Plan Review Details - Permit 13120069
Plan Review Stops For Permit 13120069
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-13 Cont ID  
Sent By jgomez Date 2014-01-14 Time 16:55 Rev Time 0.00
Received By jgomez Date 2014-01-14 Time 09:01 Sent To  
Notes
2014-01-13 16:58:24RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE SITE PLAN OR SURVEY SHOWING LOCATION, SIZE
 AND SETBACKS OF PROPOSED STRUCTURE AS REQUIRED BY SEC.
 107.3.5.3(1) OF CITY AMENDMENTS TO FBC. NEED TO VERIFY
 FIRE-RESISTANT CONSTRUCTION AS REQUIRED BY SEC. R302.1
 OF 2010 FBC-RESIDENTIAL.
  
 3- WALL SECTION:
 A) PROVIDE ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 OF 2010 FBC-RESIDENTIAL. THIS IS A FLAT ROOF.
 4"X24" VENTS DON'T PROVIDE CROSS VENTILATION, UNLESS
 THESE VENTS ARE LOCATED BETWEEN EACH RAFTERS. REVISE AS
 REQUIRED.
  
 B) SPECIFY 7/8" STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) OF 2010 FBC-RESIDENTIAL.
  
 C) SPECIFY TWO LAYERS OF WATER RESISTANT BARRIER ON
 WALL AS REQUIRED BY SEC. R703.6.3 OF 2010
 FBC-RESIDENTIAL.
  
 D) SPECIFY MIN. 8D RING SHANK NAILS FOR ROOF SHEATHING
 AS REQUIRED BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
  
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE: COORDINATE INFORMATION WITH INFORMATION SHOWN
 ON PLANS.
  
 5- PROVIDE STRUCTURAL FRAMING DETAILS FOR EXTERIOR
 DOORS AND WINDOWS TO SHOW COMPLIANCE WITH SEC. R301 OF
 2010 FBC-RESIDENTIAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOOR. INFORMATION SUBMITTED IS NOT AN
 APPROVED PRODUCT APPROVAL. NEED FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA.
  
 B) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL10970-R3 SUBMITTED IS MISSING THE WINDOW DRAWINGS.
 PLEASE PROVIDE THE WINDOW DRAWINGS.
  
 C) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE IMPACT
 GLASS.
 AND PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 E) FLAT DECK MODIFIED BITUMEN ROOF SYSTEM. NOA
 09-0224.01 SUBMITTED EXPIRED ON 11/06/13. NEED CURRENT
 NOA.
  
 ***NOTE:
 NEED ALSO TO SPECIFY WHICH APPROVED ASSEMBLY IS GOING
 TO BE USED AND NEED SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA SUBMITTED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-15 Cont ID  
Sent By rmcdouga Date 2014-01-14 Time 19:06 Rev Time 0.00
Received By rmcdouga Date 2014-01-14 Time 19:06 Sent To  
Notes
2014-01-15 14:03:30APPROVED WITH EXCEPTION. RED-LINED PLANS SUBJECT TO
 ELECTRICAL INSPECTORS APPROVAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-15 Cont ID  
Sent By rmcdouga Date 2014-01-15 Time 14:03 Rev Time 0.00
Received By rmcdouga Date 2013-12-03 Time 17:10 Sent To  
Notes
2013-12-03 17:11:18INCOMING SENT TO R23. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-01-13 Cont ID  
Sent By jgomez Date 2014-01-13 Time 16:53 Rev Time 0.00
Received By jgomez Date 2014-01-13 Time 16:53 Sent To  
Notes
2014-01-13 16:54:49BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-14 Cont ID  
Sent By jgomez Date 2014-01-14 Time 11:45 Rev Time 0.00
Received By jgomez Date 2014-01-14 Time 11:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-12-09 Cont ID  
Sent By dkittred Date 2013-12-09 Time 08:02 Rev Time 0.00
Received By dkittred Date 2013-12-05 Time 17:34 Sent To  
Notes
2013-12-09 08:01:57PLANNING & ZONING COMMENTS: ***FAILED***
  
 12/9/13
 1. PLEASE PROVIDE A SURVEY/PLOT PLAN SHOWING THE
 LOCATION AND SETBACKS FOR THE SHED/WEIGHT ROOM. MINIMUM
 REAR AND SIDE SETBACKS FOR AN ACCESSORY STRUCTURE IS 5
 FEET. ADDITIONALLY, ACCESSORY STRUCTURES WITH A SOLID
 ROOF MUST BE SEPARATED A MINIMUM OF 6 FEET FROM THE
 PRINCIPAL STRUCTURE. PLEASE INDICATE COMPLIANCE ON THE
 SURVEY/PLOT PLAN. IF THE SEPARATION IS LESS THAN 6 FEET
 THEN PRINCIPAL STRUCTURE SETBACKS SHALL APPLY TO THE
 THE ACCESSORY STRUCTURE.
  
 2. SIZE OF THE STRUCTURE SHOULD BE DIMENSIONED AND
 INDICATED ON THE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  