Plan Review Details - Permit 13120028
| Plan Review Stops For Permit 13120028 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-01-27 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-01-27 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-01-27 |
Time |
09:45 |
Sent To |
I |
|
| Notes |
| 2014-01-27 10:09:17 | AFTER FURTHER DISCUSSIONS WITH THE ENGINEER AND DH WE | | | AGREED TO APPROVED THIS REVISION TO THE SERVICE | | | CONTINGENT ON NO OCCUPANCY IN THE ADJOINING UNITS. ALL | | | OF WHICH ARE CURRENTLY IN PROCESSING FOR BUILD OUT | | | PERMITS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-01-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-01-14 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-01-14 |
Time |
12:38 |
Sent To |
I |
|
| Notes |
| 2014-01-14 12:56:25 | AMONG THE OTHER ITEMS WHICH HAVE ALREADY BEEN | | | CORRECTED, YOU MAY RECALL THAT YOU WERE INITIALLY TOLD | | | TO PROVIDE A MINIMUM OF 100 AMP SERVICE WITH A LIGHT | | | AND AN EMERGENCY LIGHT TO EACH TENANT SPACE. CORRECT | | | YOUR SUBMITTAL ACCORDINGLY. | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | | (561) 805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-12-09 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-12-09 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-12-09 |
Time |
12:38 |
Sent To |
M |
|
| Notes |
| 2013-12-09 18:42:07 | THIS REVIEW DENIED FOR LACK OF INFORMATION. | | | 1. NEED MORE DETAIL ON THE SCOPE AND/OR INTENT OF THIS | | | WORK. | | | 2. THE SUBMITTED PLAN & REVISION DO NOT MATCH.THE | | | REVISION INDICATES A FUTURE SERVICE AND THE PLANS | | | REFLECT THREE MAYBE FOUR FUTURE SERVICES. | | | 3. AT A MINIMUM IF THE INTENT IS TO CREATE THREE MAYBE | | | FOUR DIVIDED SPACES FOR FUTURE TENANT BUILD OUT, EACH | | | SPACE SHALL HAVE AT A MINIMUM A 100 AMP SERVICE WITH | | | ELECTRICAL PANEL, A WORKING LIGHT WITH SWITCH, AN | | | EMERGENCY LIGHT ALL OF WHICH SHALL BE COMPLIANCE WITH | | | THE FBC-ENERGY CONSERVATION SECTION 501.2 | | | 4. AS PER NEC 110.16 ARC-FLASH PROTECTION LABELS SHALL | | | BE REQUIRED. | | | 5. MISSING DISCONNECT AND WIRING DETAIL FOR THE | | | CONDENSING UNIT. | | | 6. AS PER NEC 210.63, A SERVICE OUTLET IS REQUIRED | | | WITHIN 25 FT. OF THE CONDENSING UNIT, NOT ONE SHOWN ON | | | PLANS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-01-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-01-14 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-12-26 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2014-01-27 10:10:11 | BACK TO SH DESK AFTER ELECTRIC APPROVAL | | 2014-01-14 12:57:34 | TO SH DESK | | 2013-12-26 10:22:01 | TO ELEC | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-12-09 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-12-02 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2013-12-02 16:56:08 | SENT TO ELECTRICAL BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-12-10 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-12-10 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2013-12-10 09:25:31 | PASS PROVISO | | | PROVIDE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | FOR THE CONDENSER AT FINAL INSPECTION. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
|