Plan Review Details - Permit 13110522
Plan Review Stops For Permit 13110522
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2014-02-28 Time 06:44 Sent To Z
Notes
2014-02-28 08:52:072/27/14 ZONING RECEIVED RSUB. SENT TO JR.SG
2014-02-28 06:45:49THIS HAS NOT BEEN COMPLETED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-02-23 Cont ID  
Sent By jwitmer Date 2014-02-23 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2014-02-23 Time 07:43 Sent To  
Notes
2014-02-23 07:44:17NOTE THIS DOCUMENT CAME IN AS A REVISION TO 12110274, J
 ROACH CORRECTED, IT IS A RESUBMITTAL TO DENIED PERMIT
 13110522, PLEASE CORRECT FOR FUTURE RESUBMITTALS. SUN.
 2/23/2014 JW
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-12-02 Cont ID  
Sent By jwitmer Date 2013-12-02 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2013-12-02 Time 07:04 Sent To  
Notes
2013-12-02 10:15:18PLANS TO BE STAMPED ONCE APPROVED BY ZONING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 12/02/2013
 I SPOKE WITH PE PHILIP RIZZO OK TO RED LINE PLANS:
 2004 FBC TO 2010 FBC
 WIND SPEED 140 MPH TO 160 MPH 3 SECOND GUST BUILDING
 CATEGORY I
  
 NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOFING,
 ROOFING TO BE SUBMITTED UNDER SEPERATE PERMIT.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-30 Cont ID  
Sent By albarran Date 2014-01-30 Time 19:42 Rev Time 0.00
Received By albarran Date 2014-01-30 Time 17:22 Sent To I
Notes
2014-01-30 19:43:32ELECTRICAL PROVISO:
 AS PER NEC 110.16, ALL PANELS SHALL HAVE FLASH
 PROTECTION WARNING DECALS.
 AS PER NEC 210.8(B), ALL OUTDOOR RECEPTACLES SHALL BE
 GFI PROTECTED.
 AS PER NEC 406.8(B), IN ADDITION TO THE IN-USE COVERS,
 THE ACTUAL DEVICE SHALL BE LISTED AS WEATHER RESISTANT.
 ALL LOW VOLTAGE AND/OR COMMUNICATION WIRING SHALL BE
 LISTED FOR THE APPLICATION.
 ALL WORK TO COMPLY W/2008 EDITION OF NEC
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-18 Cont ID  
Sent By skennedy Date 2014-03-04 Time 16:04 Rev Time 0.00
Received By skennedy Date 2014-02-27 Time 06:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2014-02-23 Cont ID  
Sent By jwitmer Date 2014-02-23 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2014-02-10 Time 07:44 Sent To  
Notes
2014-02-23 07:47:47NOTE THIS DOCUMENT CAME IN AS A REVISION TO 12110274, J
 ROACH CORRECTED, IT IS A RESUBMITTAL TO DENIED PERMIT
 13110522, PLEASE CORRECT FOR FUTURE RESUBMITTALS. SUN.
 2/23/2014 JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-31 Cont ID  
Sent By skennedy Date 2014-01-31 Time 08:06 Rev Time 0.00
Received By skennedy Date 2013-11-15 Time 13:50 Sent To  
Notes
2014-01-30 19:44:22SH DESK
2013-11-15 13:55:51C20

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-12-02 Cont ID  
Sent By jwitmer Date 2013-12-02 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2013-12-02 Time 10:15 Sent To  
Notes
2013-12-02 10:15:36NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOFING,
 ROOFING TO BE SUBMITTED UNDER SEPERATE PERMIT.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop Z ZONING
Rev No 3 Status P Date 2014-03-04 Cont ID  
Sent By jroach Date 2014-03-04 Time 14:49 Rev Time 0.00
Received By jroach Date 2014-03-04 Time 14:49 Sent To  
Notes
2014-03-03 15:10:053/3/14
2014-02-28 08:56:342/28/14 ZONING RECEIVED. SENT TO JR. SG

Review Stop Z ZONING
Rev No 2 Status F Date 2013-11-26 Cont ID  
Sent By jroach Date 2013-11-26 Time 14:24 Rev Time 0.00
Received By jroach Date 2013-11-26 Time 14:24 Sent To  
Notes
2013-11-26 14:25:03ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.26.2013
 PERMIT NO.: 13110522
 ADDRESS: 3401 PARKER AVENUE
 CONTRACTOR/CONTACT: BRIAN FRENCH
 TELEPHONE NO.: 561.301.8245
 SCOPE OF REVIEW: ATHLETIC FIELDS AT PBAU ATHLETIC
 CAMPUS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PHASES 8 AND 9 OF THE LANDSCAPE PHASING PLAN SHALL
 BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. THE
 APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF
 SIGNED/SEALED PLANS, AS WELL AS A CERTIFIED COST
 ESTIMATE (LABOR + MATERIAL). ALL LANDSCAPING WITHIN
 THESE PHASES SHALL BE INSTALLED PRIOR TO THE ISSUANCE
 OF A CERTIFICATE OF OCCUPANCY / COMPLETION FOR THE
 PROPOSED SCOPE OF WORK.
  
 2. THE PLANS ARE UNCLEAR AS TO WHAT IS INCLUDED WITHIN
 THIS APPLICATION. THE PLANS PROVIDE DETAILS REGARDING
 FIELD LAYOUT, ETC. IT IS MY UNDERSTANDING THAT HEDRICK
 BROTHERS WILL NOT BE COMPLETING THIS PORTION OF THE
 PROJECT. THE PLANS NEED TO ACCURATELY REFLECT WHAT IS
 PROPOSED BY THIS PERMIT APPLICATION. IS THE FENCING
 SURROUNDING THE BASEBALL / SOFTBALL FIELDS INCLUDED?
 ARE THE SCOREBOARDS INCLUDED?
  
 3. THE BIKE RACKS ADJACENT TO THE SOFTBALL FIELDS NEED
 TO BE INSTALLED AS PART OF THE PROPOSED SCOPE OF WORK.
 PLEASE PROVIDE A DETAIL OF THE PROPOSED RACK. YOU MAY
 CONTACT ME VIA EMAIL FOR STANDARD BIKE RACKS THAT ARE
 ACCEPTED BY THE CITY.
  
 4. PERMIT PACKAGE INCLUDES A SITE LIGHTING PLAN. ARE
 ADDITIONAL LIGHTS BEING INSTALLED? IT IS MY
 UNDERSTANDING THAT A PERMIT WAS ALREADY ISSUED FOR THE
 INSTALLATION OF ALL OF THE LIGHT POLES / FIXTURES. IF
 THIS IS NOT THE CASE, OR ADDITIONAL LIGHTS ARE BEING
 INSTALLED, A PHOTOMETRIC PLAN SHALL BE PROVIDED. PLEASE
 NOTE THAT PHOTOMETRIC LEVELS SHALL NOT EXCEED 0.5
 FOOTCANDLES WHEN MEASURE IN THE ADJACENT RESIDENTIAL
 ZONING DISTRICT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
 11/19/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-11-26 Cont ID  
Sent By jroach Date 2013-11-26 Time 09:41 Rev Time 0.00
Received By jroach Date 2013-11-26 Time 09:41 Sent To  
Notes
2013-11-26 09:41:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.26.2013
 PERMIT NO.: 13110522
 ADDRESS: 3401 PARKER AVENUE
 CONTRACTOR/CONTACT: BRIAN FRENCH
 TELEPHONE NO.: 561.301.8245
 SCOPE OF REVIEW: ATHLETIC FIELDS AT PBAU ATHLETIC
 CAMPUS
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPOSED SCOPE OF WORK WAS SUBMITTED AS A
 REVISION TO AN EXISTING BUILDING PERMIT (MAINTENANCE
 BUILDING). THIS IS NOT RECOMMENDED AS ALL OF THE
 ADDITIONAL WORK WILL HAVE TO BE COMPLETED BEFORE THE
 MAINTENANCE BUILDING COULD BE CLOSED OUT. IT IS
 SUGGESTED THAT THE ADDITIONAL SCOPE BE SUBMITTED AS A
 SEPARATE PERMIT APPLICATION.
  
 2. PHASES 8 AND 9 OF THE LANDSCAPE PHASING PLAN SHALL
 BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. THE
 APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF
 SIGNED/SEALED PLANS, AS WELL AS A CERTIFIED COST
 ESTIMATE (LABOR + MATERIAL). ALL LANDSCAPING WITHIN
 THESE PHASES SHALL BE INSTALLED PRIOR TO THE ISSUANCE
 OF A CERTIFICATE OF OCCUPANCY / COMPLETION FOR THE
 PROPOSED SCOPE OF WORK.
  
 3. THE PLANS ARE UNCLEAR AS TO WHAT IS INCLUDED WITHIN
 THIS APPLICATION. THE PLANS PROVIDE DETAILS REGARDING
 FIELD LAYOUT, ETC. IT IS MY UNDERSTANDING THAT HEDRICK
 BROTHERS WILL NOT BE COMPLETING THIS PORTION OF THE
 PROJECT. THE PLANS NEED TO ACCURATELY REFLECT WHAT IS
 PROPOSED BY THIS PERMIT APPLICATION. IS THE FENCING
 SURROUNDING THE BASEBALL / SOFTBALL FIELDS INCLUDED?
 ARE THE SCOREBOARDS INCLUDED?
  
 4. THE BIKE RACKS ADJACENT TO THE SOFTBALL FIELDS NEED
 TO BE INSTALLED AS PART OF THE PROPOSED SCOPE OF WORK.
 PLEASE PROVIDE A DETAIL OF THE PROPOSED RACK. YOU MAY
 CONTACT ME VIA EMAIL FOR STANDARD BIKE RACKS THAT ARE
 ACCEPTED BY THE CITY.
  
 5. PERMIT PACKAGE INCLUDES A SITE LIGHTING PLAN. ARE
 ADDITIONAL LIGHTS BEING INSTALLED? IT IS MY
 UNDERSTANDING THAT A PERMIT WAS ALREADY ISSUED FOR THE
 INSTALLATION OF ALL OF THE LIGHT POLES / FIXTURES. IF
 THIS IS NOT THE CASE, OR ADDITIONAL LIGHTS ARE BEING
 INSTALLED, A PHOTOMETRIC PLAN SHALL BE PROVIDED. PLEASE
 NOTE THAT PHOTOMETRIC LEVELS SHALL NOT EXCEED 0.5
 FOOTCANDLES WHEN MEASURE IN THE ADJACENT RESIDENTIAL
 ZONING DISTRICT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2013-11-19 10:37:2011/19/13