| 2014-01-13 16:58:24 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- PROVIDE SITE PLAN OR SURVEY SHOWING LOCATION, SIZE |
| | AND SETBACKS OF PROPOSED STRUCTURE AS REQUIRED BY SEC. |
| | 107.3.5.3(1) OF CITY AMENDMENTS TO FBC. NEED TO VERIFY |
| | FIRE-RESISTANT CONSTRUCTION AS REQUIRED BY SEC. R302.1 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- WALL SECTION: |
| | A) PROVIDE ROOF CROSS VENTILATION AS REQUIRED BY SEC. |
| | R806 OF 2010 FBC-RESIDENTIAL. THIS IS A FLAT ROOF. |
| | 4"X24" VENTS DON'T PROVIDE CROSS VENTILATION, UNLESS |
| | THESE VENTS ARE LOCATED BETWEEN EACH RAFTERS. REVISE AS |
| | REQUIRED. |
| | |
| | B) SPECIFY 7/8" STUCCO THICKNESS AS REQUIRED BY TABLE |
| | R702.1(1) OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) SPECIFY TWO LAYERS OF WATER RESISTANT BARRIER ON |
| | WALL AS REQUIRED BY SEC. R703.6.3 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | D) SPECIFY MIN. 8D RING SHANK NAILS FOR ROOF SHEATHING |
| | AS REQUIRED BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | ***NOTE: COORDINATE INFORMATION WITH INFORMATION SHOWN |
| | ON PLANS. |
| | |
| | 5- PROVIDE STRUCTURAL FRAMING DETAILS FOR EXTERIOR |
| | DOORS AND WINDOWS TO SHOW COMPLIANCE WITH SEC. R301 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) EXTERIOR DOOR. INFORMATION SUBMITTED IS NOT AN |
| | APPROVED PRODUCT APPROVAL. NEED FLORIDA PRODUCT |
| | APPROVAL OR MIAMI-DADE NOA. |
| | |
| | B) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL |
| | FL10970-R3 SUBMITTED IS MISSING THE WINDOW DRAWINGS. |
| | PLEASE PROVIDE THE WINDOW DRAWINGS. |
| | |
| | C) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE IMPACT |
| | GLASS. |
| | AND PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER |
| | PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | |
| | E) FLAT DECK MODIFIED BITUMEN ROOF SYSTEM. NOA |
| | 09-0224.01 SUBMITTED EXPIRED ON 11/06/13. NEED CURRENT |
| | NOA. |
| | |
| | ***NOTE: |
| | NEED ALSO TO SPECIFY WHICH APPROVED ASSEMBLY IS GOING |
| | TO BE USED AND NEED SIGNED AND SEALED RAS 117 |
| | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON |
| | LAST PAGE OF NOA SUBMITTED. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |