Plan Review Details - Permit 13110725
Plan Review Stops For Permit 13110725
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-03-27 Cont ID  
Sent By jgomez Date 2014-03-27 Time 09:07 Rev Time 0.00
Received By jgomez Date 2014-03-27 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-03-21 Cont ID  
Sent By jgomez Date 2014-03-21 Time 13:33 Rev Time 0.00
Received By jgomez Date 2014-03-21 Time 13:33 Sent To  
Notes
2014-03-21 13:35:57 
 ***REVIEW IN PROGRESS...
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) HARDIEPLANK SIDING AS SHOWN ON PLANS.
 ***NOA 07-0418.04 SUBMITTED EXPIRED ON MAY 01, 2012.
 NEED CURRENT NOA.
  
 B) HORIZONTAL SLIDER WINDOWS AS SHOWN IN THE NEW
 KITCHEN AREA.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 3- SHEET 2 OF 3:
 A) THE COMPONENTS AND CLADDING DESIGN PRESSURES SHOWN
 FOR THE ROOF ARE INCORRECT. REVISE AS REQUIRED. SEE
 TABLE R301.2(2) OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP
 IN MIND THAT THIS TABLE IS FOR EXPOSURE "B". NEED TO
 ADJUST TO EXPOSURE "C" ACCORDINGLY.
 *** REVISED VALUES ARE INCORRECT. WORST CASE SCENARIO
 IS FOR ROOF ZONE #3. PROVIDE CALCULATIONS. SEC.
 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 4- SECTION B-B ON SHEET 3 OF 3:
 A) NEED GUTTERS AS REQUIRED BY SEC. R318.6.
 ***PROVIDE COMPLETE INFORMATION. EXTERIOR REAR
 ELEVATION DOESN'T SHOW THE DOWNSPOUTS.
  
 5- NEW COMMENT: INSULATION CHANGED FROM BATT INSULATION
 TO ICYNENE INSULATION. PROVIDE ICYNENE ICC EVALUATION
 REPORT AND MANUFACTURER SPECS.
  
 6- ARCHITECT TO REVISE THE ENERGY CALCULATIONS (FORM
 402-2010 SUBMITTED THIS TIME) AND COORDINATE WITH FLOOR
 PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION:
 ***NOTES:
 A) CAREFULLY READ ALL THE GENERAL INSTRUCTIONS ON PAGE
 ONE AND ALL THE NOTES ON PAGE TWO. THEY SHOW ALL THE
 CONDITIONS THAT NEED TO BE MET IN ORDER TO USE THIS
 FORM. AND REVISE ACCORDINGLY.
  
 B) TOTAL ADDITION APPLIES TO THE NEW KITCHEN AREA AND
 THE AREA ENCLOSED BY THE PARTIALLY COVERED PORCH. TAKE
 THIS INTO CONSIDERATION FOR THE TOTAL ADDITION
 CONDITIONED AREA. THE NEW KITCHEN IS LOCATED IN AN
 EXISTING ENCLOSED PORCH. THIS AREA WAS NOT INSULATED.
 NEED TO INSULATE THE RAISED FLOOR, WALLS AND CEILING IN
 THIS AREA.
  
  
  
 ***NOTE:
 PLEASE PROVIDE A RESPONSE LETTER SHOWING HOW AND WHERE
 EACH COMMENT WAS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-06 Cont ID  
Sent By jgomez Date 2014-01-06 Time 09:50 Rev Time 0.00
Received By jgomez Date 2014-01-06 Time 09:50 Sent To  
Notes
2014-01-06 09:53:10RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- THERE ARE TWO DIFFERENT SET OF PLANS SUBMITTED. ONE
 WAS SIGNED AND SEALED BY THE ARCHITECT AND THE OTHER
 ONE WAS NOT. ALL PLANS NEED TO BE SIGNED AND SEALED BY
 THE ARCHITECT SHOWN ON THE TITLE BLOCK AS REQUIRED BY
 CHAPTER 481 FL. ST.. CLARIFY WHICH SET OF PLANS IS THE
 CORRECT ONE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 ***NOTE: ONLY THE SIGNED AND SEALED SET WAS REVIEWED.
 COMMENTS APPLY TO THOSE DRAWINGS ONLY.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES AS SHOWN ON PLANS.
  
 B) HARDIEPLANK SIDING AS SHOWN ON PLANS. INFORMATION
 SUBMITTED IS THE MANUFACTURES SPECIFICATIONS, NOT AN
 OFFICIAL PRODUCT APPROVAL. NEED EITHER MIAMI-DADE NOA
 OR FLORIDA PRODUCT APPROVAL WITH THE CORRESPONDING
 FLORIDA PRODUCT APPROVAL NUMBER.
  
 C) HORIZONTAL SLIDER WINDOWS AS SHOWN IN THE NEW
 KITCHEN AREA.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 5- SHEET 2 OF 3:
 A) THE COMPONENTS AND CLADDING DESIGN PRESSURES SHOWN
 FOR THE ROOF ARE INCORRECT. REVISE AS REQUIRED. SEE
 TABLE R301.2(2) OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP
 IN MIND THAT THIS TABLE IS FOR EXPOSURE "B". NEED TO
 ADJUST TO EXPOSURE "C" ACCORDINGLY.
  
 B) REVISE ALL THE LANDINGS TO COMPLY WITH SEC. R311.3
 OF 2010 FBC-RESIDENTIAL.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. REVISE THE VALUATION.
  
 7- SECTION B-B ON SHEET 3 OF 3:
 A) SPECIFY ROOF PITCH AND SPECIFY TWO LAYERS OF
 UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2.
  
 B) R-19 BUTT INSULATION DOESN'T FIT ON 2X4 WALL. REVISE
 AS REQUIRED. AND COORDINATE WITH THE ENERGY
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) COORDINATE CEILING INSULATION WITH INFORMATION ON
 THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) NO GYPSUM BOARD ON CEILING?. PROVIDE FRAMING DETAILS
 FOR NEW CEILING. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 D) NEED GUTTERS AS REQUIRED BY SEC. R318.6.
  
 E) SPECIFY WEATHER RESISTANT SHEATHING PAPER AS
 REQUIRED BY SEC. R703.2.
  
 8- REVISE ROOF SHEATHING NOTE ON SHEET 3 OF 3. NEED
 4"0." NAILS ON GABLE END AS REQUIRED BY SEC. R803.2.3.1
 AND TABLE R803.2.3.1.
 ***NOTE: ROOF ZONE #3 IS AT LEAST 5'-0" OF ENTIRE GABLE
 END. SEE FIGURE R803.2.3.1.
  
 9- SPECIFY ATTIC VENTILATION AS REQUIRED BY SEC. R806.
 AND, COORDINATE WITH THE ENERGY CALCULATIONS.
  
 10- REVISE ENERGY CALCULATIONS SUBMITTED AND COORDINATE
 WITH FLOOR PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION:
 A) AREA WEIGHTED AVERAGE OVERHANG DEPTH SHOWN ON ITEM 7
 DOESN'T MATCH PLANS.
  
 B) REVISE FLOOR TYPE AND INSULATION TO MATCH REVISED
 PLANS. (NEED INSULATION). TIS IS NOT A CONCRETE SLAB ON
 GRADE.
  
 C) COORDINATE ROOF/ATTIC VENTILATION WITH REVISED
 PLANS.
  
 D) REVISE ROOF MATERIAL ON PAGE 2 OF 5 TO MATCH PLANS.
  
 E) CLEARLY SPECIFY ACTUAL WINDOW ORIENTATION ON PAGE 3
 OF 5 TO MATCH PLANS.
  
 F) COMPLETE ALL THE INFORMATION ON TOP OF FORM.
  
 11- ARCHITECT TO COORDINATE ALL PLANS WITH THE REVISED
 ENERGY CALCULATIONS. COORDINATE INSULATION VALUE SHOWN
 ON WALLS, CEILINGS, RAISED FLOOR. ALSO, COORDINATE THE
 ROOF VENTILATION. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ***NOTE:
 PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-03-14 Cont ID  
Sent By skennedy Date 2014-03-14 Time 09:41 Rev Time 0.00
Received By skennedy Date 2014-03-14 Time 09:41 Sent To  
Notes
2014-03-12 17:39:27NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-07 Cont ID  
Sent By skennedy Date 2014-01-07 Time 09:28 Rev Time 0.00
Received By skennedy Date 2014-01-07 Time 09:28 Sent To  
Notes
2014-01-07 09:31:44WILL STAMP UPON RESUBMITTAL OF TWO SETS OF PLANS PER
 BUILDING COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-27 Cont ID  
Sent By jgomez Date 2014-03-27 Time 09:07 Rev Time 0.00
Received By jgomez Date 2014-03-27 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-21 Cont ID  
Sent By jgomez Date 2014-03-21 Time 17:51 Rev Time 0.00
Received By jgomez Date 2014-03-12 Time 17:41 Sent To  
Notes
2014-03-12 17:41:45SENT TO S. KENNEDY'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-07 Cont ID  
Sent By skennedy Date 2014-01-07 Time 09:28 Rev Time 0.00
Received By skennedy Date 2013-11-22 Time 17:43 Sent To  
Notes
2013-11-22 17:44:20R16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-03-21 Cont ID  
Sent By jgomez Date 2014-03-21 Time 17:35 Rev Time 0.00
Received By jgomez Date 2014-03-21 Time 17:35 Sent To  
Notes
2014-03-21 17:37:17NO IMPACT FEES DUE. MU-2013-26513 STAMPED BY DB ON
 SHEET 2 OF 3 SUBMITTED. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-01-06 Cont ID  
Sent By jgomez Date 2014-01-06 Time 10:47 Rev Time 0.00
Received By jgomez Date 2014-01-06 Time 10:47 Sent To  
Notes
2014-01-06 10:49:20AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-12-18 Cont ID  
Sent By shill Date 2013-12-18 Time 15:56 Rev Time 0.00
Received By skennedy Date 2013-12-18 Time 15:55 Sent To  
Notes
2013-12-18 15:56:38OK PER J SAEZ
 PX 1328
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-03-21 Cont ID  
Sent By jgomez Date 2014-03-21 Time 17:50 Rev Time 0.00
Received By jgomez Date 2014-03-21 Time 17:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-06 Cont ID  
Sent By jgomez Date 2014-01-06 Time 17:23 Rev Time 0.00
Received By jgomez Date 2014-01-06 Time 16:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-12-03 Cont ID  
Sent By dkittred Date 2013-12-03 Time 08:17 Rev Time 0.00
Received By dkittred Date 2013-12-02 Time 17:33 Sent To  
Notes
2013-12-03 08:17:24PLANNING AND ZONING COMMENTS:
  
 12/3/13
 ADDITION (ENCLOSING EXISTING COVERED PORCH) AND REMODEL
 HAS BEEN APPROVED BY P&Z. HOWEVER, NOTES HAVE BEEN
 ADDED TO THE PLAN REGARDING THE OPTIONAL CIRCULAR DRIVE
 - PROPOSED CIRCULAR DRIVE IS NOT PERMITTED AS PROPOSED.
 ONLY ONE DRIVEWAY UP TO 20' WIDE OR TWO DRIVEWAYS UP TO
 10' WIDE EACH IS PERMITTED PER PROPERTY. OBTAINING A
 PERMIT FOR THE DRIVEWAY IN THE FUTURE WILL REQUIRE
 REVISION TO BE IN COMPLIANCE WITH CODE REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-12-02 12:23:1812/2/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved