Plan Review Details - Permit 13110875
Plan Review Stops For Permit 13110875
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-06 Cont ID  
Sent By jwitmer Date 2013-12-06 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2013-12-06 Time 08:39 Sent To  
Notes
2013-12-06 11:48:16BUILDING PLAN REVIEW
 PERMIT: 13110875
 ADD: 217 BUTLER ST UBIT # 9 A CHANGE IN OCCUPANCY
 CONT: ALK CORP INC
 TEL: (561)718-8616
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY DEC.06/ 2013
 ACTION: DENIED
  
 1) THE PLANS INDICATE UNIT # 9 TO BE A CHANGE IN
 OCCUPANCY PLEASE PROVIDE DIMENSIONS ON THE FLOOR PLAN
 AND PLEASE ALSO PROVIDE A EXISTING FLOOR PLAN LAYOUT
 AND PROPOSED WORK FOR THIS UNIT. THERE SEEMS TO BE A
 DISCREPANCY IN THE UNIT SIZE AS INDICATED ON THIS PLAN
 AND THE LAST PERMITTED WORK UNDER PERMIT # 01100681
 SHEET A-3 FIRST FLOOR & A-4 THE MEZZANINE LEVEL. THE
 COMMON TENANT SEPERATION WALL (SOUTH WALL) APPEARS TO
 HAVE BEEN MOVED AT LEAST 3'-0" SOUTH AS WELL AS THE
 NORTH PROPOSED
 FLOOR AREA OF THE SECOND FLOOR (OLD MEZZANINE).
  
 PLEASE NOTE AREAS OF MEZZANINE ARE FIGURED ON THE 1/3RD
 THE CLEAR FLOOR AREA OF THE ROOM IN WHICH THEY ARE
 LOCATED 2010 FBC-B 505.2. PLEASE SEE THE NEW CLOSET,
 BEDROOM AND FLOOR AREA FROM THE TENANT SEPERATION WALL
 BEING MOVED HAS CREATED A TRUE SECOND FLOOR AND NOT A
 MEZZANINE. THE CLEAR FLOOR AREA FOR THE FIRST FLOOR
 AREA IS
 322.875 SQ FT AND THE MAXIMUM FLOOR AREA OF THE
 MEZANINE WOULD BE 106.25 SQ FT.
  
 2) PLEASE PROVIDE WHAT THE OCCUPANCY OR USAGE FOR THE
 2ND FLOOR AREA WILL BE USED FOR? 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE PLANS DO NOT INDICATE A CHANGE OF OCCUPANCY ONLY
 THE PERMIT APPLICATION, PLEASE PROVIDE COMPLIANCE FOR
 ALL OF 2010 FL EXST BLDG CODE 912 REQUIREMENTS:
  
 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 3A) 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 3B) 912.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 3C) 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-01-07 Cont ID  
Sent By skennedy Date 2014-01-07 Time 09:54 Rev Time 0.00
Received By skennedy Date 2014-01-07 Time 09:54 Sent To  
Notes
2014-01-07 09:57:48PLEASE ADDRESS THE ITEMS NOTED BELOW:
 FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY
 SUBMITTAL COMPLIANT WITH FBC-E 103
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 NEC 210.12B ? PROVIDE AFCI PROTECTION.
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
 THIS IS AN INCOMPLETE REVIEW PENDING THE QUALITY OF THE
 RESUBMITTAL.
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-12-13 Cont ID  
Sent By wjolin Date 2013-12-13 Time 13:03 Rev Time 0.00
Received By wjolin Date 2013-12-13 Time 12:44 Sent To  
Notes
2013-12-13 13:02:13217 BUTLER STREET - UNIT #9
 PERMIT #13110875
 REVIEW COMMENTS - FIRE DEPARTMENT
 **CHANGE OF OCCUPANCY FROM BUSINESS TO APARTMENT**
  
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2009. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 FIRE RATED WALLS, EXITS, EGRESS WINDOWS, TRAVEL
 DISTANCES, ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER NFPA 101 SECTION 30.3.5 ALL NEW APARTMENTS SHALL BE
 PROTECTED BY AN AUTOMATIC AND SUPERVISED SPRINKLER
 SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-07 Cont ID  
Sent By skennedy Date 2014-01-07 Time 09:57 Rev Time 0.00
Received By skennedy Date 2013-11-26 Time 11:43 Sent To  
Notes
2013-11-27 11:44:02SENT TO B3 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-12-06 Cont ID  
Sent By jwitmer Date 2013-12-06 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2013-12-06 Time 10:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-12-19 Cont ID  
Sent By skennedy Date 2013-12-19 Time 11:05 Rev Time 0.00
Received By skennedy Date 2013-12-19 Time 11:05 Sent To  
Notes
2013-12-19 11:06:02REVIEW BY PX 1328 J SAEZ

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-12-06 Cont ID  
Sent By lwagner Date 2013-12-06 Time 13:43 Rev Time 0.00
Received By lwagner Date 2013-12-06 Time 13:26 Sent To  
Notes
2013-12-06 13:52:52PLEASE SEE BUILDING REVIEW COMMENTS CONCERNING
 OCCUPANCY CHANGE, VALUE, CHANGE IN FLOOR PLAN, ETC.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-01-06 Cont ID  
Sent By jroach Date 2014-01-06 Time 14:15 Rev Time 0.00
Received By jroach Date 2014-01-06 Time 14:15 Sent To  
Notes
2014-01-06 14:15:17ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.06.2014
 PERMIT NO.: 13110875
 ADDRESS: 217 BUTLER STREET
 CONTRACTOR/CONTACT: LANE KIASCHUS
 TELEPHONE NO.: 561.718.8616
 SCOPE OF REVIEW: CONVERSION OF EXISTING OFFICE INTO A
 LIVING UNIT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-215(D)(8) OF THE CITY?S
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS), ?ALL
 PROPERTIES SHALL BE BROUGHT INTO COMPLIANCE WITH THE
 LANDSCAPE REGULATIONS AT SUCH TIME THAT A BUILDING
 PERMIT IS ISSUED FOR WORK VALUED AT $5,000.00 OR MORE.?
 PLANS SHALL BE SUBMITTED INDICATING SUCH. IF EXISTING
 MATERIAL IS SHOWN ON THE PLANS AND ALL PROVISIONS OF
 ARTICLE XIV HAVE BEEN MET, THEN NO ADDITIONAL
 PERMIT/INSTALLATION IS REQUIRED. IF THE EXISTING
 MATERIAL ON SITE DOES NOT CONFORM TO ALL OF THE
 REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL MATERIAL
 WILL NEED TO BE SHOWN ON THE PLANS AND PERMITTED UNDER
 A LANDSCAPE PERMIT. PLEASE NOTE THAT PLANS SHOULD
 INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
  
 A. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
 B. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
 C. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
 D. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
 E. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
 F. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE PROVIDED
 WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM, INCLUDING
 THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT ANY NEW
 IRRIGATION SHALL BE DONE UNDER A SEPARATE PERMIT).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  