Plan Review Details - Permit 13110591
Plan Review Stops For Permit 13110591
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-05-01 Cont ID  
Sent By shill Date 2014-05-01 Time 12:27 Rev Time 0.00
Received By shill Date 2014-05-01 Time 12:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-02-09 Cont ID  
Sent By shill Date 2014-02-09 Time 13:41 Rev Time 0.00
Received By shill Date 2014-02-09 Time 13:41 Sent To  
Notes
2014-02-09 13:51:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 1. PRODUCT APPROVAL SUBMITTED IS ILLEGIBLE. THERE IS A
 LINE THROUGH FASTENER TYPE. ONLY ONE SET SUBMITTED.
 PROVIDE TWO LEGIBLE SETS OF PRODUCT APPROVALS. FBC 107.
  
 2. SEE SHEET 6, ANCHOR CHART. TAP CON CANNOT BE USED
 FOR WALL MOUNT TYPE 8.
  
 3. ALTHOUGH IT IS ACCEPTABLE TO EXCEED CODE COMPLIANCE,
 IT IS NOT CLEAR WHY A DP OF -76 HAS BEEN STATED FOR
 THIS JOB. -45.8 PSF IS WORST CASE FOR ZONE 4, 10SF,
 25'MRH. ZONE 5 WORST CASE, SAME CONDITIONS, IS -56.6.
 SEE FBC 2010 RESIDENTIAL TABLE 301.2(2) AND (3).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-01-24 Cont ID  
Sent By shill Date 2014-01-24 Time 18:14 Rev Time 0.00
Received By shill Date 2014-01-24 Time 18:14 Sent To  
Notes
2014-01-24 18:19:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. OK
  
 2. FROM PREVIOUS LIST: COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE (AVAILABLE IN THE LOBBY AND AT
 HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-19 Cont ID  
Sent By shill Date 2013-11-19 Time 17:46 Rev Time 0.00
Received By shill Date 2013-11-19 Time 17:46 Sent To  
Notes
2013-11-19 17:51:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-09 Cont ID  
Sent By shill Date 2014-02-09 Time 13:51 Rev Time 0.00
Received By shill Date 2014-01-31 Time 11:33 Sent To  
Notes
2014-01-31 11:37:11INCOMING SENT TO S. H. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-24 Cont ID  
Sent By shill Date 2014-01-24 Time 18:22 Rev Time 0.00
Received By shill Date 2014-01-07 Time 17:34 Sent To  
Notes
2014-01-07 17:35:16INCOMING SENT TO S HILL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-19 Cont ID  
Sent By shill Date 2013-11-19 Time 17:51 Rev Time 0.00
Received By shill Date 2013-11-18 Time 16:23 Sent To  
Notes
2013-11-18 16:23:14BLDG LESS THAN 5000