Plan Review Details - Permit 13120138
Plan Review Stops For Permit 13120138
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-10 Cont ID  
Sent By dharvey Date 2014-01-10 Time 07:00 Rev Time 0.00
Received By dharvey Date 2014-01-10 Time 07:00 Sent To  
Notes
2014-01-10 07:02:30ALL WORK TO COMPLY WITH NEC, SECTION 590 AND OTHER
 APPLICABLE SECTIONS AS WELL AS FPL SERVICE GUIDELINES
 FOR SERVICE. TEMPORARY SERVICE TO BE MAINTAINED IN A
 SAFE MANNER DURING COURSE OF SONSTRUCTION. APPROVED AS
 NOTED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-26 Cont ID  
Sent By albarran Date 2013-12-26 Time 17:28 Rev Time 0.00
Received By albarran Date 2013-12-26 Time 17:20 Sent To I
Notes
2013-12-26 17:33:43BECAUSE THIS EQUIPMENT WILL BE IN PLACE FOR AN EXTENDED
 PERIOD YOU SHALL:
 1. PROVIDE A SITE DRAWING INDICATING THE LOCATION OF
 BOTH THE TRANSFORMER AND THE EQUIPMENT REFLECTED ON THE
 DRAWING.
 2. THIS APPARATUS IS NOT FREE STANDING, AND THEREFORE
 YOU MUST SHOW HOW WILL THIS BE SUPPORTED. IF THIS IS TO
 BE MOUNTED ON A POLE OR A SITE BUILT RACK, YOU MUST
 PROVIDE ENGINEERED DRAWINGS SHOWING COMPLIANCE WITH
 WIND LOADS.
 3. ALL RECEPTACLES SHALL BE GFCI PROTECTED AND COMPLY
 WITH NEC 406.8.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-31 Cont ID  
Sent By shill Date 2013-12-31 Time 17:02 Rev Time 0.00
Received By shill Date 2013-12-04 Time 11:07 Sent To  
Notes
2013-12-26 17:34:29ROUTED TO SH DESK
  
2013-12-04 11:07:40ROUTED TO ELECTRICAL