| Plan Review Stops For Permit 13110778 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2014-03-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-03-14 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-03-14 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-03-27 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-03-27 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-03-19 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2014-03-27 13:26:39 | ELECTRICAL PROVISO FOR PERMIT 13110778, ALL ELECTRICAL | | | APPARATUS SHALL COMPLY WITH ARTICLE 682 OF THE 2008 | | | EDITION OF THE NEC | | | RECEIVED VIA EMAIL AUTHORIZATION FROM THE DESIGN | | | PROFESSIONAL, VINCE REA TO CROSS OUT THE WORDS AS | | | INDICATED. FOR THE RECORD, ASKED THAT EMAIL BE UPLOADED | | | INTO FILE. | | 2014-03-26 14:43:37 | THIS FILE WAS REVIEWED AND IS ALMOST READY FOR | | | APPROVAL. I HAVE A COUPLE OF CORRECTIONS PENDING BUT | | | NEED THE APPROVAL OF THE DESIGN PROFESSIONAL TO MAKE | | | THEM. I CALLED AT THE TIME OF THE REVIEW BUT THIS | | | AFTERNOON I SENT VINCE RAE AN EMAIL WITH THE QUESTIONS | | | I HAVE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-02-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-02-20 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-02-20 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
2 |
Status |
N |
Date |
2014-06-11 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-11 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-11 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2014-06-11 14:37:45 | SEE 14040354, DERM APPROVED TANK 3/27/14. |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
F |
Date |
2014-02-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2014-02-13 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-02-13 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2014-02-13 11:53:02 | **DENIED** | | | UNDERGROUND FUEL STORAGE TANKS >110 GALLONS AND ABOVE | | | GROUND FUEL STORAGE TANKS >550 GALLONS SHALL BE | | | APPROVED BY THE PALM BEACH COUNTY DEPARTMENT OF | | | ENVIRONMENTAL RESOURCE MANAGEMENT PRIOR TO PERMIT | | | ISSUANCE. | | | | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-06-17 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2014-06-17 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2014-06-03 |
Time |
05:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2014-03-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-02-13 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2014-06-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-23 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-23 |
Time |
17:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-06-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-06-17 |
Time |
13:26 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2014-06-17 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2014-06-17 13:24:16 | PASSED | | | | | | 1) THE NEW HEDGES TO SCREEN THE GENERATOR ENCLOSURE AND | | | THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT | | | BUILDING SHALL BE INSTALLED AS PART OF THIS PERMIT. | | | | | | 2) THE GENERATOR SHALL BE SCREENED WITH AN OPAQUE | | | FENCE/WALL FOR THE FULL HEIGHT OF THE GENERATOR. A | | | FENCE PERMIT IS REQUIRED. THE FENCE SHALL BE INSTALLED | | | AND PASS INSPECTION PRIOR TO THE FINAL (104) INSPECTION | | | FOR THIS PERMIT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | | | | | | | 2014-06-06 11:18:27 | 6/5/14 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-03-12 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-03-12 |
Time |
09:16 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2014-03-12 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2014-03-12 09:57:27 | FAILED | | | | | | 1) THE PLACEMENT OF THE NEW GENERATOR, PAD, ENCLOSURE | | | AND THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT | | | BUILDING IS A MODIFICATION TO THE APPROVED SITE AND | | | LANDSCAPE PLANS AND REQUIRES A MINOR PLANNED | | | DEVELOPMENT AMENDMENT. | | | | | | 2) PLEASE BE AWARE THAT THIS IS A POSSIBLE LOCATION FOR | | | THE RELOCATION OF THE PACE BUS PARKING ONCE TRADITIONS | | | PHASE II IS CONSTRUCTED. STAFF RECOMMENDS TAKING INTO | | | ACCOUNT THE FUTURE PARKING RELOCATION WHEN PLANNING ANY | | | NEW SITE FACILITIES. | | | | | | 3) ANY TREE RELOCATION REQUIRES A TREE ALTERATION | | | PERMIT. | | | | | | 4) LANDSCAPE IS REQUIRED TO SCREEN THE GENERATOR AND | | | THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT | | | BUILDING. A LANDSCAPE PERMIT IS REQUIRED. | | | | | | 5) THE GENERATOR SHALL BE SCREENED WITH AN OPAQUE | | | FENCE/WALL FOR THE FULL HEIGHT OF THE GENERATOR. A | | | FENCE PERMIT IS REQUIRED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | | | | 2014-02-18 15:12:39 | 2/18/14 |
|
|