Plan Review Details - Permit 13110903
Plan Review Stops For Permit 13110903
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-10 Cont ID  
Sent By jgomez Date 2014-01-10 Time 16:13 Rev Time 0.00
Received By jgomez Date 2014-01-10 Time 16:07 Sent To  
Notes
2014-01-10 16:46:40RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO PROVIDE DESIGN CRITERIA AS REQUIRED BY
 SEC. R301 OF 2010 FBC-RESIDENTIAL. SPECIFY BUILDING
 CODE, EXPOSURE, WIND LOADS, ETC. AND REVISE THE WINDOWS
 DESIGN PRESSURES. ACCORDING TO SEC. R301.2.1.4.3 OF
 2010 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN
 EXPOSURE "D". DESIGN PRESSURES SHOWN ON PLANS DON'T
 CORRESPOND TO EXPOSURE "D". REVISE AS REQUIRED.
  
 2- SCOPE OF WORK IN PERMIT APPLICATION IS TO REPLACE
 EXISTING AWNING WINDOWS WITH IMPACT RESISTANCE WINDOWS
 (12 TOTAL). MIAMI-DADE NOA 12-0906.06 SUBMITTED IS FOR
 NON-IMPACT SINGLE HUNG WINDOWS. CLARIFY AS REQUIRED.
 ***NOTE; WINDOWS NEED TO HAVE HURRICANE IMPACT
 PROTECTION AS REQUIRED BY SEC. R301.2.1.2.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) IMPACT WINDOWS AS SPECIFIED ON PERMIT APPLICATION.
 (NOTE: VERIFY DESIGN PRESSURES WITH ENGINEER REVISED
 DESIGN PRESSURES AS REQUIRED BY ITEM #1 ABOVE).
  
 B) HURRICANE SHUTTERS IF WINDOWS TO BE INSTALLED HAVE
 NOT IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE . SEE CITY HURRICANE SHUTTERS INSTALLATION
 SCHEDULE SAMPLE.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 5- SPECIFY SAFETY GLASS FOR WINDOWS LOCATED IN MASTER
 BATHROOM AND GUEST BATHROOM AS REQUIRED BY SEC. R308.4.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS TO FBC. REVISE
 AS REQUIRED.
  
 ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By rmcdouga Date 2014-01-13 Time 06:55 Rev Time 0.00
Received By rmcdouga Date 2014-01-13 Time 06:55 Sent To  
Notes
2014-01-13 06:57:35APPROVED WITH THE EXCEPTION THAT THE REDLINED ITEMS ON
 THE ELECTRICAL PLANS BE ADDRESSED. SMOKE ALARMS, VAPOR
 PROOF FIXTURES, TAMPER RESISTANT RECEPTACLES, AFCI
 PROTECTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-13 Cont ID  
Sent By rmcdouga Date 2014-01-13 Time 06:55 Rev Time 0.00
Received By rmcdouga Date 2013-11-27 Time 17:09 Sent To  
Notes
2013-11-27 17:09:27R06

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-10 Cont ID  
Sent By jgomez Date 2014-01-10 Time 18:36 Rev Time 0.00
Received By jgomez Date 2014-01-10 Time 18:33 Sent To  
Notes
***NONE***