Plan Review Details - Permit 13110716
Plan Review Stops For Permit 13110716
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-11 Cont ID  
Sent By rmcdouga Date 2014-01-11 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2014-01-11 Time 10:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 18:21 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 18:21 Sent To  
Notes
2013-12-11 18:46:552010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF FLOOR PLANS WITH THE PRINTED
 NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. CITY AMENDMENTS 107.2.1
  
 2) LABEL THE ROOMS AND SHOW THE LOCATION OF THE SLIDING
 GLASS DOOR TO BE ELIMINATED AND THE AREAS WHERE THE
 DRYWALL IS TO BE PATCHED. CITY AMENDMENTS 107.2.1
  
 3) PROVIDE A DETAIL SHOWING HOW THE OPENING FOR THE
 SLIDING GLASS TO IS TO BE IN-FILLED. SPECIFY FRAMING
 MATERIAL, SIZE AND SPACING, ANCHORS AND CONNECTORS,
 INSULATION, INTERIOR WALL COVERING, EXTERIOR SHEATHING,
 WATER RESISTIVE BARRIER AND EXTERIOR WALL COVERING
 MATERIAL. CITY AMENDMENTS 107.2.1
  
 4) SHOW THAT THE MASTER BEDROOM WILL HAVE A REQUIRED
 EMERGENCY ESCAPE AND RESCUE OPENING AFTER THE SLIDING
 GLASS DOOR IS ELIMINATED. FBC R310.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-11 Cont ID  
Sent By rmcdouga Date 2014-01-11 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2014-01-11 Time 11:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 18:21 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 18:21 Sent To  
Notes
2013-12-11 18:39:532010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) SUBMIT TWO SETS OF ELECTRICAL FLOOR PLANS WITH THE
 PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. CITY AMENDMENTS
 107.2.1
  
 2) LABEL THE ROOMS AND SHOW THE LOCATIONS OF THE SMOKE
 ALARMS, RECEPTACLES, LIGHTING OUTLETS AND SWITCHES THAT
 WILL BE ADDED AND THE EXISTING ONES IN THESE AREAS.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-11 Cont ID  
Sent By rmcdouga Date 2014-01-11 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2014-01-04 Time 15:46 Sent To  
Notes
2014-01-04 15:47:02TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 19:05 Rev Time 0.00
Received By rmcdouga Date 2013-11-21 Time 16:10 Sent To  
Notes
2013-11-21 16:10:27R14
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 18:18 Sent To  
Notes
2013-12-11 18:19:07REPLACE FIXTURES IN THE SAME LOCATIONS. A PLUMBING
 SUB-CONTRACTOR IS REQUIRED.