Plan Review Details - Permit 13110790
Plan Review Stops For Permit 13110790
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-11-25 Cont ID  
Sent By lphilmor Date 2013-11-25 Time 13:40 Rev Time 0.00
Received By lphilmor Date 2013-11-25 Time 13:40 Sent To  
Notes
2013-11-25 13:42:242419 S DIXIE HWY
 PERMIT # 13110790
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75
 FEET. PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH
 GREASE OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jlmitch Date 2013-11-25 Time 10:58 Sent To  
Notes
2013-11-25 10:59:00ROUTED TO TEMP TENTS