Plan Review Details - Permit 13120028
Plan Review Stops For Permit 13120028
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-01-27 Cont ID  
Sent By albarran Date 2014-01-27 Time 10:06 Rev Time 0.00
Received By albarran Date 2014-01-27 Time 09:45 Sent To I
Notes
2014-01-27 10:09:17AFTER FURTHER DISCUSSIONS WITH THE ENGINEER AND DH WE
 AGREED TO APPROVED THIS REVISION TO THE SERVICE
 CONTINGENT ON NO OCCUPANCY IN THE ADJOINING UNITS. ALL
 OF WHICH ARE CURRENTLY IN PROCESSING FOR BUILD OUT
 PERMITS.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-01-14 Cont ID  
Sent By albarran Date 2014-01-14 Time 12:53 Rev Time 0.00
Received By albarran Date 2014-01-14 Time 12:38 Sent To I
Notes
2014-01-14 12:56:25AMONG THE OTHER ITEMS WHICH HAVE ALREADY BEEN
 CORRECTED, YOU MAY RECALL THAT YOU WERE INITIALLY TOLD
 TO PROVIDE A MINIMUM OF 100 AMP SERVICE WITH A LIGHT
 AND AN EMERGENCY LIGHT TO EACH TENANT SPACE. CORRECT
 YOUR SUBMITTAL ACCORDINGLY.
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH BLDG. DEPARTMENT
 (561) 805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-09 Cont ID  
Sent By albarran Date 2013-12-09 Time 18:22 Rev Time 0.00
Received By albarran Date 2013-12-09 Time 12:38 Sent To M
Notes
2013-12-09 18:42:07THIS REVIEW DENIED FOR LACK OF INFORMATION.
 1. NEED MORE DETAIL ON THE SCOPE AND/OR INTENT OF THIS
 WORK.
 2. THE SUBMITTED PLAN & REVISION DO NOT MATCH.THE
 REVISION INDICATES A FUTURE SERVICE AND THE PLANS
 REFLECT THREE MAYBE FOUR FUTURE SERVICES.
 3. AT A MINIMUM IF THE INTENT IS TO CREATE THREE MAYBE
 FOUR DIVIDED SPACES FOR FUTURE TENANT BUILD OUT, EACH
 SPACE SHALL HAVE AT A MINIMUM A 100 AMP SERVICE WITH
 ELECTRICAL PANEL, A WORKING LIGHT WITH SWITCH, AN
 EMERGENCY LIGHT ALL OF WHICH SHALL BE COMPLIANCE WITH
 THE FBC-ENERGY CONSERVATION SECTION 501.2
 4. AS PER NEC 110.16 ARC-FLASH PROTECTION LABELS SHALL
 BE REQUIRED.
 5. MISSING DISCONNECT AND WIRING DETAIL FOR THE
 CONDENSING UNIT.
 6. AS PER NEC 210.63, A SERVICE OUTLET IS REQUIRED
 WITHIN 25 FT. OF THE CONDENSING UNIT, NOT ONE SHOWN ON
 PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-14 Cont ID  
Sent By shill Date 2014-01-14 Time 13:33 Rev Time 0.00
Received By shill Date 2013-12-26 Time 10:21 Sent To  
Notes
2014-01-27 10:10:11BACK TO SH DESK AFTER ELECTRIC APPROVAL
2014-01-14 12:57:34TO SH DESK
2013-12-26 10:22:01TO ELEC
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-10 Cont ID  
Sent By albarran Date 2013-12-09 Time 18:42 Rev Time 0.00
Received By hmoser Date 2013-12-02 Time 16:53 Sent To  
Notes
2013-12-02 16:56:08SENT TO ELECTRICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-12-10 Cont ID  
Sent By hmoser Date 2013-12-10 Time 09:25 Rev Time 0.00
Received By hmoser Date 2013-12-10 Time 09:20 Sent To  
Notes
2013-12-10 09:25:31PASS PROVISO
 PROVIDE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 FOR THE CONDENSER AT FINAL INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676