2013-12-10 06:11:11COMMENTS:
  
 #1 TAPP TO CITY OF WEST PALM BEACH WATERMAIN FOR
 FIRELINE WILL REQUIRE A SEPARATE SUBMITTAL TO
 ENGINEERING SERVICES.
  
 GO TO
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 SUBMIT USING ROW PEMIT APPLICATION FORM. TYPE B)
 UTILITY SERVICE MAINTENANCE / CONSTRUCTION PERMIT
 APPLICATION.
 ALL PERMIT APPLICATIONS PROPOSING VEHICULAR /
 PEDESTRIAN OBSTRUCTIONS SHALL INCLUDE A PROFESSIONALLY
 PREPARED MAINTENANCE OF TRAFFIC PLAN (MOT). ALL
 CONSTRUCTION
 DRAWINGS SHALL BE SEALED BY A FLORIDA LICENSED
 PROFESSIONAL ENGINEER AND/OR REGISTERED LANDSCAPE
 ARCHITECT. MINIMUM PLAN DRAWING SIZE SHALL BE 11? X17?,
 MAXIMUM SIZE
 SHALL BE 24? X 36?.
  
 FOR REFERENCE GO TO:"STANDARDS FOR CONSTRUCTION AND USE
 OF PUBLIC RIGHTS-OF-WAY AND EASEMENTS" HAVE BEEN
 DEVELOPED AND COMPILED
 BY THE ENGINEERING SERVICES DEPARTMENT OF THE CITY OF
 WEST PALM BEACH, FLORIDA. THE CREATION OF THIS MANUAL
 HAS BEEN
 AUTHORIZED BY ORDINANCE NUMBER 4198-09, ADOPTED BY THE
 CITY COMMISSION ON MARCH 9, 2009.
  
 FOR QUESTIONS CONTACT:
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-30 Cont ID  
Sent By wjolin Date 2013-11-30 Time 19:24 Rev Time 0.00
Received By wjolin Date 2013-11-30 Time 18:58 Sent To ENG
Notes
2013-11-30 19:24:101700 NORTH DIXIE HIGHWAY
 PERMIT #13110504
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE JOB VALUE OF $2500 APPEARS IS LOW. THE TOTAL PERMIT
 JOB VALUE SHALL INCLUDE MATERIALS AND LABOR. SUBMIT A
 SIGNED COPY OF THE CONTRACT.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE CHAIN WITH LOCK (AND TAMPER SWITCHES) FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 NOTE: SEPARATE UNDERGROUND FIRELINE PERMIT WILL BE
 NEEDED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-12 Cont ID  
Sent By hmoser Date 2013-12-12 Time 10:41 Rev Time 0.00
Received By hmoser Date 2013-11-14 Time 16:31 Sent To  
Notes
2013-11-14 16:31:39ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-12 Cont ID  
Sent By hmoser Date 2013-12-12 Time 10:36 Rev Time 0.00
Received By hmoser Date 2013-12-12 Time 10:36 Sent To  
Notes
2013-12-12 10:40:56PLAN DENIED
 VALUE IS TO LOW . PROVIDE A CONTRACT WITH OWNERS
 SIGNATURE.