Plan Review Details - Permit 13110579
Plan Review Stops For Permit 13110579
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-21 Cont ID  
Sent By skennedy Date 2014-01-21 Time 10:19 Rev Time 0.00
Received By skennedy Date 2014-01-21 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-09 Cont ID  
Sent By skennedy Date 2013-12-09 Time 10:17 Rev Time 0.00
Received By skennedy Date 2013-12-09 Time 09:59 Sent To  
Notes
2013-12-09 10:18:19PROVIDE RISER DIAGRAM AND WIRING DETAILS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-01-09 Cont ID  
Sent By wjolin Date 2014-01-09 Time 17:28 Rev Time 0.00
Received By wjolin Date 2014-01-09 Time 17:28 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-30 Cont ID  
Sent By wjolin Date 2013-11-30 Time 19:49 Rev Time 0.00
Received By wjolin Date 2013-11-30 Time 19:27 Sent To E
Notes
2013-11-30 19:49:41550 SOUTH ROSEMARY AVENUE - SUITE #250
 PERMIT #13110579
 MASTER #12100361
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS INDICATE "ALL DEVICES WERE REMOVED IN THE
 DEMOLITION AND THEY WILL BE REINSTALLED." FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SHEET FA-1 OF THE ENGINEERED FIRE ALARM CONSTRUCTION
 DOCUMENTS INDICATE THE CONTRACTOR SHALL PROVIDE BATTERY
 CALCULATIONS AND RISER DIAGRAM; NEITHER OF WHICH WERE
 PROVIDED.
  
 SHEET FA-1 OF THE ENGINEERED FIRE ALARM CONSTRUCTION
 DOCUMENTS INDICATE THAT THE FIRE ALARM SYSTEM SHALL BE
 INTERFACED WITH THE SOUND SYSTEM SO THAT THE SOUND
 SYSTEM IS DEACTIVATED UPON ACTIVATION OF THE FIRE ALARM
 SYSTEM.
  
 SUBMIT A SIGNED COPY OF THE CONTRACT. THE TOTAL PERMIT
 JOB VALUE SHALL INCLUDE MATERIALS AND LABOR.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-21 Cont ID  
Sent By skennedy Date 2014-01-21 Time 10:19 Rev Time 0.00
Received By skennedy Date 2014-01-03 Time 16:51 Sent To  
Notes
2014-01-03 16:51:16TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-09 Cont ID  
Sent By skennedy Date 2013-12-09 Time 10:18 Rev Time 0.00
Received By skennedy Date 2013-11-30 Time 19:27 Sent To  
Notes
2013-11-18 14:16:01ROUTED TO FIRE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved