Plan Review Details - Permit 13110902
Plan Review Stops For Permit 13110902
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-02-12 Cont ID  
Sent By skennedy Date 2014-02-12 Time 08:23 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-04 Cont ID  
Sent By jwitmer Date 2013-12-04 Time 19:28 Rev Time 0.00
Received By jwitmer Date 2013-12-04 Time 19:03 Sent To  
Notes
2013-12-04 19:18:51SEE FIRE PLAN REVIEW NOTES. ROOMS WITH CLOSETS ARE
 TRATED AS SLEEPING ROOMS NEEDING SMOKE DETECTION
 DEVISES.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-02-12 Cont ID  
Sent By skennedy Date 2014-02-12 Time 08:23 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-27 Cont ID  
Sent By skennedy Date 2013-12-27 Time 10:17 Rev Time 0.00
Received By skennedy Date 2013-12-27 Time 10:17 Sent To  
Notes
2013-12-27 10:22:03PLEASE MODIFY THE DRAWING TO DEMONSTRATE COMPLIANCE
 WITH THE FOLLOWING:
 FBC- 107 SMOKE DETECTOR LOCATIONS
 NEC 210.12B ? AFCI PROTECTION.
 NEC 406.11- TAMPER RESISTANT RECEPTACLES.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-01-29 Cont ID  
Sent By wjolin Date 2014-01-29 Time 14:26 Rev Time 0.00
Received By wjolin Date 2014-01-29 Time 14:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-30 Cont ID  
Sent By wjolin Date 2013-11-30 Time 17:07 Rev Time 0.00
Received By wjolin Date 2013-11-30 Time 17:00 Sent To  
Notes
2013-11-30 17:07:52801 SOUTH OLIVE AVENUE - SUITE #1409
 PERMIT #13110902
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 HARD-WIRED MULTI-STATION SMOKE ALARMS SHALL BE
 INSTALLED ON ALL LEVELS OF THE DWELLING UNIT, INSIDE
 EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS.
  
 NO SPRINKLER PROTECTION PROVIDED INSIDE THE CLOSET.
  
 THE EXISTING SIDEWALL SPRINKLER MAY BE OBSTRUCTED BY
 THE NEW CLOSET TO BE INSTALLED BELOW THE SPRINKLER.
  
 INDICATE THE LOCATION OF THE NEAREST EXISTING SPRINKLER
 LOCATED OUTSIDE/ADJACENT THE NEW BEDROOM WALL.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-12 Cont ID  
Sent By skennedy Date 2014-02-12 Time 08:24 Rev Time 0.00
Received By skennedy Date 2014-01-21 Time 16:31 Sent To  
Notes
2014-01-22 16:31:29RESUBMITTAL SENT TO B18 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-27 Cont ID  
Sent By skennedy Date 2013-12-27 Time 10:24 Rev Time 0.00
Received By skennedy Date 2013-11-27 Time 17:13 Sent To  
Notes
2013-11-27 17:14:03B05
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-02-04 Cont ID  
Sent By hmoser Date 2014-02-04 Time 09:23 Rev Time 0.00
Received By hmoser Date 2014-02-04 Time 09:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-12-19 Cont ID  
Sent By skennedy Date 2013-12-19 Time 11:08 Rev Time 0.00
Received By skennedy Date 2013-12-19 Time 11:08 Sent To  
Notes
2013-12-19 11:09:00REVIEW BY PX 1328 J SAEZ