Plan Review Details - Permit 13110586
Plan Review Stops For Permit 13110586
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-27 Cont ID  
Sent By jgomez Date 2014-01-24 Time 16:08 Rev Time 0.00
Received By jgomez Date 2014-01-24 Time 16:08 Sent To  
Notes
2014-01-24 16:11:57BUILDING REVIEW APPROVED WITH PROVISO;
  
 1- PROVIDE COMPLETE MANUFACTURER'S SPECS FOR OUTDOOR
 KITCHEN BBQ DESIGNED TO BE INSTALLED IN PORCH AS SHOWN
 ON PLANS. SEC. M1901.2 AND G2408.1 OF 2010
 FBC-RESIDENTIAL.
  
 2- PROVIDE DRAINAGE PLAN. SEC. R401.3
  
 3- SHEET S-5. UPDATE THE FLORIDA PRODUCT APPROVAL
 NUMBERS FOR ALL SIMPSON STRUCTURAL CONNECTORS. ALL
 PRODUCTS NEED TO BE APPROVED FOR 2010 FBC VERSION.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOOR SIZE AS SHOWN ON PLANS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-26 Cont ID  
Sent By jgomez Date 2013-12-19 Time 16:10 Rev Time 0.00
Received By jgomez Date 2013-12-19 Time 16:03 Sent To  
Notes
2013-12-19 16:12:00NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PLANS NEED TO SPECIFY A BATHROOM LOCATED WITH
 MAXIMUM POSSIBLE PRIVACY WITH A DOOR THAT HAS A 29"
 CLEAR OPENING AS REQUIRED BY SEC. R320 OF 2010
 FBC-RESIDENTIAL.
  
 2- PROVIDE MANUFACTURER'S SPECS FOR OUTDOOR KITCHEN BBQ
 DESIGNED TO BE INSTALLED IN PORCH AS SHOWN ON PLANS.
 SEC. M1901.2 AND G2408.1 OF 2010 FBC-RESIDENTIAL.
  
 3- TYPICAL WALL SECTION ON SHEET A801:
 A) SPECIFY 12" MIN. FOOTING DEPTH AS REQUIRED BY SEC.
 R403.1.4. REVISE AS REQUIRED.
  
 B) SPECIFY THE MINIMUM FOOTING HEIGHT ABOVE FINISHED
 GRADE AS REQUIRED BY SEC. R404.1.6.
  
 C) CONCRETE ROOF TILE: SPECIFY NAIL TYPE, SIZE AND
 NUMBER AS REQUIRED BY SEC. 107.2.1.2 OF CITY AMENDMENTS
 TO FBC.
  
 4- VALUATION UPDATED AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. THE PERMIT FEE BALANCE IS $11,992.60.
  
 5- SHEET A901: REVISE ALL WINDOW AND DOOR STRUCTURAL
 BUCK DETAILS. BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE
 WINDOW/DOOR FRAME AS REQUIRED BY SEC. R612.10.2.1.
  
 6- PROVIDE DRAINAGE PLAN. SEC. R401.3
  
 7- SHEET S-2: REVISE THE WIND PRESSURES ON OPENINGS.
 SEC. R301. *(A) SPECIFY WHERE ARE THE A, B AND C ZONES.
 **(B) INFORMATION ON THIS PAGE DOESN'T MATCH
 INFORMATION SHOWN ON STRUCTURAL NOTES ON SHEET S-4.
 ***C) WHY THE DESIGN PRESSURES FOR ZONE B AND C ARE THE
 SAME?. ****(D) SPECIFY THE ULTIMATE WIND SPEED AND THE
 NOMINAL WIND SPEED. COORDINATE WITH ITEM #9 BELOW.
  
 8- SHEET S-3: REVISE FOOTING DEPTH TO COMPLY WITH ITEM
 #3(A) AND #3(B) ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET S-4:
 *(A) DESIGN PRESSURES FOR THE ROOF COMPONENT AND
 CLADDING DESIGN PRESSURES ARE TOO LOW. PROVIDE
 CALCULATIONS. COORDINATE WITH ITEM #7 ABOVE. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 **(B) REVISE ALL DOORS AND WINDOWS STRUCTURAL BUCK
 DETAILS. NEED TO SPECIFY BUCK FASTENING. AND, BUCK NEED
 TO PROVIDE FULL SUPPORT TO THE DOOR/WINDOW FRAME AS
 REQUIRED BY SEC. R612.10.2.1. ***NOTE: COORDINATE WITH
 ITEM #5 ABOVE. SEC. R612.10.2.1.
  
 ***(C) SPECIFY FASTENING FOR GARAGE DOOR STRUCTURAL
 BUCK. SEC. R301.1.
  
 10- SHEET S-5. REVISE THE DESIGN PRESSURES SHOWN ON THE
 ROOF WIND ZONE DIAGRAM. COORDINATE WITH ITEM #9(A)
 ABOVE. SEC. R301.
  
 11- ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN
 CREDITS. SHOW ON PLANS CEILING FANS ON ALL ROOMS
 (INCLUDING THE LIVING AREA AND LIBRARY) AND SIZES AS
 REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 12- REVISE ENERGY CALCULATIONS SUBMITTED. SEC.
 103.2.1.1.1 OF 2010 FBC-ENERGY CONSERVATION.
 A) HOT WATER SYSTEM IS NOT ELECTRIC. SEE PLANS.
 B) THERE ARE NOT WOOD DOORS. SEE PLANS AND PRODUCT
 APPROVALS SUBMITTED.
 C) PROVIDE CORRECT NAME OF BUILDER.
 D) PERMIT OFFICE IS WEST PALM BEACH, NOT PALM BEACH
 COUNTY.
 E) JURISDICTION NUMBER IS 604700, NOT 601000.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A)ALUMINUM FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA.
 B) LARGE FIXED WINDOWS SHOWN ON THE LIVING AREA. (4'-0"
 X 11'-0"). SEE PLANS.
 C) ALUMINUM CASEMENT WINDOWS NOA 11-1110.18 SUBMITTED
 EXPIRED ON MAY 22, 2013. NEED CURRENT NOA.
 D) ALUMINUM MULLIONS. NOA 11-0922.01 WAS SUPERSEDED BY
 MIAMI-DADE. NEED CURRENT NOA. AND, CLEARLY SPECIFY
 MULLION SIZES TO BE USED (SPECIALLY THOSE SHOWN ON
 LIVING AREA LARGE WINDOWS) TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES.
 E) ENTRY DOOR SIZE AS SHOWN ON PLANS.
 F) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. ALL FLORIDA PRODUCT APPROVAL
 NUMBER SHOWN ON PLANS NEED TO BE UPDATED TO THE CURRENT
 2010 FBC.
 G) PRECAST LINTELS AS SHOWN ON PLANS.
 H) 16'-0" WIDE GARAGE DOORS. ONLY DRAWINGS FOR 9'-0"
 GARAGE DOORS WERE SUBMITTED.
  
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 15-CLARIFY WHY SUBMITTING PRODUCT APPROVALS FOR SINGLE
 HUNG WINDOWS. PLANS DON'T SHOW ANY SINGLE HUNG WINDOWS.
 (SINGLE HUNG WINDOWS MAY NOT COMPLY WITH BEDROOM EGRESS
 WINDOWS. THAT'S WHY IS IMPORTANT TO CLARIFY). SEC.
 107.2.1 CITY AMENDMENTS.
  
 16- NEED TO SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
2013-12-12 15:47:53BIN R19

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-12 Cont ID  
Sent By albarran Date 2013-12-12 Time 15:39 Rev Time 0.00
Received By albarran Date 2013-12-12 Time 14:48 Sent To B
Notes
2013-12-12 15:47:22THIS APPLICATION IS CONDITIONALLY APPROVED PROVIDED
 THAT COMPLIANCE WITH THE HEREIN DESCRIBED IS OBSERVED:
 1. AS PER NEC 680.71, THE OUTLET FOR THE HYDROMASSAGE
 TUB SHALL BE GFCI PROTECTED.
 2. AS PER FBC-R315, CARBON MONOXIDE DETECTORS SHALL BE
 INSTALLED
 3. THOUGH NOT INDICATED ON THE DRAWINGS, COMPLIANCE
 WITH FBC-E404.1 SHALL BE REQUIRED.
 4. ALL WORK SHALL COMPLY WITH ALL THE REQUIREMENTS OF
 THE 2008 EDITION OF THE NEC AND BE SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 THE SUBMITTED DRAWINGS ARE VERY DIFFICULT TO
 UNDERSTAND, THEREFORE ADDITIONAL REQUIRED ITEMS MAY
 HAVE BEEN MISSED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-27 Cont ID  
Sent By jgomez Date 2014-01-27 Time 13:39 Rev Time 0.00
Received By jgomez Date 2014-01-13 Time 17:30 Sent To  
Notes
2014-01-13 17:31:06INCOMING SENT J GOMEZ DESK. BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-26 Cont ID  
Sent By jgomez Date 2013-12-26 Time 16:03 Rev Time 0.00
Received By jgomez Date 2013-11-19 Time 09:02 Sent To  
Notes
2013-11-19 09:02:25R19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-12-19 Cont ID  
Sent By jgomez Date 2013-12-19 Time 16:52 Rev Time 0.00
Received By jgomez Date 2013-12-19 Time 16:52 Sent To  
Notes
2013-12-19 16:53:13MU-2013-024456. $8608.60. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-01-29 Cont ID  
Sent By jgomez Date 2014-01-29 Time 10:01 Rev Time 0.00
Received By jgomez Date 2014-01-27 Time 10:01 Sent To  
Notes
2014-01-29 12:56:581/28/14 SECOND COPY OF A/C PLAN AND LOAD CALCULATIONS
 SUBMITTED BY SHELDON. JG.
2014-01-27 10:01:37NEED 2 COPIES OF A/C PLAN AND LOAD CALCULATIONS. ONLY
 ONE SUBMITTED AT THIS TIME. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-27 Cont ID  
Sent By jgomez Date 2013-12-26 Time 16:02 Rev Time 0.00
Received By jgomez Date 2013-12-26 Time 16:02 Sent To  
Notes
2013-12-26 16:02:57NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- CLARIFY WHY SUBMITTING TWO DIFFERENT EQUIPMENT
 SIZING CALCULATIONS. PROVIDE ONLY ONE. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 2- CALCULATIONS DONE BY APOLLO AIR:
 A) EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS SUBMITTED DON'T MATCH EQUIPMENT SHOWN ON
 THE A/C PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) REVISE DESIGN DATA ON PAGE 2. THE REFERENCE CITY IS
 WEST PALM BEACH, NOT FORT LAUDERDALE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- MECHANICAL PLAN SUBMITTED:
 A) PERSON RESPONSIBLE FOR THE DESIGN NEED TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 B) REVISE GENERAL MECHANICAL NOTE #6. DOOR NEEDS AT
 LEAST 1", NOT 3/4" UNDERCUT AS REQUIRED BY SEC. M1602.4
 OF 2010 FBC-RESIDENTIAL.
  
 C) NEED AT LEAST 12" TRANSFER DUCT SIZE FOR GUEST SUITE
 AS REQUIRED BY SEC. M1602.4. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-27 Cont ID  
Sent By jgomez Date 2014-01-27 Time 13:19 Rev Time 0.00
Received By jgomez Date 2014-01-27 Time 13:19 Sent To  
Notes
2014-01-27 13:39:19PLUMBING REVIEW APPROVED WITH PROVISO;
  
 1- PROVIDE COMPLETE AND CORRECT PLUMBING RISER DIAGRAM.
 NEED DIAGRAM THAT MATCHES FLOOR LAYOUT. MISSING THE BAR
 SINK. VENTING FOR BATHROOM #3 IS INCORRECT. CLOTHES
 WASHER DISCHARGE IS INCORRECT. MASTER BATH WATER
 CLOSET, BIDET AND LAVATORY DISCHARGE IS NOT CLEAR THE
 WAY IS SHOWN. REVISE COMPLETE PLUMBING RISER DIAGRAM AS
 REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-12-27 Cont ID  
Sent By jgomez Date 2013-12-26 Time 16:03 Rev Time 0.00
Received By jgomez Date 2013-12-26 Time 16:03 Sent To  
Notes
2013-12-26 16:03:22NEW SINGLE FAMILY RESIDENCE (R3), PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM TO MATCH ACTUAL FLOOR
 PLAN LAYOUT. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- REVISE CLOTHES WASHER DISCHARGE. APPLIANCES WITH
 PUMPING ACTION DISCHARGE CAN'T BE CONNECTED AS SHOWN.
 SEC. P3005.1.1 OF 2010 FBC-RESIDENTIAL.
  
 3- SOME FIXTURES ARE MISSING THE DRAIN PIPE SIZE.
 SPECIFY THE DRAIN SIZE OF EACH FIXTURE AS REQUIRED BY
 SEC. P3005.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-12-27 Cont ID  
Sent By jgomez Date 2013-12-26 Time 16:03 Rev Time 0.00
Received By jgomez Date 2013-12-26 Time 16:03 Sent To  
Notes
2013-12-26 16:03:41PRODUCT APPROVALS SUBMITTED:
 A) ROOF TILE: FL3505-R5.
 B) METAL RIDGE SYSTEM: FL8095-R2.
 C) ROF TILE ADHESIVE: FL6332-R4.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-12-04 Cont ID  
Sent By dkittred Date 2013-11-26 Time 09:37 Rev Time 0.00
Received By dkittred Date 2013-11-25 Time 08:31 Sent To  
Notes
2014-09-08 08:16:509/8/14 - APPLICANT HAS SUBMITTED AND RECEIVED APPROVAL
 FOR A LANDSCAPE PERMIT (14090152). DK
2013-12-04 09:57:23***SPECIFIC CONDITIONS APPLY SEE ZONING PROVISO***
 12/4/13
 APPLICANT HAS CONDITIONAL APPROVAL. PRIOR TO C.O. BEING
 ISSUED FOR 7290 WINDING BAY LANE SFR LANDSCAPE AND
 IRRIGATION PERMIT IS REQUIRED AND INSTALLATION SHALL
 PASS FINAL INSPECTION. (DK)
  
  
2013-11-26 09:37:08PLANNING & ZONING COMMENTS: ***FAILED***
  
 11/26/13
 1. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED. NOTE: ZLDR SEC.
 94-442(B)(2)A. ? FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF. PLEASE NOTE THAT
 THE DEFINITION OF OPEN SPACE 'MEANS AN OPEN, UNENCLOSED
 AREA CONSISTING OF SETBACKS, LANDSCAPING, BUFFERS,
 VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES, AND
 SURFACE PARKING.'
  
 2. DRIVEWAY WIDTHS STILL UNDER REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-11-22 14:50:3311/22/13