| 2013-12-06 09:29:29 | PLAN CORRECTED PER CONTRACTOR |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2013-12-05 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-12-05 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-12-04 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2013-12-05 09:42:19 | FBC 2010 FUEL GAS REVIEW #1 | | | DENIED: | | | | | | 1. THE GAS PIPE APPEARS TO BE UNDERSIZED IF TABLE | | | 402.4(2) FOR METALLIC PIPE IS BEING USED. 3/4" @ 60' | | | ALLOWS 137,000 BTU | | | | | | 2. THE PLAN SHOWS A STOVE @ 10,000 BTU. A STANDARD COOK | | | TOP UNIT USES 40,000 BTU AND A STANDARD RANGE USES | | | 65,000 BTU PLEASE PROVIDE MANUFACTURE SHEETS IF STOVE | | | IS 10,000 BTU | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION: | | | | | | 1. OK | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | 4. OK | | | 5. OK | | | 6. NA | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | 8. NA | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2007 FUEL GAS SEC. 402.2 | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-12-05 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-12-05 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-12-03 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2013-12-03 08:37:58 | ROUTED TO PLUMBING $5000 & UNDER |
|
|
|