAD PRESSURES AT | | | THE JOB LOCATION AND THE ATTACHMENT METHOD AND | | | FASTENERS THAT WILL BE USED TO ATTACH THE GENERATOR TO | | | THE PAD AND BE CAPABLE OF RESISTING THE WINLOADS. FBC | | | R301.2.1 | | | | | | 3) SUBMIT TWO COMPLETE SETS OF THE MANUFACTURER'S | | | INSTALLATION AND OWNER'S MANUAL. CITY AMENDMENTS | | | 107.2.1.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2014-07-23 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-23 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-23 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2014-07-11 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-11 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-11 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2014-07-11 12:12:53 | DATE: 7/11/2014 | | | PROJECT: SUMMA ST. GENERATOR | | | PERMIT#: 13120147 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 3RD ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) THE PROPOSED GENERATOR IS NOT CAPABLE OF SUSTAINING | | | THE ENTIRE LOAD OF THE HOME, THEREFORE AN EMERGENCY | | | SUB-PANEL SHALL BE PROVIDED IF THERE IS TO BE AN | | | AUTOMATIC TRANSFER SWITCH. NEC 702.4(2)(B) | | | | | | 2) THE ONE LINE DIAGRAM APPEARS TO BE INCOMPLETE. HOW | | | DOES THE BALANCE OF THE HOME RECEIVE ELECTRICAL | | | UTILITY? IS THERE ANOTHER PANEL INSIDE THE HOUSE? OR | | | ARE THE BALANCE OF BRANCH CIRCUITS FED FROM THE "MAIN" | | | PANEL? MORE INFORMATION REQUIRED. FBC 107.3.1.2 | | | | | | 3) LOAD CALCULATIONS, PANEL SCHEDULE AND SPECIFICATIONS | | | SHALL BE PROVIDED FOR THE ATS/SUB-PANEL AND A PANEL | | | SCHEDULE AND LOAD CALCULATION FOR THE "MAIN" PANEL. THE | | | SUBMITTAL PACKAGE INCLUDES INFORMATION ON A LINE OF | | | ATS'S BUT NOT A SPECIFIC ONE. THE LIST DOES NOT LIST | | | ANY THAT ARE ALSO USED AS LOAD CENTERS. I NEED THE | | | SPECIFIC MODEL NUMBER OF THE ATS/SUB-PANEL PROPOSED | | | INDICATING THE CAPACITY TO INCLUDE A SUB-PANEL AS AN | | | INTEGRAL PART OF THE EQUIPMENT AS INDICATED ON THE ONE | | | LINE DIAGRAM. MORE INFORMATION REQUIRED. FBC 107.3.1.2 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-02-18 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-18 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-18 |
Time |
14:00 |
Sent To |
I |
|
| Notes |
| 2014-02-18 14:19:40 | THE PROPOSED GENERAUTOR IS NOT CAPABLE OF SUSTAINING | | | THE ENTIRE LOAD OF THE HOME, THEREFORE AS PROVIDED IN | | | NEC 702.4(2)(B) AND EMERGENCY SUB-PANEL SHALL BE | | | PROVIDED IF THERE IS TO BE AN AUTOMATIC TRANSFER | | | SWITCH. | | | THE FOLLOWING CORRECTIONS TO THE DRAWINGS SHALL BE | | | MADE: | | | 1. THE RISER DIAGRAM SHALL BE REVISED ACCORDINGLY. | | | 2. LOAD CALCS SHALL BE PROVIDED FOR THE EMERGENCY | | | SUB-PANEL | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-01-07 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-01-07 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-01-07 |
Time |
16:29 |
Sent To |
I |
|
| Notes |
| 2014-01-07 17:18:37 | THIS PERMIT CAN NOT BE ISSUED WITHOUT PERMITS FOR THE | | | REMOVAL AND SAFE-OFF OF THE GENERATOR AT 5407 S. | | | FLAGLER. (THIS MAY REQUIRE ADDITIONAL PERMITS BEYOND | | | JUST ELECTRICAL) | | | THE NEW INSTALLATION REQUIRES ADDITIONAL PERMITS BEYOND | | | AN ELECTRICAL IF NOT ALREADY SECURED UNDER SEPARATE | | | COVER FOR THE CONCRETE SLAB AND THE INSTALLATION OF THE | | | FUEL SOURCE. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2014-07-23 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-23 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-19 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2014-07-19 09:18:36 | SENT TO ELECTRIC UNDER $5000 BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-07-11 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-11 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-02-18 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-18 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-18 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2014-02-18 14:23:19 | SCOTT WAS CONTACTED TODAY AND TOLD OF BOTH, FAILED | | | BLDG. & FAILED ELECTRIC |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-01-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-14 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-19 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2014-01-07 17:19:18 | SAK DESK | | 2013-12-19 12:24:44 | ROUTRD TO ZONING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-01-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-14 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-14 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2014-01-14 16:07:03 | THE GENERATOR SHALL BE INSTALLED ACCORDING TO THE | | | MANUFACTURER'S SPECIFICATIONS AND THE EXHAUST OUTLET | | | SHALL BE A MINIMUM OF 10 FEET FROM ANY OPENINGS INTO | | | THE STRUCTURE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-12-26 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2013-12-26 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2013-12-26 |
Time |
16:37 |
Sent To |
E |
|
| Notes |
| 2013-12-26 16:39:50 | ZONING APPROVED WITH THE FOLLOWING PROVISOS: | | | | | | 1.) THE LOCATION OF THE GENERATOR AND POOL EQUIPMENT | | | SHALL BE SETBACK AT LEAST 4 FT. FROM THE WEST SIDE | | | PROPERTY LINE. (ZLDR S.94-305(B)(4)) | | | | | | 2.) THE NOISE LEVEL FROM ALL MECHANICAL EQUIPMENT | | | INSTALLED SHALL BE MAINTAINED IN ACCORDANCE WITH CH.34, | | | ART. II, S.34-37, OF THE CITY'S CODE OF ORDINANCES. | | | |
|
|