Plan Review Details - Permit 13110691
Plan Review Stops For Permit 13110691
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2014-03-14 Cont ID  
Sent By shill Date 2014-03-14 Time 15:33 Rev Time 0.00
Received By shill Date 2014-03-14 Time 15:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-02-27 Cont ID  
Sent By shill Date 2014-02-27 Time 11:18 Rev Time 0.00
Received By shill Date 2014-02-27 Time 11:18 Sent To  
Notes
2014-02-27 11:19:25****PROVISO****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SUBMIT AN INSTALLATION SCHEDULE AS A REVISION FOR
 REVIEW PRIOR TO FIRST INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-02-22 Cont ID  
Sent By shill Date 2014-02-22 Time 10:38 Rev Time 0.00
Received By shill Date 2014-02-22 Time 10:38 Sent To  
Notes
2014-02-22 10:38:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 AN ATTEMPT WAS MADE TO REDLINE THE INSTALLATION
 SCHEDULE TO MAKE IT CONSISTENT WITH THE INFORMATION
 CIRCLED ON THE PRODUCT APPROVAL. HOWEVER, SOME OF THE
 DETAILS PROPOSED ARE IN CONFLICT WITH INFORMATION ON
 THE INSTALLATION SCHEDULE AND THE WRONG CHART WAS USED
 (WRONG SPAN).
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SHUTTER CONNECTION MOUNTING TYPE PROPOSED NOT CLEAR.
 TOP IS 6B, SEE SHEET 6, NO 6B. SECTION 6 IS FOR POURED
 CONCRETE, INSTALLATION SCHEDULE STATES TOP SUBSTRATE IS
 WOOD.
  
 **4TH REVIEW, ALT 1 WAS CIRCLED ON THE PRODUCT
 APPROVAL, BUT INSTALLATION SCHEDULE STILL PROPOSES SECT
 6B. PLEASE REVISE TO ALT 1.
  
 2. ANCHOR SPACING DOES NOT APPEAR TO COMPLY WITH
 REQUIREMENTS OF PRODUCT APPROVAL. 12", 1, TOP CIRCLED
 ON SHEET 5, 3" EDGE DISTANCE. SEE FACTOR CHART ON SHEET
 5; THIS REQUIRES A .35 FACTOR APPLIED TO THE ANCHOR
 SPACING (12" X .35). THIS CHART IS FOR CONCRETE
 SUBSTRATE, INSTALLATION SCHEDULE STATES TOP IS WOOD.
 PLEASE CORRELATE.
  
 **4TH REVIEW, ANCHOR SPACING TOP WAS CHANGED TO 6".
 FASTENER PROPOSED IS TAPCON, LAG SCREW REQUIRED FOR
 THIS CONNECTION TYPE. REVISE.
  
 **BOTTOM, SECTION 3 PROPOSED ON THE INSTALLATION
 SCHEDULE, SECTION 6 CIRCLED ON PRODUCT APPROVAL.
  
 **BOTTOM, 12" PROPOSED, BUT 11" CIRCLED ON THE PRODUCT
 APPROVAL.
  
 **BOTTOM, TAPCONS PROPOSED, CALK-IN CIRCLED ON PRODUCT
 APPROVAL.
  
 3. THE 8' OR LESS CHART WAS USED, SHEET 5, BUT THE SPAN
 STATED IS 110". SPAN SHOULD BE MEASURED ANCHOR TO
 ANCHOR, WHICH SHOULD BE 116" FOR A 110" OPENING WITH 3"
 EDGE DISTANCE TOP AND BOTTOM. REVISE.
  
 **RESPONSE FROM CONTRACTOR STATES - "WITH DESIGN
 PRESSURE SPAN IS 9'8" @ 117" SHUTTER SIZE 112". "
 PLEASE SEE ANCHOR CHART ON SHEET 5 OF 8. ITEMS CIRCLED
 WERE FOR 8'0" SPAN OR LESS. THE CHART UNDERNEATH THIS
 IS THE ANCHOR SPACING FOR 8'0" TO 9'8". IF SECTION 6
 BOTTOM IS PROPOSED, 8" ANCHOR SPACING IS REQUIRED. THE
 CHART USED BY CONTRACTOR IS FOR SPANS OF 96" AND LESS.
  
 CONTRACTOR IS REFERRING TO THE CHART ON SHEET 6 WHICH
 IS LIMITATIONS FOR VARIOUS TYPES OF TRACKS/MOUNTING.
 THE SPAN IS DETERMINED BY THE ACTUAL SIZE OF THE PANEL.
 ANCHOR SPACING DETERMINED BY SPAN OF PANEL (NOT SPAN
 ALLOWED BY DESIGN PRESSURE), CONNECTION TYPE AND
 FASTENER PROPOSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-02-09 Cont ID  
Sent By shill Date 2014-02-09 Time 13:33 Rev Time 0.00
Received By shill Date 2014-02-09 Time 13:33 Sent To  
Notes
2014-02-09 13:34:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE SAME INSTALLATION SCHEUDLE DATED 1/3 WAS SUBMITTED.
 ALL COMMENTS FROM PREVIOUS REVIEW WERE IN REGARDS TO
 THE INSTALLATIN SCHEDULE. AS SAME INFORMATION WAS
 RESUBMITTED, COMMENTS REMAIN THE SAME. FOR YOUR
 CONVENIENCE, THE COMMENTS ARE AS FOLLOWS:
  
 1. SHUTTER CONNECTION MOUNTING TYPE PROPOSED NOT CLEAR.
 TOP IS 6B, SEE SHEET 6, NO 6B. SECTION 6 IS FOR POURED
 CONCRETE, INSTALLATION SCHEDULE STATES TOP SUBSTRATE IS
 WOOD.
  
 2. ANCHOR SPACING DOES NOT APPEAR TO COMPLY WITH
 REQUIREMENTS OF PRODUCT APPROVAL. 12", 1, TOP CIRCLED
 ON SHEET 5, 3" EDGE DISTANCE. SEE FACTOR CHART ON SHEET
 5; THIS REQUIRES A .35 FACTOR APPLIED TO THE ANCHOR
 SPACING (12" X .35). THIS CHART IS FOR CONCRETE
 SUBSTRATE, INSTALLATION SCHEDULE STATES TOP IS WOOD.
 PLEASE CORRELATE.
  
 ALSO CIRCLED IS 11", 8, BOTTOM; 12" PROPOSED. IT
 APPEARS THAT, WITH A 3" EDGE DISTANCE, ANCHOR SPACING
 TO BE 11" X .35.
  
 3. THE 8' OR LESS CHART WAS USED, SHEET 5, BUT THE SPAN
 STATED IS 110". SPAN SHOULD BE MEASURED ANCHOR TO
 ANCHOR, WHICH SHOULD BE 116" FOR A 110" OPENING WITH 3"
 EDGE DISTANCE TOP AND BOTTOM. REVISE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-01-24 Cont ID  
Sent By shill Date 2014-01-24 Time 18:03 Rev Time 0.00
Received By shill Date 2014-01-24 Time 18:03 Sent To  
Notes
2014-01-24 18:10:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHUTTER CONNECTION MOUNTING TYPE PROPOSED NOT CLEAR.
 TOP IS 6B, SEE SHEET 6, NO 6B. SECTION 6 IS FOR POURED
 CONCRETE, INSTALLATION SCHEDULE STATES TOP SUBSTRATE IS
 WOOD.
  
 2. ANCHOR SPACING DOES NOT APPEAR TO COMPLY WITH
 REQUIREMENTS OF PRODUCT APPROVAL. 12", 1, TOP CIRCLED
 ON SHEET 5, 3" EDGE DISTANCE. SEE FACTOR CHART ON SHEET
 5; THIS REQUIRES A .35 FACTOR APPLIED TO THE ANCHOR
 SPACING (12" X .35). THIS CHART IS FOR CONCRETE
 SUBSTRATE, INSTALLATION SCHEDULE STATES TOP IS WOOD.
 PLEASE CORRELATE.
  
 ALSO CIRCLED IS 11", 8, BOTTOM; 12" PROPOSED. IT
 APPEARS THAT, WITH A 3" EDGE DISTANCE, ANCHOR SPACING
 TO BE 11" X .35.
  
 3. THE 8' OR LESS CHART WAS USED, SHEET 5, BUT THE SPAN
 STATED IS 110". SPAN SHOULD BE MEASURED ANCHOR TO
 ANCHOR, WHICH SHOULD BE 116" FOR A 110" OPENING WITH 3"
 EDGE DISTANCE TOP AND BOTTOM. REVISE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-03 Cont ID  
Sent By shill Date 2013-12-03 Time 18:36 Rev Time 0.00
Received By shill Date 2013-12-03 Time 18:36 Sent To  
Notes
2013-12-03 18:37:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEET, FAC9N-3.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-03-14 Cont ID  
Sent By shill Date 2014-03-14 Time 15:33 Rev Time 0.00
Received By shill Date 2014-02-28 Time 16:57 Sent To  
Notes
2014-03-04 16:58:05RESUBMITTAL SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-02-22 Cont ID  
Sent By shill Date 2014-02-22 Time 11:17 Rev Time 0.00
Received By shill Date 2014-02-22 Time 11:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-09 Cont ID  
Sent By shill Date 2014-02-09 Time 13:34 Rev Time 0.00
Received By shill Date 2014-01-31 Time 11:32 Sent To  
Notes
2014-01-31 11:32:59INCOMING SENT TO S. H. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-24 Cont ID  
Sent By shill Date 2014-01-24 Time 18:10 Rev Time 0.00
Received By shill Date 2014-01-06 Time 08:13 Sent To  
Notes
2014-01-07 08:14:01SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-03 Cont ID  
Sent By shill Date 2013-12-03 Time 18:37 Rev Time 0.00
Received By shill Date 2013-11-21 Time 10:36 Sent To  
Notes
2013-11-21 10:37:21ROUTED TO BLDG LESS THAN 5000