Plan Review Details - Permit 13110526
Plan Review Stops For Permit 13110526
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-16 Cont ID  
Sent By rmcdouga Date 2013-11-16 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2013-11-15 Time 15:21 Sent To  
Notes
2013-11-15 15:23:57TO RM DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-11-16 Cont ID  
Sent By rmcdouga Date 2013-11-16 Time 06:35 Rev Time 0.00
Received By rmcdouga Date 2013-11-16 Time 06:35 Sent To  
Notes
2013-11-16 08:02:592010 FBC
  
 MECHANICAL REVISION IS DENIED
  
 1) THE PERMIT FOR THIS DWELLING WAS ISSUED UNDER A
 MASTERED PROJECT BY THE CITY OF WEST PALM BEACH HOUSING
 AND COMMUNITY DEVELOPMENT DEPARTMENT. ANY CHANGES TO
 THE PLANS FOR A SPECIFIC SITE WILL ONLY APPLY TO THAT
 SITE AND NEEDS TO BE APPROVED IN WRITING BY THE HCD
 DEPARTMENT.
  
 2) THE PLANS THAT WERE SUBMITTED ARE NOT ACCEPTABLE.
 THEY ARE NOT OF A SUFFICIENT QUALITY OR CLARITY TO BE
 FILED FOR PUBLIC RECORD. CITY AMENDMENTS 107.2.1.4
  
 3) THE PLANS THAT WERE SUBMITTED ARE THE PROPERTY OF
 REG ARCHITECTS AS INDICATED BY THE TITLE BLOCK AND CAN
 NOT BE USED WITHOUT THEIR PERMISSION. FLORIDA STATUTES
 481
  
 4) THE APPROVED MASTERED MECHANICAL PLANS CONSIST OF
 TWO SHEETS OF DRAWINGS THAT WERE DESIGNED, SIGNED AND
 SEALED BY MICHAEL A. BASSFORD A FLORIDA PROFESSIONAL
 ENGINEER. IN ORDER FOR A NEW DESIGNER TO REVISE THE
 PLANS THEY TAKE THE DESIGN RESPONSIBILITY FOR THE
 MECHANICAL SYSTEM. THE NEW DESIGNER SHALL SUBMIT HIS
 OWN DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA
 WHICH SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. IF THE DESIGNER IS A
 FLORIDA LICENSED ENGINEER OR ARCHITECT THE DRAWINGS ARE
 REQUIRED TO BE SIGNED, SEALED AND DATED. IF THE
 DESIGNER IS AN A/C OR MECHANICAL CONTRACTOR LICENSED
 UNDER FS 489 IN ACCORDANCE WITH THE PROVISIONS FS
 471.003 (2) (H) 1 C IS REQUIRED TO HAVE THEIR LICENSE
 NUMBER, PRINTED NAME AND SIGNATURE ON THE DRAWINGS. FS
 471, 481 AND CITY AMENDMENTS 107.2
  
 5) SPECIFY IF THE A/H IS LOCATED IN THE ATTIC OR NOT.
 CITY AMENDMENTS 107.2.1 IF IT IS SHOW THAT IT COMPLIES
 WITH M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 EXCEPTION: THE PASSAGEWAY AND LEVEL SERVICE SPACE ARE
 NOT REQUIRED WHERE THE APPLIANCE CAN BE SERVICED AND
 REMOVED THROUGH THE REQUIRED OPENING.
  
 6) THE DUCT SYSTEM SHOWN DOES NOT COMPLY WITH M1602.4
 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
  
 EXCEPTIONS:
  
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 7) CLEARLY SPECIFY THE SIZES OF ALL SUPPLY/RETURN DUCTS
 AND GRILLS ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]