Plan Review Details - Permit 13110723
Plan Review Stops For Permit 13110723
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-07 Cont ID  
Sent By jwitmer Date 2014-01-07 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2014-01-07 Time 07:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-11-26 Cont ID  
Sent By jwitmer Date 2013-11-26 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2013-11-26 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-16 Cont ID  
Sent By albarran Date 2014-01-16 Time 15:51 Rev Time 0.00
Received By albarran Date 2014-01-16 Time 15:41 Sent To I
Notes
2014-01-16 15:52:12NOTICE:
 AS INDICATED ON NEC 422.52, ELECTRIC DRINKING FOUNTAINS
 SHALL BE ON A GFI PROTECTED CIRCUIT.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-12 Cont ID  
Sent By skennedy Date 2013-12-12 Time 10:27 Rev Time 0.00
Received By skennedy Date 2013-12-12 Time 10:27 Sent To FIRE
Notes
2013-12-12 10:27:32PROVIDE AN ELECTRICAL PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-01-08 Cont ID  
Sent By lphilmor Date 2014-01-08 Time 10:40 Rev Time 0.00
Received By lphilmor Date 2014-01-08 Time 10:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-12 Cont ID  
Sent By lphilmor Date 2013-12-12 Time 13:39 Rev Time 0.00
Received By lphilmor Date 2013-12-12 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-16 Cont ID  
Sent By skennedy Date 2014-01-16 Time 16:43 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2014-01-16 15:52:36SENT TO SAK DESK 2 OF 2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-13 Cont ID  
Sent By shill Date 2013-12-13 Time 18:27 Rev Time 0.00
Received By shill Date 2013-11-22 Time 17:16 Sent To  
Notes
2013-11-22 17:16:27B08 - TRAVELING WITH 13061104

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-07 Cont ID  
Sent By jwitmer Date 2014-01-07 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2014-01-07 Time 07:31 Sent To  
Notes
2014-01-07 07:32:58PLUMBING PLAN REVIEW
 PERMIT: 13110723
 ADD: 5800 S DIXIE HWY, SUITE #B
 CONT: MIKE MOORE CONSTRUCTION
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN. 07/2014
  
 ACTION:PLUMBING PROVISO:
  
 1) A HIGH/ LOW DRINKING FOUNTAIN IS REQUIRED. 2010
 FBC-BLUMBING TABLE 403.1 SEE FOOTNOTES (E) & (F):
 FOOTNOTE (E). THE MINIMUM NUMBER OF REQUIRED DRINKING
 FOUNTAINS SHALL COMPLY WITH TABLE 403.1 AND THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 FOOTNOTE (F). DRINKING FOUNTAINS ARE NOT REQUIRED FOR
 AN OCCUPANT LOAD OF 15 OR FEWER. NOTE THE OCCUPANT LOAD
 FOR THIS SPACE MIN. BUSINESS IS 29/ MERCANTILE 95.
  
 2) 2010 FBC-ACCESSIBILITY CODE: 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-12-12 Cont ID  
Sent By lwagner Date 2013-12-12 Time 09:40 Rev Time 0.00
Received By lwagner Date 2013-12-12 Time 09:23 Sent To  
Notes
2013-12-12 09:33:21FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 REVIEW COMMENT #2 FROM PERMIT #13061104 HAS NOT BEEN
 ADDRESSED:
 2. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15
 OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN .
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 NOTE: UNLESS A PLUMBING ISOMETRIC IS PROVIDED, A
 PLUMBING APPLICATION, DRAWINGS, FEES, AND PERMIT WIILL
 BE REQUIRED.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-12-12 Cont ID  
Sent By jroach Date 2013-12-12 Time 10:28 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2013-12-02 12:21:3112/2/13